Plan Review Details - Permit 99121955
Plan Review Stops For Permit 99121955
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-12-05 Cont ID  
Sent By aneil Date 2000-12-05 Time 15:33 Rev Time 0.00
Received By aneil Date 2000-12-05 Time 15:33 Sent To  
Notes
2001-01-08 00:00:00APPROVED BY D. PALMER. SEE APPLICATION

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-02-05 Cont ID  
Sent By dpalmer Date 2000-02-05 Time 13:29 Rev Time 0.00
Received By dpalmer Date 2000-02-05 Time 13:29 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE: NEED TO SUBMIT AIC RATING OF
 EQUIPMENT MAINS. MAINS TO BE RATED FOR
 AVAILABLE FAULT CURRENT.AS REQ`D BY ARTS
 110-9/110-10/215-5 O FTHE NEC.
  
 2)NOTE:SHOW DISC. FOR A/C COND.UNIT
 AS PER 440-11/215-5
  
 3)NOTE: SHOW MAIN DISC. ON PLANS BY
 METER AS SHOWN ON RISER DIAGRAM.
  
 4)NOTE:AS PER NFPA-72 2-2.1.1.1 SMOKE
 DETECTORS ARE REQ`D INSIDE AND OUTSIDE
 ALL SLEEPING ROOMS.
  
 5)NOTE:ALL OUTLETS SERVING KITCHEN
 COUNTER SPACE ARE TO BE GFI/GFI PROTECT-
 -ED. AS PER 210-8-A-6
  
 6)NOTE:PLEASE SHOW THE DEDICATED CIRCUT
 FOR THE BATH(S) AS REQ`D BY 210-52D
 MUST BE 20AMP # 12 AWG. PLEASE LIST ON
 PANEL SCHEDULE.
  
 NEED TO SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW AND APPROAVL. IF THERE ARE
 ANY QUESTIONS PLEASE CALL 659-8096 X8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-11-06 Cont ID  
Sent By jleech Date 2000-11-06 Time 19:07 Rev Time 0.33
Received By jleech Date 2000-11-06 Time 19:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-02-05 Cont ID  
Sent By jleech Date 2000-02-05 Time 11:52 Rev Time 0.35
Received By jleech Date 2000-02-05 Time 11:52 Sent To  
Notes
2001-01-08 00:00:00PROVISO;
 REVISE DRAWINGS BEFORE ROUGH A/C INSP-
 TION.
 1.SHOW R/A LOCATION AND DUCT SIZE.
 2.IS A/H MOUNTED VERTICAL OR HORIZONTAL.

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-11-06 Cont ID  
Sent By jleech Date 2000-11-06 Time 19:08 Rev Time 0.33
Received By jleech Date 2000-11-06 Time 19:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-02-02 Cont ID  
Sent By tlarge Date 2000-02-02 Time 05:08 Rev Time 0.50
Received By tlarge Date 2000-02-02 Time 05:08 Sent To  
Notes
2001-01-08 00:00:00*****************PROVISO****************
 LOCATION OF PLBG.FIXTURES ON SANITARY
 RISER DOESN'T MATCH FLOOR PLAN.SUBMIT
 REVISED SANITARY RISER PRIOR TO ROUGH
 PLBG.INSP.

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2001-02-14 Cont ID  
Sent By jgomez Date 2001-02-14 Time 11:57 Rev Time 0.50
Received By jgomez Date 2001-02-14 Time 11:57 Sent To  
Notes
2001-02-14 00:00:00TRUSS DRAWINGS CHECKLIST:
  
 1-TRUSS DRAWINGS STILL SHOW THE WRONG
 MEAN ROOF HEIGHT. THIS IS A TWO STORY
 BUILDING. THEREFORE, MEAN ROOF HEIGHT
 IS +/- 23'-8". REVISE AS REQUIRED.
 2-SBC 1997 DOESN'T USE "WALL HEIGHT". IT
 USES THE MEAN ROOF HEIGHT OF THE
 BUILDING. REVISE AS REQUIRED.
 3-CHECK IF CONNECTORS SPECIFIED WILL
 RESIST THE LOADS CALCULATED ON THE
 REVISED ENGINEERED TRUSS DRAWINGS
 PRIOR TO SUBMITTAL TO THIS OFFICE.
 4-UNABLE TO IDENTIFY ENGINEER.
 -ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND NUMBER ON EACH SHEET
 AS REQUIRED BY CHAPTER 471 OF FLORIDA
 STATUTES.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2000-12-01 Cont ID  
Sent By jgomez Date 2000-12-01 Time 16:30 Rev Time 3.00
Received By jgomez Date 2000-12-01 Time 16:30 Sent To  
Notes
2001-01-08 00:00:00APPROVED WITH PROVISO:
  
 1-FLOOD ZONE "A8". WILL NEED ELEVATION
 CERTIFICATE.
 2-PRODUCT APPROVAL FOR GARAGE DOORS
 DOESN'T MEET THE DESIGN PRESSURES
 CALCULATED BY THE ENGINEER. RESUBMIT
 3-PROVIDE PRODUCT APPROVAL FOR:
 -FRENCH DOORS.
 -FLAT ROOF SYSTEM.
 4-SEE COMMENTS ON PLANS AND REVISE/
 CLARIFY/UPDATE AS REQUIRED.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-06-20 Cont ID  
Sent By lsmith Date 2000-06-20 Time 14:55 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
2001-01-08 00:00:00PER TM 6/19/00

Review Stop Z ZONING
Rev No 1 Status P Date 2000-06-22 Cont ID  
Sent By gjoyce Date 2000-06-22 Time 08:58 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***