Plan Review Details - Permit 99121835
Plan Review Stops For Permit 99121835
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-03-07 Cont ID  
Sent By dpalmer Date 2000-03-07 Time 07:18 Rev Time 0.00
Received By dpalmer Date 2000-03-07 Time 07:18 Sent To  
Notes
2001-01-08 00:00:00**************** PROVISO ***************
  
 1)NOTE: PLEASE NOTE AS PER 384-15
 YOU SHOW 48 POLES FOR PANEL???
  
 2)NOTE:AS REQ`D BY 210-8-A-6 ALL OUTLETS
 SERVING KITCHEN COUNTERSPACE ARE TO BE
 GFI/GFI PROTECTED.PLEASE SHOW!!!
  
 3)NOTE: RISER SHOWS MAIN DISCONNECT.
 PLEASE SHOW ON PLANS.215-5
  
 4) PLEASE INDICATE THE BATH(S) CIRCUT AS
 REQ`D BY 210-11-C-3
  
 PLEASE HAVE ALL THE ABOVE SUBMITTED FOR
 REVIEW AND APPROVAL BEFORE ANY ELEC.
 INSPECTION IS CALLED IN.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-03-13 Cont ID  
Sent By cthirben Date 2000-03-13 Time 09:46 Rev Time 1.00
Received By cthirben Date 2000-03-13 Time 09:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-03-06 Cont ID  
Sent By tlarge Date 2000-03-06 Time 07:23 Rev Time 0.33
Received By tlarge Date 2000-03-06 Time 07:23 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2000-06-20 Cont ID  
Sent By jgomez Date 2000-06-20 Time 09:05 Rev Time 0.50
Received By jgomez Date 2000-06-20 Time 09:05 Sent To  
Notes
2001-01-08 00:00:00CHECKLIST:
 TRUSS DRAWINGS:
 -TRUSS ENGINEER TO SIGN, SEAL AND DATE
 ALL DOCUMENTS AS REQUIRED WHEN
 SUBMITTING THEM FOR PUBLIC RECORDS.
 -UPDATE ALL GENERAL DETAILS ACCORDING TO
 SBC 1997 OR ASCE 7-95. REMEMBER TO SIGN
 SEAL AND DATE AS ABOVE.
 -CLARIFY WHY THERE ARE SOME DETAILS THAT
 HAVE THE COPY OF THE SEAL OF ONE ENG'R
 AND THE SEAL OF ANOTHER ENGINEER.
 PLEASE REVIEW ALL GENERAL DETAILS
 SUBMITTED AND REVISE/UPDATE AS REQUIRED

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2000-03-15 Cont ID  
Sent By jgomez Date 2000-03-15 Time 11:05 Rev Time 0.50
Received By jgomez Date 2000-03-15 Time 11:05 Sent To  
Notes
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-FLOOD ZONE A8.PROVIDE ELEVATION
 CERTIFICATE.
 2-REVISE/UPDATE ALL DRAWINGS AS REQUIRED
 SEE COMMENTS ON PLANS.
 3-RE-SUBMIT GARAGE DOOR, ENTRY DOOR AND
 EXTERIOR DOORS AND WINDOWS PRODUCT
 APPROVALS. SEE COMMENTS.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-03-14 Cont ID  
Sent By jgomez Date 2000-03-14 Time 09:11 Rev Time 2.00
Received By jgomez Date 2000-03-14 Time 09:11 Sent To  
Notes
2001-01-08 00:00:00 
 1-FLOOD ZONE A8.PROVIDE ELEVATION
 CERTIFICATE.
 2-REVISE/UPDATE ALL DRAWINGS. SEE
 COMMENTS ON PLANS.
 3-STORM PANELS:
 -REVISE/UPDATE INSTALLATION SCHEDULE
 TO EXACTLY MATCH FLOOR PLANS AND
 ELEVATIONS.
 -SEE NOTE #4 ON SHEET 3 OF 5 OF STORM
 PANELS DRAWINGS AND STORM PANEL AT
 OPENING #12. REVISE AS REQUIRED.
 4-RE-SUBMIT GARAGE DOOR, ENTRY DOOR AND
 EXTERIOR DOORS AND WINDOWS. SEE
 COMMENTS.
 5-PAY IMPACT FEES.
 6-PAY FEES TO CITY OF WEST PALM BEACH
 FOR RADON FEES AND CHANGE OF LOCATION.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-02-16 Cont ID  
Sent By gjoyce Date 2000-02-16 Time 12:10 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***