Plan Review Details - Permit 99121824
Plan Review Stops For Permit 99121824
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-02-28 Cont ID  
Sent By dpalmer Date 2001-02-28 Time 21:34 Rev Time 0.00
Received By dpalmer Date 2001-02-28 Time 21:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-02-05 Cont ID  
Sent By dpalmer Date 2000-02-05 Time 15:31 Rev Time 0.00
Received By dpalmer Date 2000-02-05 Time 15:31 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE: NEED TO SUBMIT PLANS SHOWING
 AIC RATING OF MAINS. MAIN IS TO BE
 RATED FOR AVAILABLE FAULT CURRENT.
 AS REQ`D BY ARTS:110-9/110-10/215-5
  
 2) NOTE: RISER SHOWS MAIN,,,PLEASE SHOW
 ON PLANS NEXT TO METER.
  
 3)NOTE:PLEASE LABEL ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED.AS REQ`D BY ART:210-8-A-6 OF THE
 NEC.
  
 4)NOTE: AS REQ`D BY NFPA-72 2-2.1.1.1
 SMOKE DETECTORS ARE REQ`D INSIDE AND
 OUTSIDE ALL SLEEPING ROOMS. IF THERE
 IS A OPTIONAL DEN PLEASE SHOW AS OPT.
  
 5)NOTE:PLEASE LIST THE DEDICATED BATH(S)
 CIRUCT(S) ON PANEL SCHEDULE. AS REQ`D
 BY 210-52. MUST BE 20AMP AND #12 AWG.
  
 PLEASE HAVE ALL THE ABOVE INFORMAITON
 SUBMITTED FOR REVIEW AND APPROVAL.
 IF THERE ARE ANY QUESTIONS PLEASE CALL
 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-02-24 Cont ID  
Sent By jleech Date 2001-02-24 Time 12:42 Rev Time 0.25
Received By jleech Date 2001-02-24 Time 12:42 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-02-05 Cont ID  
Sent By jleech Date 2000-02-05 Time 07:48 Rev Time 0.50
Received By jleech Date 2000-02-05 Time 07:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-02-24 Cont ID  
Sent By jleech Date 2001-02-24 Time 12:42 Rev Time 0.25
Received By jleech Date 2001-02-24 Time 12:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-01-28 Cont ID  
Sent By tlarge Date 2000-01-28 Time 17:35 Rev Time 0.33
Received By tlarge Date 2000-01-28 Time 17:33 Sent To  
Notes
2001-01-08 00:00:00SANITARY RISER DOESN'T COMPLY W/SPC.
 THE LOCATION OF THE PLBG.FIXTURES ON THE
 SANITARY RISER DON'T CORRELATE W/THE
 ARCH.FLOOR PLAN.COUNTYWIDE AMENDMENTS
 TO SPC SEC.104.2.1.
 SANITARY RISER SHALL BE SIGNED AND
 SEALED BY ENG.OF RECORD.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2001-03-09 Cont ID  
Sent By lmartine Date 2001-03-09 Time 13:53 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-03-09 00:00:00APPROVED BY ROBBIE 3/2/01
2001-03-02 00:00:00****************PROVISO*****************
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) PROVIDE FLOOD ZONE ELEVATION
 CERTIFICATE FOR NEW CONSTRUTION WITH BFE
  
 3)PROVIDE PRODUCT APPROVAL FOR
 OVERHEAD GARAGE DOOR THAT HAS DESIGN
 LOADS WHICH EQUAL OR EXCEED THE
 CALCULATED WINDLOADS FOR THE GARAGE
 OPENING OF THE STRUCTURE.
  
 4)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - ARCHED FIXED GLASS
 - STRUCTURAL WINDOW MULLIONS
  
 5) WINDOW PRESSURE SCHEDULE VALUES FOR
 WINDOWS J,S AND T DO NOT CORRESPOND WITH
 THE PRESSURES LISTED ON THE DRAWINGS.
 SUBMIT REVISED SCHEDULE OR REVISED SHEET
 A-4A.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-06-20 Cont ID  
Sent By lsmith Date 2000-06-20 Time 15:34 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
2001-01-08 00:00:00PER TM 6/19/00

Review Stop Z ZONING
Rev No 1 Status P Date 2000-06-22 Cont ID  
Sent By gjoyce Date 2000-06-22 Time 08:52 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***