Plan Review Details - Permit 99121883
| Plan Review Stops For Permit 99121883 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2000-04-04 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-04-04 |
Time |
14:51 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-04-04 |
Time |
14:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-02-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-02-05 |
Time |
15:14 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-02-05 |
Time |
15:14 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************** UNSAT ****************** | | | | | | 1)NOTE: NEED TO SUBMIT AIC RATING OF | | | MAINS. MAINS NEED TO BE RATED FOR THE | | | AVAILABLE FAULT CURRENT.AS REQ`D BY | | | ARTS:110-9/110-10/215-5 | | | | | | 2)NOTE: SHOW A/C DISC.REQ`D BY 440-11 | | | OF THE NEC. | | | | | | 3)NOTE: NEED TO SHOW ALL OUTLETS SERVING | | | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- | | | -ED. AS PER ART:210-8-A-6 | | | | | | 4)NOTE: NEED TO HAVE THE DEDICATED CIR- | | | -CUT(S) FOR THE BATH(S) AS REQ`D BY | | | ART:210-52D THEY MUST BE 20AMP AND #12 | | | AWG. | | | | | | 5)NOTE: PLEASE SHOW ON PLANS MAIN DISC. | | | AS SHOWN RISER DIAGRAM. | | | | | | NEED TO SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW AND APPROVAL. IF THERE ARE | | | ANY QUESTIONS PLEASE CALL 659-8096 | | | EXT 8372 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2000-02-05 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2000-02-05 |
Time |
07:58 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
2000-02-05 |
Time |
07:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2000-04-04 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-04-04 |
Time |
12:10 |
Rev Time |
0.33 |
| Received By |
tlarge |
Date |
2000-04-04 |
Time |
12:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2000-01-28 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-01-28 |
Time |
17:31 |
Rev Time |
0.33 |
| Received By |
tlarge |
Date |
2000-01-28 |
Time |
17:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
3 |
Status |
F |
Date |
2000-06-20 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2000-06-20 |
Time |
09:53 |
Rev Time |
0.50 |
| Received By |
jgomez |
Date |
2000-06-20 |
Time |
09:53 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | TRUSS DRAWINGS CHECKLIST: | | | -TRUSS ENGINEER TO SIGN, SEAL AND DATE | | | ALL DOCUMENTS AS REQUIRED WHEN | | | SUBMITTING THEM FOR PUBLIC RECORDS. | | | -UPDATE ALL GENERAL DETAILS ACCORDING TO | | | SBC 1997 OR ASCE 7-95. REMEMBER TO SIGN | | | SEAL AND DATE THEM AS ABOVE. | | | -CLARIFY WHY THERE ARE SOME DETAILS THAT | | | HAVE THE COPY OF THE SEAL OF ONE | | | ENGINEER AND THE SEAL OF ANOTHER | | | ENGINEER. PLEASE REVIEW ALL GENERAL | | | DETAILS SUBMITTED AND REVISE/UPDATE | | | AS REQUIRED. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2000-04-07 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2000-04-07 |
Time |
13:30 |
Rev Time |
0.50 |
| Received By |
jgomez |
Date |
2000-04-07 |
Time |
13:30 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | APPROVED WITH PROVISO. SEE LIST ON | | | PREVIOUS REVIEW. | | | IMPACT FEES PAID. | | | | | | NOTE:PROVIDE ELEVATION CERTIFICATE. | | | FLOOD ZONE A8. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2000-04-05 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2000-04-05 |
Time |
20:26 |
Rev Time |
2.50 |
| Received By |
jgomez |
Date |
2000-04-05 |
Time |
20:26 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO: | | | | | | 1-PROVIDE ATTIC ACCESS AT ROOF ABOVE | | | GARAGE. SECTION 2309.6 SBC 1997. | | | 2-UPDATE/REVISE ALL DRAWINGS AS REQUIRED | | | SEE PLANS FOR COMMENTS. | | | 3-FLOOD ZONE "A8" PROVIDE ELEVATION | | | CERTIFICATE. | | | 4-STAIRS DETAIL: CLARIFY TREAD TO RISER | | | RATIO, SEC. 1007.3 SBC 1997. | | | -PROVIDE FIREBLOCKING SEC 2305 SBC/1997 | | | 5-PROVIDE LEGIBLE AND COMPLETE PRODUCT | | | APPROVALS FOR ENTRY DOOR AND GARAGE | | | DOOR. | | | 6-SECOND FLOOR BEDROOM WINDOWS TO COMPLY | | | WITH SECTION 1005.4 SBC 1997 BY HAVING | | | A MINIMUM CLEAR OPENING OF 5.7 SQ. FT. | | | AND A MINIMUM CLEAR HEIGHT OPENING | | | OF 24". | | | NOTE: REVISE FLOOR PLAN TO CLARIFY THE | | | SIZE OF WINDOW AND MASONRY OPENING. | | | THEY DON'T MATCH. | | | 7-PROVIDE COMPLETE DETAILS FOR ROUND | | | OPENINGS AT WOOD FRAMING WALL. | | | 8-ATTIC ACCESS AT MASTER BEDROOM CLOSET | | | TO BE 22"X36" MIN. SEC 2309.6 SBC/97. | | | 9-PROVIDE DRAFSTOPPING AT SECOND FLOOR | | | FRAMING PLAN. INDICATE LOCATION AND | | | MATERIAL AS PER SECTION 2305.2 SBC/97. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2000-04-07 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2000-04-07 |
Time |
13:33 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2000-04-07 |
Time |
13:33 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | APPROVED BY GRACE JOYCE. SEE SURVEY AND | | | APPLICATION. |
|
|
|