Plan Review Details - Permit 99122041
Plan Review Stops For Permit 99122041
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-03-15 Cont ID  
Sent By dpalmer Date 2000-03-15 Time 10:39 Rev Time 0.00
Received By dpalmer Date 2000-03-15 Time 10:39 Sent To  
Notes
2001-01-08 00:00:00PLANS ARE TO BE RE DRAWN BEFORE ROUGH.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-03-07 Cont ID  
Sent By dpalmer Date 2000-03-07 Time 08:59 Rev Time 0.00
Received By dpalmer Date 2000-03-07 Time 08:59 Sent To  
Notes
2001-01-08 00:00:00************* UNSAT *******************
  
 1)NOTE: PLEASE SHOW MAIN DISC ON PLANS
 215-5
  
 2)NOTE:210-8-A-6 ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE ARE TO BE GFI/GFI
 PROTECTED. PLEASE SHOW.
  
 3)NOTE:PANEL SHOWS 48 POLES. NOTE 384-15
 42 CIRCUT.MAX
  
 4)NOTE:YOU SHOW ON RISER DIAGRAM TWO
 SETS OF WIRES FOR PANEL FEEDS.??
 PLEASE CLARIFY.
  
 5)NOTE:SMOKE DETECTORS ARE REQ`D INSIDE
 AND OUTSIDE ALL SLEEPING ROOMS AS REQ`D
 BY NFPA-72 2-2.1.1.1
  
 6)NOTE:AS REQ`D BY 210-63 OF THE NEC.
 AN OUTLET IS REQ`D FOR AHU UNIT IN THE
 ATTIC. DO NOT LIST AS OPTIONAL.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW AND APPROVAL. IF THERE ARE
 ANY QUESTIONS PLEASE CALL 659-8096 EXT
 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-03-13 Cont ID  
Sent By cthirben Date 2000-03-13 Time 09:47 Rev Time 1.00
Received By cthirben Date 2000-03-13 Time 09:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-03-06 Cont ID  
Sent By tlarge Date 2000-03-06 Time 06:29 Rev Time 0.33
Received By tlarge Date 2000-03-06 Time 06:29 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2000-03-16 Cont ID  
Sent By jgomez Date 2000-03-16 Time 15:18 Rev Time 4.00
Received By jgomez Date 2000-03-16 Time 15:18 Sent To  
Notes
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-PROVIDE COMPLETE BATHROOM WITH A DOOR
 HAVING A MINIMUM OF 29" CLEAR OPENING.
 SECTION 11 OF FLORIDA ACCESSIBILITY
 CODE FOR BUILDING CONSTRUCTION,1997.
 2-PROVIDE PRODUCT APPROVAL FOR SLIDING
 WINDOWS.
 RE-SUBMIT OTHER PRODUCT APPROVALS. SEE
 COMMENTS.
 3-REVISE SIZE OF EGRESS WINDOW AT
 BEDROOM #3. MINIMUM NET CLEAR OPENING
 TO BE 5.7 SQ. FT. SEC. 1005.4 SBC/1997
 4-PROVIDE COMPLETE FRAMING DETAILS FOR
 ARCHED OPENINGS.
 5-SEE ALL COMMENTS ON PLANS AND REVISE/
 UPDATE ALL DRAWINGS AS REQUIRED.
 RE-SUBMIT PRIOR TO INSPECTIONS.
 6-ATTIC ACCESS TO BE 22" X 36" MIN.
 SECTION 2309.6 SBC 1997.
 7-PROVIDE DRAFSTOPPING AT SECOND FLOOR
 FRAMING PLAN. SEE SEC.2305.2 SBC/1997.
 8-COMPLY WITH PROVISOS BY OTHER TRADES.
 9-PROVIDE PRODUCT APPROVAL FOR FLAT
 ROOF SYSTEM.
 10-PROVIDE THE DESIGN PRESSURES AT ALL
 EXTERIOR OPENINGS AS PER SECTION 1606
 SBC 1997.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-02-16 Cont ID  
Sent By gjoyce Date 2000-02-16 Time 11:36 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***