Plan Review Details - Permit 99121818
Plan Review Stops For Permit 99121818
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-07-31 Cont ID  
Sent By dpalmer Date 2001-07-31 Time 20:23 Rev Time 0.00
Received By dpalmer Date 2001-07-31 Time 20:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-02-05 Cont ID  
Sent By dpalmer Date 2000-02-05 Time 14:58 Rev Time 0.00
Received By dpalmer Date 2000-02-05 Time 14:58 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE: NEED TO SHOW AIC RATING OF
 EQUIPMENT MAINS. MAINS NEED TO BE RATED
 FOR AVAILABLE FAULT CURRENT. AS REQ`D
 BY ARTS: 110-9/110-10/215-5
  
 2)NOTE:SHOW BLDG.STEEL ON PLANS.
  
 3)NOTE:AS REQ`D BY 1993/1993 NFPA-72
 2-2.1.1.1 SMOKE DETECTORS ARE REQ`D
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
  
 4)NOTE: PLEASE SHOW ALL OUTLETS THAT
 ARE SERVING KITCHEN COUNTER SPACE
 AS GFI/GFI PROTECTED.
  
 5)NOTE: PLEASE HAVE THE DEDICATED BATH(S
 CIRCUT(S)LISTED ON PANEL SCHEDULE.
 MUST BE 20AMP AND #12 AWG. AS REQ`D BY
 ART:210-52D OF THE NEC.
  
 PLEASE HAVE ALL THE ABOVE INFORMATION
 SUBMITTED FOR REVIEW AND APPROVAL.
 IF THERE ARE ANY QUESTIONS PLEASE CALL
 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-07-28 Cont ID  
Sent By hmoser Date 2001-07-28 Time 12:08 Rev Time 0.33
Received By hmoser Date 2001-07-28 Time 12:07 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-02-05 Cont ID  
Sent By jleech Date 2000-02-05 Time 11:31 Rev Time 0.35
Received By jleech Date 2000-02-05 Time 11:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-07-28 Cont ID  
Sent By jleech Date 2001-07-28 Time 11:37 Rev Time 0.33
Received By jleech Date 2001-07-28 Time 11:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-02-02 Cont ID  
Sent By tlarge Date 2000-02-02 Time 05:22 Rev Time 0.33
Received By tlarge Date 2000-02-02 Time 05:22 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status P Date 2002-01-14 Cont ID  
Sent By rmcdouga Date 2002-01-14 Time 10:28 Rev Time 1.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-01-14 00:00:00TRUSSES OK, W/LETTER FROM ENGINEER

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2001-10-29 Cont ID  
Sent By rmcdouga Date 2001-10-29 Time 15:21 Rev Time 1.00
Received By rmcdouga Date 2001-10-29 Time 15:24 Sent To  
Notes
2001-10-30 00:00:00TRUSSES UNSAT
 SAME COMMENTS AS PERMIT # 01070623
 10-29-01 RM

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2001-08-07 Cont ID  
Sent By lsmith Date 2001-08-07 Time 16:32 Rev Time 3.50
Received By lsmith Date   Time   Sent To  
Notes
2001-08-07 00:00:00************BUILDING PROVISO************
  
 SBC 104.2.2
  
 1.STRUCTURE IS LOCATED IN AN "A"
 FLOODZONE. A FLOOD ELEVATION
 CERTIFICATE WILLBE REQUIRED BEFORE C/O.
  
 2.SUBMIT ENGINEERED SIGNED & SEALED
 TRUSS DRAWINGS APPROVED BY ARCHITECT OF
 RECORD BEFORE INSTALLING.
  
 3.NO OPTIONS MARKED ON PLANS
 SUBMITTEDANY OPTIONS ADDED MUST BE
 APPROVED WITH PLANS SUBMITTED BEFORE
 PROCEDING WITH
 CHANGE.
  
 ANY QUESTIONS PLEASE CALL LEA SMITH
 BUILDING PLANS EXAMINER 659-8096
 EXT. 8394

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-06-20 Cont ID  
Sent By lsmith Date 2000-06-20 Time 14:49 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
2001-01-08 00:00:00PER TM 6/19/00

Review Stop Z ZONING
Rev No 2 Status P Date 2001-08-06 Cont ID  
Sent By sgraham Date 2001-08-02 Time 14:30 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2001-08-02 00:00:00NEED PLOT PLAN FOR LOT-61 NOT LOT-96

Review Stop Z ZONING
Rev No 1 Status P Date 2000-06-22 Cont ID  
Sent By gjoyce Date 2000-06-22 Time 08:53 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***