Plan Review Details - Permit 99122120
Plan Review Stops For Permit 99122120
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-08-08 Cont ID  
Sent By dpalmer Date 2000-08-08 Time 12:38 Rev Time 0.00
Received By dpalmer Date 2000-08-08 Time 12:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-02-01 Cont ID  
Sent By dpalmer Date 2000-02-01 Time 14:01 Rev Time 0.00
Received By dpalmer Date 2000-02-01 Time 14:00 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT ****************
  
 1)NOTE: NEED TO SUBMIT AIC RATING OF
 EQUIPMENTMAINS. RATING NEEDS TO BE
 ABLE TO HANDLE AVAILABLE FAULT CURRENT.
 110-9/230-65
  
 2))NOTE:SHOW DISCONNECTS REQ`D FOR A/C
 PER 440-11
  
 3)NOTE: MASTER BEDROOM NEEDS TO HAVE
 MEANS OF EGRESS LIGHTING AS PER 210-70A
 AN ALSO FROM FAMILY ROOM GOING OUTSDIE.
  
 4)NOTE:NEED TO CHECK FOR KITCHEN PENIN-
 SULAR REQ`D RECEPT.PER 210-52-C
  
 5)NOTE: ALL OUTLETS SERVING KITCHEN
 COUNTERSPACE ARE TO BE GFI/GFI PROTECT-
 ED. AS PER 210-8-A-6
  
 6)NOTE: NEED TO LABEL ALL OUTLETS THAT
 ARE REQ`D TO BE GFI/ GFI PROTECTED.
 GARAGE,OUTSIDE,BATHS AS PER 210-8
  
 7)NOTE: YOU SHOW EQUIPMENT GROUNDING
 CONDUCTOR BEING INSTALLED FROM METER
 TO PANELS?? ONLY AFTER FIRST MEANS
 OF DISC.
  
 8)NOTE:NOTE MISSING RECEPTS AS REQ`D BY
 210-52 2`6`12` RULE.
  
 9)NOTE:SMOKE DETECTORS INSTALLED INSIDE
 AND OUTSIDE ALL SLEEPING ROOMS AS REQ`D
 BY 1993/1996 NFPA-72 2-2.1.1.1
  
 10)NOTE: NEED TO HAVE COLD WATER PIPE,
 AND BLDG. STEEL AS PART OF THE GROUNDING
 ELECTRODE SYSTEM. AS PER 250-81
 PLEASE SHOW ON RISER DIAGRAM 215-5
  
 11)NOTE:PLEASE SHOW ON PANEL SCHEDULES
 THE REQ`D BATH(S) CIRCUT(S) AS PER ART
 210-52D. NEED TO BE 20AMP #12 AWG.
  
 12)NOTE PLEASE INDICATE WHEATER OR NOT
 MAIN CIRCUT BRKR. PANELS OR NOT.215-5
  
 NEED TO SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW AND APPROVAL. IF THERE ARE
 ANY QUESTIONS PLEASE CALL 659-8096
 EXT. 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-08-04 Cont ID  
Sent By cthirben Date 2000-08-04 Time 09:59 Rev Time 1.00
Received By cthirben Date 2000-08-04 Time 09:59 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 PROVISO ADDITIONAL INFORMATION ON THE
 EXHAUST FANS IN BATHROOMS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2000-01-22 Cont ID  
Sent By jleech Date 2000-01-22 Time 10:40 Rev Time 0.35
Received By jleech Date 2000-01-22 Time 10:40 Sent To  
Notes
2001-01-08 00:00:00NOTE;
 NO A/C DRAWING.
 A/C DRAWING TO BE SUBMITED BY A/C
 CONTRACTOR WITH APPLICATION.

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-05-07 Cont ID  
Sent By kstevens Date 2001-05-07 Time 13:31 Rev Time 0.33
Received By kstevens Date 2001-05-07 Time 13:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-01-07 Cont ID  
Sent By tlarge Date 2000-01-07 Time 13:35 Rev Time 0.00
Received By tlarge Date 2000-01-07 Time 13:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-01-06 Cont ID  
Sent By tlarge Date 2000-01-06 Time 05:51 Rev Time 0.33
Received By tlarge Date 2000-01-06 Time 05:51 Sent To  
Notes
2001-01-08 00:00:00SUBMIT SANITARY ISOMETRIC FOR REVIEW.
 COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status P Date 2000-09-25 Cont ID  
Sent By fknapp Date 2000-09-25 Time 14:21 Rev Time 4.00
Received By fknapp Date 2000-09-22 Time 15:12 Sent To  
Notes
2001-01-08 00:00:00 
  
  
 *************BUILDING PROVISO***********
  
 SBC 104.2.2
  
 1)PROVIDE PRODUCT APPROVAL FOR ROOF
 COVERING UNDER SEPARATE PERMIT.
  
 2)PROVIDE STORM PANEL INFORMATION FOR
 ALL NON IMPACT RESISTANT GLASS UNDER
 SEPARATE PERMIT.
  
 PLEASE SUBMIT PRIOR TO INSTALLATION

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2000-08-29 Cont ID  
Sent By fknapp Date 2000-08-29 Time 14:18 Rev Time 2.00
Received By fknapp Date 2000-08-29 Time 14:18 Sent To  
Notes
2001-01-08 00:00:00SEE PREVIOUS REVIEW NOTES

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2000-08-09 Cont ID  
Sent By fknapp Date 2000-08-09 Time 13:32 Rev Time 2.00
Received By fknapp Date 2000-08-09 Time 13:32 Sent To  
Notes
2001-01-08 00:00:00 
  
  
 **********BUILDING DENIED**************
  
 SEE ORIGINAL NOTES FROM FIRST REVIEW

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-02-17 Cont ID  
Sent By fknapp Date 2000-02-17 Time 15:14 Rev Time 4.00
Received By fknapp Date 2000-02-17 Time 15:14 Sent To  
Notes
2001-01-08 00:00:00 
 *****************DENIED*****************
  
 SBC 104.2.2
  
 1)PROVIDE RAISE SEAL AND ORIGINAL
 SIGNATURE OF ARCHITECT ON ALL SHEETS OF
 PLANS.
  
 2)PROVIDE SOIL REPORT.
  
 3)PROVIDE 2 CURRENT COPIES OF PRODUCT
 APPROVALS FOR:
 ROOF COVERING
 EXTERIOR DOORS,WINDOWS AND MULLIONS
 GARAGE DOOR
 STORM PANELS WITH INSTALLATION
 SCHEDULE AND KEY PLAN WITH SPECIFIC
 ANCHORS TO BE USED.
  
 4)PROVIDE ENERGY CALCULATIONS WITH
 MANUEL J.
  
 5)PROVIDE ROOF FRAMING PLAN WITH UPLIFT
 CALCULATIONS AND ANCHOR SCHEDULE SBC1606
  
 6)PROVIDE FLOOR FRAMING PLAN SBC 1606
  
 7)PROVIDE CURRENT DESIGN COMPLIANCE FORM
  
 8)PROVIDE ROOF SHEATING NAILING ZONES
 COMPLYING WITH CITY AMENDMENTS 2306.1
 AND SBC 1606
  
 9)PROVIDE SPECIFIC WINDOW AND DOOR BUCK
 CONNECTIONS FOR WINDLOAD RESISTANCE
 SBC 1606
  
 10)PROVIDE STAIR SECTION,TREAD,RISER
 DIMENSIONS,HANDRAIL,GUARDRAIL SBC 1006,
 1007 AND 1015
  
 11)PROVIDE MECHANICAL DRAWINGS WITH
 PERMIT APPLICATION.
  
 12)BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH CO.,THE PLANS STAMPED BY THEM AND
 THE RECIEPT ATTACHED TO PERMIT
 APPLICATION.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-01-05 Cont ID  
Sent By gjoyce Date 2000-01-05 Time 13:18 Rev Time 0.50
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***