Plan Review Details - Permit 99122063
| Plan Review Stops For Permit 99122063 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2000-02-17 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-02-17 |
Time |
06:43 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-02-17 |
Time |
06:43 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ************* PROVISO****************** | | | | | | 1)NOTE: STILL NEED TO LOOK AT THE AMOUNT | | | OF CIRCUTS YOU SHOW IN THE 20 CIRCUT | | | PANEL!!.IT IS REQ`D TO HAVE TWO SPARE | | | SPACES. PLEASE CORRECT. | | | | | | NEED TO HAVE THE ABOVE SUBMITTED FOR | | | APPROVAL AND REVIEW BEFORE FINAL. | | | SUBMIT NEW REVISED PANEL SCHEDULE | | | BEFORE THAT TIME. IF THERE ARE ANY QUES- | | | -TIONS PLEASE CALL 659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-01-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-01-15 |
Time |
07:53 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ************ UNSAT ********************* | | | | | | 1)NOTE:MISSING WP GFI OUTLET AS REQ`D | | | BY ART;210-52E OF THE NEC BACK OF NEW | | | ADDIDTION. | | | | | | 2)NOTE: NEW ADDITION BATH GFI OOUTLET IS | | | TO BE LISTED ON PANEL SCHEDULE AS 20AMP | | | #12 AS REQ`D BY 210-52D/215-5 | | | | | | 3)NOTE:GROUNDING ELECTRODE CONDUCTOR | | | IS TO GO TO BLDG.STEEL OF NEW ADDITION | | | AS REQ`D BY 250-81 OF THE NEC. | | | | | | 4)NOTE:RISER DIAGRAM SHOWS 18 POLE | | | MCB PANEL??? YET PANEL SCHEDULE HAS MORE | | | BRKRS/CIRCUTS THAN WILL FIT.PLEASE | | | CHANGE. | | | | | | 5)NOTE: LOAD FOR GEN LIGHTING NEEDS TO | | | BE BY TOTAL AREA OF LIVING AREAS. 3 VA | | | PER SQ FT. | | | | | | NEED TO HAVE THE ABOVE SUBMITTED FOR | | | REVIEW AND APPROVAL. IF THERE ARE ANY | | | QUESTIONS CALL 659-8096 EXT 8372 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2000-01-10 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-01-10 |
Time |
11:10 |
Rev Time |
0.25 |
| Received By |
ndenmark |
Date |
2000-01-10 |
Time |
11:10 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | NO MECHANICAL INCLUDED | | | PROVIDE MECHANICAL PLANS AT TIME OF MECH | | | PERMIT APPLICATION PRIOR TO ANY MECHANIC | | | AL WORK COMMENCING |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2000-01-07 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
0900-01-07 |
Time |
15:23 |
Rev Time |
0.50 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO: SEE SHT #5. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2000-02-22 |
|
|
Cont ID |
|
| Sent By |
fknapp |
Date |
2000-02-22 |
Time |
09:51 |
Rev Time |
2.00 |
| Received By |
fknapp |
Date |
2000-02-22 |
Time |
09:51 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | | | | | | | ****************DENIED****************** | | | | | | SBC 104.2.2 | | | | | | 1)ROOF RAFTERS SHOWN DO NOT COMPLY WITH | | | SPAN TABLES PLEASE REVISE. | | | | | | 2)PROVIDE 2 CURRENT COPIES OF PRODUCT | | | APPROVALS FOR NEW EXTERIOR DOOR,WINDOWS | | | AND ROOF COVERING. | | | | | | 3)PROVIDE PROPOSED ROOF PITCH ON PLANS. | | | | | | 4)IDENTIFY SPECIFIC ANCHOR STRAP TO BE | | | USED ON EXISTING WALL. | | | | | | 5)PROVIDE CONNECTION OF NEW SLAB TO | | | EXISTING SLAB ON PLANS. | | | | | | 6)SUBMIT MECHANICAL DRAWINGS WITH PERMIT | | | APPLICATION. | | | | | | 7)BEFORE A PERMIT TO CONSTRUCT CAN BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM | | | BEACH CO., THE PERMIT PLANS STAMPED BY | | | THEM AND THE RECIEPT ATTACHED TO THE | | | PERMIT APPLICATION. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2000-01-20 |
|
|
Cont ID |
|
| Sent By |
jcaloger |
Date |
2000-01-20 |
Time |
10:11 |
Rev Time |
1.00 |
| Received By |
jcaloger |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVIDE UPDATED DESIGN COMPLIANCE FORM | | | | | | PROVIDE PRODUCT APPROVAL FOR THE WINDOWS | | | AND EXTERIOR DOORS. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2000-01-06 |
|
|
Cont ID |
|
| Sent By |
gjoyce |
Date |
2000-01-06 |
Time |
11:04 |
Rev Time |
0.25 |
| Received By |
gjoyce |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
|