| 2001-04-25 00:00:00 | *************BUILDING UNSAT************* |
| | |
| | 1) STRUCTURE IS LOCATED IN AN "A8" FLOOD |
| | ZONE AN ELEVATION CERTIFICATE WILL BE |
| | REQUIRED PRIOR TO RECEIVING A C.O. |
| | |
| | 2) THE TYPICAL CEILING DETAIL ON SHEETS |
| | A-1 AND A-1B IS FOR VERTICLE (WALL) |
| | APPLICATION. SECTION 2504.2.2 OF THE |
| | 1997 SBC REFERS TO ASTM C 1603, WHICH |
| | REQUIRES 1 3/4" PENETRATION INTO |
| | HORIZONTAL FRAMING MEMBERS FOR LATH ON |
| | CEILINGS. |
| | |
| | 3) THE MAXIMUM HEIGHT ALLOWED FOR THE |
| | PRIVACY WALL ON SHEETS A-1 & A-1B IS 6' |
| | ABOVE FINISH GRADE. PLEASE CORRECT |
| | DRAWINGS. |
| | |
| | 4) THE WIND LOADS LISTED IN THE WINDOW |
| | PRESSURE SCHEDULE ON SHEETS A-4A & A-4B |
| | FOR ( J,S,& T ) DO NOT CORRESPOND WITH |
| | THOSE GIVEN ON THE ELEVATION DRAWINGS ON |
| | THE SAME SHEETS. PLEASE CORRECT. |
| | |
| | 5) SECTION 104.2.1 OF THE CITY OF W.P.B. |
| | AMENDFMENTS TO THE 97 SBC REQUIRES |
| | INFORMATION TO BE SPECIFIC AND THAT THE |
| | TECHINCAL CODES NOT BE CITED. THE STAIR |
| | DETAILS ON SHEETS A-3A AND A-8A STATE |
| | THAT STAIRS ARE TO BE CONSTRUCTED IN |
| | ACCORDANCE WITH SECT. 1007 OF THE 97 SBC |
| | THIS IS NOT ACCEPTABLE. PLEASE PROVIDE |
| | SPECIFIC DETAILS OF HANDRAILS,GUARDRAILS |
| | ,ETC.(INCLUDE INTERMEDIATE RAIL SPACING) |
| | |
| | 6) PER SEC. 1007.3 OF THE 1997 SBC |
| | REQUIRES THAT THE SUM OF 2 RISERS AND |
| | 1 TREAD FOR STAIRS IS TO BE NOT LESS |
| | THAN 24" NOR MORE THAN 25". THE VALUES |
| | ON SHEETS A-3A & A-8A, DO NOT COMPLY. |
| | PLEASE CORRECT. |
| | |
| | 7) THE 16'X7' GARAGE DOOR DOES NOT MEET |
| | THE WIND LOADS REQUIRED ON THE DRAWINGS. |
| | |
| | THESE SAME ISSUES ARE RECURRING ON |
| | SUBSEQUENT SUBMITTALS. PLEASE CORRECT |
| | THE ORIGIONALS TO HELP EXPEDIATE THE |
| | PLAN REVIEW PROCESS. |
| | |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |