Plan Review Details - Permit 99121969
Plan Review Stops For Permit 99121969
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-02-02 Cont ID  
Sent By jleahy Date 2000-02-02 Time 10:21 Rev Time 4.00
Received By jleahy Date 2000-02-02 Time 10:13 Sent To  
Notes
2001-01-08 00:00:001-ALL BRANCH CIRCUIT NUMBERS TO BE
 SHOWN ON PLAN FOR # OF OUTLETS AND
 LIGHTS PER CIRCUIT.
  
 2-NEED TO SHOW LOCATION OF ALL EQUIPME
 UNITS DO NOT SHOW WATERHEATER AND
 AIRHANDLER LOCATIONS.
  
 3-2 BEDROOM UNIT SHOWS WASHER AND
 DRYER ON LOAD CALCULATION BUT NOT ON
 PLANS.
  
 4-NO PANEL SCHEDULES SHOWN FOR 1 AND 2
 BEDROOM UNITS.
  
 5-NO WIRE SIZES SHOWN FOR THE MAINS
 OUT TO FPL.
  
 6-PANEL SCHEDULS FOR THE UNITS NEEDED
 SHOW SIZE, AIC RATING,CIRCUIT NUMBER
  
 7-PROVIDE ALL THE ABOVE INFORMATION
 PRIOR TO THE FIRST ELCTRICAL ROUGH
 INSPECTION.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-01-13 Cont ID  
Sent By rturnque Date 2000-01-13 Time 15:49 Rev Time 0.45
Received By rturnque Date   Time   Sent To  
Notes
2001-01-08 00:00:001. DEAD END CORRIDORS SHALL NOT EXCEED
 35 FEET.
 2. FIRE HYDRANTS SHALL BE WITHIN 150
 FEET OF FIRE DEPARTMENT CONNECTIONS.
 3. FIRE ALARM SYSTEM SHALL BE CLASS "A"
 OR ADDRESSABLE. PROVIDE PERMIT AND SHOP
 DRAWINGS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-01-12 Cont ID  
Sent By ndenmark Date 2000-01-12 Time 09:31 Rev Time 2.00
Received By ndenmark Date 2000-01-12 Time 09:31 Sent To  
Notes
2001-01-08 00:00:00************DENIED**********************
  
 1. ALL DUCTS TO HAVE FIRE DAMPERS AT
 SHAFTWALL PENETRATION PER 1997 SMC 610.1
 2. DRYER VENT DUCTS TO BE MIN. 26 GA.
 AND SHALL RUN FULL LENGTH TO OUTSIDE OF
 BUILDING AND NOT TERMINATE INTO CONCEAL-
 ED SHAFT.SUBDUCT NOT ALLOWED FOR DRYER
 VENTS.SMC 509
 3. PROVIDE RISER SHOWING BATH EXHAUST
 SUBDUCT AND SHAFT
 4. PROVIDE DUCT SIZE FROM 16X10 TO 4" &
 8" @ TRIANGLE BOX ON 2ND BEDROOM PLAN
 5. SHOW HEIGHT OF INTAKE LOUVER OVER
 CONDENSER UNITS- OUTSIDE AIR INTAKE IS
 ONLY 2' FROM CONDENSING UNITS PER PLAN
 6. OVERFLOW PROTECTION REQUIRED ON ALL
 AHU'S. 1997 SMC 304.8.6
 7. PROVIDE INFORMATION ON FLUE VENT
 (DETAIL AND ROOF TERMINATION) FOR GENER-
 ATOR

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-02-04 Cont ID  
Sent By tlarge Date 2000-02-04 Time 06:29 Rev Time 4.00
Received By tlarge Date 2000-02-04 Time 06:29 Sent To  
Notes
2001-01-08 00:00:00SUBMIT DETAIL OF REINFORCEMENT OF WALLS
 FOR FUTURE INSTALLATION OF GRAB BARS AS
 REQUIRED BY THE FEDERAL FAIR HOUSING ACT
 24 CFR 100.205 SEC.3 REQUIREMENT #6.
 NOTE:ALL BATHROOMS WITHIN THE COVERED
 DWELLING UNIT SHALL COMPLY.
  
 ALL BATHROOMS IN THE COVERED DWELLING
 UNIT SHALL COMPLY W/THE PROVISIONS OF
 THE FEDERAL FAIR HOUSING ACT 24 CFR
 100.205 (C)(3)(IV) REQUIREMENT #7 (2)
 PARAGRAPH (A)OR(B).CLEAR FLOOR SPACE
 SHALL BE PROVIDED AT FIXTURES TO ALLOW A
 PERSON IN A WHEELCHAIR OR OTHER MOBILITY
 AID USE OF THE FIXTURES.CLEAR FLOOR
 SPACE SHALL BE SHOWN ON THE PLANS AND
 DESIGNATE WHICH OPTION OF REQUIREMENT#7
 (A OR B) IS BEING USED.
  
 LAUNDRY ROOMS SHALL COMPLY W/ANSI A117.1
 1986 SEC.4.32.1-4.32.6.3.
  
 ALL TOILET ROOMS AND BATHING FACILITIES
 IN ALL PUBLIC AND COMMON AREAS SHALL BE
 ACCESSIBLE PER ANSI A117.1 1986 SEC.
 4.22.1-4.22.4.
  
 SUBMIT SQUARE FOOTAGE OF REC.BUILDING
 AND OCCUPANT LOAD TO ENSURE COMPLIANCE
 W/SPC TABLE 407.
  
 SHT.A-4.2.1.-HANDICAP STALLS ARE UNDER-
 SIZED.COMPLY W/FACBC SEC.4.17.3
 EXCEPTION:NEW CONSTRUCTION.
  
 SHOW CLEAR FLOOR SPACE AT URINAL AND
 HEIGHT OF URINAL.COMPLY W/FACBC SEC.
 4.18.1 THRU 4.18.4.
  
 SUBMIT DETAILS/MOUNTING HEIGHTS OF ALL
 PLUMBING FIXTURES/APPURTENANCES.COMPLY
 W/FACBC AND SPC 403.4.
  
 SHT.P-1-CLEANOUTS SHALL BE INSTALLED
 IN BUILDING DRAIN AND COMPLY W/SPC SEC.
 710.2.4.
  
 SUBMIT RISER DIAGRAM FOR COMPLETE STORM
 WATER SYSTEM.SUBMIT DETAILS/CALCULATIONS
 FOR SECONDARY DRAINAGE PER SPC 1109.1,
 1109.2,APPENDIX"A"& TABLE A101.2.
  
 DETAIL THE TYPE OF OPERATIONS TO BE
 CONDUCTED IN THE KITCHEN.IF FOOD WILL BE
 COOKED A GREASE INTERCEPTOR WILL BE REQD
 PER SPC 1OO4.1.SUBMIT DETAIL OF GREASE
 TRAP.SPC 1004.2.
  
 SIZE THE UNDERGROUND SANITARY SYSTEM
 IN ITS ENTIRETY.COMPLY W/SPC SEC.714.1,
 714.2.
  
 SIZE THE WATER RISERS ON SHT.P-8.COMPLY
 W/SPC SEC.607.1,APPENDIX"F".
  
 WATER SUPPLY BRANCHES TO KIT.SINKS SHALL
 BE VALVED PER SPC SEC.610.4.1.
  
 SHT.P-9-VERTICAL COMBINATION WASTE AND
 VENT SYSTEM FOR KIT.SINK.SHALL COMPLY W/
 SPC SEC.911.4.AND TABLE 911.4.(SEE
 RISERS S2,S3,S5,S6,S7,S9.
  
 SANITARY RISERS S1,S4,S5,S8-SHALL COMPLY
 W/SPC SEC.911.3.(SIZE OF LOWEST WET VENT
  
 P & T DRAINS SHALL COMPLY W/COUNTYWIDE
 AMENDMENTS TO SPC SEC.507.6(3).
 (DISCHARGE TO EXTERIOR).
  
 CLARIFY TYPE OF DRAINS FOR WASHING
 MACHINES.DESIGN IS UNFAMILIAR AND DOES
 NOT APPEAR TO COMPLY W/SPC.

Review Stop Z ZONING
Rev No 1 Status F Date 2000-01-06 Cont ID  
Sent By gjoyce Date 2000-01-06 Time 09:49 Rev Time 1.00
Received By gjoyce Date   Time   Sent To  
Notes
2001-01-08 00:00:00GOING FOR REZONING