Plan Review Details - Permit 99122063
Plan Review Stops For Permit 99122063
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-02-17 Cont ID  
Sent By dpalmer Date 2000-02-17 Time 06:43 Rev Time 0.00
Received By dpalmer Date 2000-02-17 Time 06:43 Sent To  
Notes
2001-01-08 00:00:00************* PROVISO******************
  
 1)NOTE: STILL NEED TO LOOK AT THE AMOUNT
 OF CIRCUTS YOU SHOW IN THE 20 CIRCUT
 PANEL!!.IT IS REQ`D TO HAVE TWO SPARE
 SPACES. PLEASE CORRECT.
  
 NEED TO HAVE THE ABOVE SUBMITTED FOR
 APPROVAL AND REVIEW BEFORE FINAL.
 SUBMIT NEW REVISED PANEL SCHEDULE
 BEFORE THAT TIME. IF THERE ARE ANY QUES-
 -TIONS PLEASE CALL 659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-01-15 Cont ID  
Sent By dpalmer Date 2000-01-15 Time 07:53 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
2001-01-08 00:00:00************ UNSAT *********************
  
 1)NOTE:MISSING WP GFI OUTLET AS REQ`D
 BY ART;210-52E OF THE NEC BACK OF NEW
 ADDIDTION.
  
 2)NOTE: NEW ADDITION BATH GFI OOUTLET IS
 TO BE LISTED ON PANEL SCHEDULE AS 20AMP
 #12 AS REQ`D BY 210-52D/215-5
  
 3)NOTE:GROUNDING ELECTRODE CONDUCTOR
 IS TO GO TO BLDG.STEEL OF NEW ADDITION
 AS REQ`D BY 250-81 OF THE NEC.
  
 4)NOTE:RISER DIAGRAM SHOWS 18 POLE
 MCB PANEL??? YET PANEL SCHEDULE HAS MORE
 BRKRS/CIRCUTS THAN WILL FIT.PLEASE
 CHANGE.
  
 5)NOTE: LOAD FOR GEN LIGHTING NEEDS TO
 BE BY TOTAL AREA OF LIVING AREAS. 3 VA
 PER SQ FT.
  
 NEED TO HAVE THE ABOVE SUBMITTED FOR
 REVIEW AND APPROVAL. IF THERE ARE ANY
 QUESTIONS CALL 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2000-01-10 Cont ID  
Sent By ndenmark Date 2000-01-10 Time 11:10 Rev Time 0.25
Received By ndenmark Date 2000-01-10 Time 11:10 Sent To  
Notes
2001-01-08 00:00:00NO MECHANICAL INCLUDED
 PROVIDE MECHANICAL PLANS AT TIME OF MECH
 PERMIT APPLICATION PRIOR TO ANY MECHANIC
 AL WORK COMMENCING

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-01-07 Cont ID  
Sent By pschmitz Date 0900-01-07 Time 15:23 Rev Time 0.50
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVISO: SEE SHT #5.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2000-02-22 Cont ID  
Sent By fknapp Date 2000-02-22 Time 09:51 Rev Time 2.00
Received By fknapp Date 2000-02-22 Time 09:51 Sent To  
Notes
2001-01-08 00:00:00 
  
 ****************DENIED******************
  
 SBC 104.2.2
  
 1)ROOF RAFTERS SHOWN DO NOT COMPLY WITH
 SPAN TABLES PLEASE REVISE.
  
 2)PROVIDE 2 CURRENT COPIES OF PRODUCT
 APPROVALS FOR NEW EXTERIOR DOOR,WINDOWS
 AND ROOF COVERING.
  
 3)PROVIDE PROPOSED ROOF PITCH ON PLANS.
  
 4)IDENTIFY SPECIFIC ANCHOR STRAP TO BE
 USED ON EXISTING WALL.
  
 5)PROVIDE CONNECTION OF NEW SLAB TO
 EXISTING SLAB ON PLANS.
  
 6)SUBMIT MECHANICAL DRAWINGS WITH PERMIT
 APPLICATION.
  
 7)BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH CO., THE PERMIT PLANS STAMPED BY
 THEM AND THE RECIEPT ATTACHED TO THE
 PERMIT APPLICATION.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-01-20 Cont ID  
Sent By jcaloger Date 2000-01-20 Time 10:11 Rev Time 1.00
Received By jcaloger Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVIDE UPDATED DESIGN COMPLIANCE FORM
  
 PROVIDE PRODUCT APPROVAL FOR THE WINDOWS
 AND EXTERIOR DOORS.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-01-06 Cont ID  
Sent By gjoyce Date 2000-01-06 Time 11:04 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***