| Plan Review Stops For Permit 99121955 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2000-12-05 |
|
|
Cont ID |
|
| Sent By |
aneil |
Date |
2000-12-05 |
Time |
15:33 |
Rev Time |
0.00 |
| Received By |
aneil |
Date |
2000-12-05 |
Time |
15:33 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | APPROVED BY D. PALMER. SEE APPLICATION |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-02-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-02-05 |
Time |
13:29 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-02-05 |
Time |
13:29 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************** UNSAT ****************** | | | | | | 1)NOTE: NEED TO SUBMIT AIC RATING OF | | | EQUIPMENT MAINS. MAINS TO BE RATED FOR | | | AVAILABLE FAULT CURRENT.AS REQ`D BY ARTS | | | 110-9/110-10/215-5 O FTHE NEC. | | | | | | 2)NOTE:SHOW DISC. FOR A/C COND.UNIT | | | AS PER 440-11/215-5 | | | | | | 3)NOTE: SHOW MAIN DISC. ON PLANS BY | | | METER AS SHOWN ON RISER DIAGRAM. | | | | | | 4)NOTE:AS PER NFPA-72 2-2.1.1.1 SMOKE | | | DETECTORS ARE REQ`D INSIDE AND OUTSIDE | | | ALL SLEEPING ROOMS. | | | | | | 5)NOTE:ALL OUTLETS SERVING KITCHEN | | | COUNTER SPACE ARE TO BE GFI/GFI PROTECT- | | | -ED. AS PER 210-8-A-6 | | | | | | 6)NOTE:PLEASE SHOW THE DEDICATED CIRCUT | | | FOR THE BATH(S) AS REQ`D BY 210-52D | | | MUST BE 20AMP # 12 AWG. PLEASE LIST ON | | | PANEL SCHEDULE. | | | | | | NEED TO SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW AND APPROAVL. IF THERE ARE | | | ANY QUESTIONS PLEASE CALL 659-8096 X8372 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2000-11-06 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2000-11-06 |
Time |
19:07 |
Rev Time |
0.33 |
| Received By |
jleech |
Date |
2000-11-06 |
Time |
19:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2000-02-05 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2000-02-05 |
Time |
11:52 |
Rev Time |
0.35 |
| Received By |
jleech |
Date |
2000-02-05 |
Time |
11:52 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO; | | | REVISE DRAWINGS BEFORE ROUGH A/C INSP- | | | TION. | | | 1.SHOW R/A LOCATION AND DUCT SIZE. | | | 2.IS A/H MOUNTED VERTICAL OR HORIZONTAL. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2000-11-06 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2000-11-06 |
Time |
19:08 |
Rev Time |
0.33 |
| Received By |
jleech |
Date |
2000-11-06 |
Time |
19:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2000-02-02 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-02-02 |
Time |
05:08 |
Rev Time |
0.50 |
| Received By |
tlarge |
Date |
2000-02-02 |
Time |
05:08 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *****************PROVISO**************** | | | LOCATION OF PLBG.FIXTURES ON SANITARY | | | RISER DOESN'T MATCH FLOOR PLAN.SUBMIT | | | REVISED SANITARY RISER PRIOR TO ROUGH | | | PLBG.INSP. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
3 |
Status |
F |
Date |
2001-02-14 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2001-02-14 |
Time |
11:57 |
Rev Time |
0.50 |
| Received By |
jgomez |
Date |
2001-02-14 |
Time |
11:57 |
Sent To |
|
|
| Notes |
| 2001-02-14 00:00:00 | TRUSS DRAWINGS CHECKLIST: | | | | | | 1-TRUSS DRAWINGS STILL SHOW THE WRONG | | | MEAN ROOF HEIGHT. THIS IS A TWO STORY | | | BUILDING. THEREFORE, MEAN ROOF HEIGHT | | | IS +/- 23'-8". REVISE AS REQUIRED. | | | 2-SBC 1997 DOESN'T USE "WALL HEIGHT". IT | | | USES THE MEAN ROOF HEIGHT OF THE | | | BUILDING. REVISE AS REQUIRED. | | | 3-CHECK IF CONNECTORS SPECIFIED WILL | | | RESIST THE LOADS CALCULATED ON THE | | | REVISED ENGINEERED TRUSS DRAWINGS | | | PRIOR TO SUBMITTAL TO THIS OFFICE. | | | 4-UNABLE TO IDENTIFY ENGINEER. | | | -ENGINEERS SHALL LEGIBLY INDICATE THEIR | | | NAME, ADDRESS AND NUMBER ON EACH SHEET | | | AS REQUIRED BY CHAPTER 471 OF FLORIDA | | | STATUTES. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2000-12-01 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2000-12-01 |
Time |
16:30 |
Rev Time |
3.00 |
| Received By |
jgomez |
Date |
2000-12-01 |
Time |
16:30 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | APPROVED WITH PROVISO: | | | | | | 1-FLOOD ZONE "A8". WILL NEED ELEVATION | | | CERTIFICATE. | | | 2-PRODUCT APPROVAL FOR GARAGE DOORS | | | DOESN'T MEET THE DESIGN PRESSURES | | | CALCULATED BY THE ENGINEER. RESUBMIT | | | 3-PROVIDE PRODUCT APPROVAL FOR: | | | -FRENCH DOORS. | | | -FLAT ROOF SYSTEM. | | | 4-SEE COMMENTS ON PLANS AND REVISE/ | | | CLARIFY/UPDATE AS REQUIRED. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2000-06-20 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2000-06-20 |
Time |
14:55 |
Rev Time |
0.50 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PER TM 6/19/00 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2000-06-22 |
|
|
Cont ID |
|
| Sent By |
gjoyce |
Date |
2000-06-22 |
Time |
08:58 |
Rev Time |
0.25 |
| Received By |
gjoyce |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|