Plan Review Details - Permit 99121905
Plan Review Stops For Permit 99121905
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-02-12 Cont ID  
Sent By dpalmer Date 2000-02-12 Time 15:10 Rev Time 0.00
Received By dpalmer Date 2000-02-12 Time 15:10 Sent To  
Notes
2001-01-08 00:00:00*************** PROVISO **************
  
 1)NOTE:PLEASE NOTE THAT YOU HAVE A 52AMP
 LOAD ON PANEL B AND YOU SHOW A 2P-40
 FEEDING THAT PANLE.ALSO PLEASE NOTE THAT
 AS PER 310-16 #8 IN THE 75C COLUMN IS
 ONLY RATED FOR 50 AMPS. CANNOT USE THE
 90C RATING.
  
 PLEASE CORRECT THE ABOVE AND SUBMIT FOR
 REVIEW AND APPROVAL BEFORE FIRST ROUGH
 ELECTRICAL INSPECTION IS CALLED.
 IF THERE ARE ANY QUESTIONS PLEASE CALL
 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-05-30 Cont ID  
Sent By cthirben Date 2000-05-30 Time 14:09 Rev Time 1.00
Received By cthirben Date 2000-05-30 Time 14:09 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-01-28 Cont ID  
Sent By jleech Date 2000-01-28 Time 07:50 Rev Time 0.35
Received By jleech Date 2000-01-28 Time 07:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-06-05 Cont ID  
Sent By tlarge Date 2000-06-05 Time 17:30 Rev Time 0.25
Received By tlarge Date 2000-06-05 Time 17:30 Sent To  
Notes
2001-01-08 00:00:00REVISED SANITARY RISER.

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-01-27 Cont ID  
Sent By tlarge Date 2000-01-27 Time 06:03 Rev Time 0.33
Received By tlarge Date 2000-01-27 Time 06:03 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2000-03-03 Cont ID  
Sent By fknapp Date 2000-03-03 Time 15:54 Rev Time 4.00
Received By fknapp Date 2000-03-03 Time 15:27 Sent To  
Notes
2001-01-08 00:00:00 
  
 ******************PROVISO***************
  
 SBC 104.2.2
  
 1)PROVIDE SOIL REPORT,SUBMIT PRIOR TO
 FIRST INSPECTION.
  
 2)PROVIDE 2 CURRENT COPIES OF PRODUCT
 APPROVALS FOR STORM PANELS,SUBMIT PRIOR
 TO INSTALLATION.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-03-22 Cont ID  
Sent By gjoyce Date 2000-03-22 Time 08:50 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***