Plan Review Details - Permit 99121858
Plan Review Stops For Permit 99121858
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-11-07 Cont ID  
Sent By dpalmer Date 2000-11-07 Time 18:33 Rev Time 0.00
Received By dpalmer Date 2000-11-07 Time 18:32 Sent To  
Notes
2001-01-08 00:00:00**************** PROVISO **************
  
 REVISE PLAN BEFORE FINAL!!!!
  
 1)NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED. PER 210-8-A-6
  
 2)NOTE: PLEASE SHOW MAIN DISCONNECT ON
 PLAN THAT IS SHOWN ON RISER DIAGRAM.
  
 3)NOTE: PLEASE SEE RISER AND PANEL SCHED
 -ULE. ONE SHOWS MLO AND THE OTHER THE
 PANEL IS SHOWN AS MCB.
  
 4)NOTE: PLEASE PROVIDE CLARIFICATION
 FOR THE 28 CIRCUIT PANEL SHOWN. THIS
 DOES NOT SEEM TO BE A STANDARD SIZE PAN-
 -EL. 215-5
  
 5)NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3 AND 215-5
  
 PLEASE REVISE AND SUBMIT ALL THE ABOVE
 INFORMATION FOR REVIEW BEFORE FINAL.
 IF THERE ARE ANY QUESTIONS PLEASE CALL
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-08-06 Cont ID  
Sent By pkrauss Date 2001-08-06 Time 12:01 Rev Time 0.30
Received By pkrauss Date 2001-08-06 Time 11:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-11-06 Cont ID  
Sent By jleech Date 2000-11-06 Time 18:43 Rev Time 0.33
Received By jleech Date 2000-11-06 Time 18:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-11-06 Cont ID  
Sent By jleech Date 2000-11-06 Time 18:43 Rev Time 0.33
Received By jleech Date 2000-11-06 Time 18:43 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2001-02-15 Cont ID  
Sent By jgomez Date 2001-02-14 Time 13:11 Rev Time 0.50
Received By jgomez Date 2001-02-14 Time 13:11 Sent To  
Notes
2001-02-15 00:00:00TRUSS DRAWINGS CHECKLIST:
  
 1-UNABLE TO IDENTIFY ENGINEER.
 -ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND NUMBER ON EACH SHEET
 AS REQUIRED BY CHAPTER 471 FLORIDA
 STATUTES.
  
  
  
  
  
  
 BUILDING PLAN REVIEWER: JULIO GOMEZ AT
 659-8096 EXT. 8232.
2001-02-14 00:00:00TRUSS DRAWINGS APPROVAL.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2000-11-30 Cont ID  
Sent By jgomez Date 2000-11-30 Time 10:49 Rev Time 2.50
Received By jgomez Date 2000-11-30 Time 10:49 Sent To  
Notes
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-FLOOD ZONE "AO". NEED TO PROVIDE THE
 ELEVATION CERTIFICATE.
 2-CLARIFY/REVISE DRAWINGS AS REQUIRED.
 SEE COMMENTS ON PLANS.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-06-20 Cont ID  
Sent By lsmith Date 2000-06-20 Time 14:50 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
2001-01-08 00:00:00PER TM 6/19/00

Review Stop Z ZONING
Rev No 1 Status P Date 2000-02-16 Cont ID  
Sent By gjoyce Date 2000-02-16 Time 12:14 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***