Plan Review Details - Permit 99121824
| Plan Review Stops For Permit 99121824 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2001-02-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-02-28 |
Time |
21:34 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-02-28 |
Time |
21:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-02-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-02-05 |
Time |
15:31 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-02-05 |
Time |
15:31 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE: NEED TO SUBMIT PLANS SHOWING | | | AIC RATING OF MAINS. MAIN IS TO BE | | | RATED FOR AVAILABLE FAULT CURRENT. | | | AS REQ`D BY ARTS:110-9/110-10/215-5 | | | | | | 2) NOTE: RISER SHOWS MAIN,,,PLEASE SHOW | | | ON PLANS NEXT TO METER. | | | | | | 3)NOTE:PLEASE LABEL ALL OUTLETS SERVING | | | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- | | | -ED.AS REQ`D BY ART:210-8-A-6 OF THE | | | NEC. | | | | | | 4)NOTE: AS REQ`D BY NFPA-72 2-2.1.1.1 | | | SMOKE DETECTORS ARE REQ`D INSIDE AND | | | OUTSIDE ALL SLEEPING ROOMS. IF THERE | | | IS A OPTIONAL DEN PLEASE SHOW AS OPT. | | | | | | 5)NOTE:PLEASE LIST THE DEDICATED BATH(S) | | | CIRUCT(S) ON PANEL SCHEDULE. AS REQ`D | | | BY 210-52. MUST BE 20AMP AND #12 AWG. | | | | | | PLEASE HAVE ALL THE ABOVE INFORMAITON | | | SUBMITTED FOR REVIEW AND APPROVAL. | | | IF THERE ARE ANY QUESTIONS PLEASE CALL | | | 659-8096 EXT 8372 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2001-02-24 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-02-24 |
Time |
12:42 |
Rev Time |
0.25 |
| Received By |
jleech |
Date |
2001-02-24 |
Time |
12:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2000-02-05 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2000-02-05 |
Time |
07:48 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
2000-02-05 |
Time |
07:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2001-02-24 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-02-24 |
Time |
12:42 |
Rev Time |
0.25 |
| Received By |
jleech |
Date |
2001-02-24 |
Time |
12:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-01-28 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-01-28 |
Time |
17:35 |
Rev Time |
0.33 |
| Received By |
tlarge |
Date |
2000-01-28 |
Time |
17:33 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | SANITARY RISER DOESN'T COMPLY W/SPC. | | | THE LOCATION OF THE PLBG.FIXTURES ON THE | | | SANITARY RISER DON'T CORRELATE W/THE | | | ARCH.FLOOR PLAN.COUNTYWIDE AMENDMENTS | | | TO SPC SEC.104.2.1. | | | SANITARY RISER SHALL BE SIGNED AND | | | SEALED BY ENG.OF RECORD. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2001-03-09 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2001-03-09 |
Time |
13:53 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-03-09 00:00:00 | APPROVED BY ROBBIE 3/2/01 | | 2001-03-02 00:00:00 | ****************PROVISO***************** | | | | | | 1) A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2) PROVIDE FLOOD ZONE ELEVATION | | | CERTIFICATE FOR NEW CONSTRUTION WITH BFE | | | | | | 3)PROVIDE PRODUCT APPROVAL FOR | | | OVERHEAD GARAGE DOOR THAT HAS DESIGN | | | LOADS WHICH EQUAL OR EXCEED THE | | | CALCULATED WINDLOADS FOR THE GARAGE | | | OPENING OF THE STRUCTURE. | | | | | | 4)PROVIDE (2) CURRENT AND COMPLETE | | | COPIES OF SBCCI OR METRO-DADE PRODUCT | | | APPROVALS FOR: | | | - ARCHED FIXED GLASS | | | - STRUCTURAL WINDOW MULLIONS | | | | | | 5) WINDOW PRESSURE SCHEDULE VALUES FOR | | | WINDOWS J,S AND T DO NOT CORRESPOND WITH | | | THE PRESSURES LISTED ON THE DRAWINGS. | | | SUBMIT REVISED SCHEDULE OR REVISED SHEET | | | A-4A. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2000-06-20 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2000-06-20 |
Time |
15:34 |
Rev Time |
0.50 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PER TM 6/19/00 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2000-06-22 |
|
|
Cont ID |
|
| Sent By |
gjoyce |
Date |
2000-06-22 |
Time |
08:52 |
Rev Time |
0.25 |
| Received By |
gjoyce |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
|