| 2001-01-08 00:00:00 | APPROVED WITH PROVISO: |
| | 1-PROVIDE COMPLETE WINDOW INSTALLATION |
| | DETAIL AT BREAKFAST AREA ACCORDING TO |
| | THE PRODUCT APPROVAL AND FASTENING TO |
| | THE STEEL COLUMN. |
| | 2-PROVIDE ATTIC ACCESS AT GARAGE CEILING |
| | SECTION 2309.6 SBC 1997. |
| | 3-PROVIDE COMPLETE AIR HANDLER UNIT |
| | HANGING DETAILS. SPECIFY ALL FASTENERS |
| | SEC 104.2.2 CITY AMENDMENTS. |
| | 4-SLIDING GLASS DOORS WITH TRANSOM: |
| | -PROVIDE A COMPLETE DETAIL CLEARLY |
| | SHOWING ALL THE COMPONENTS AND |
| | FASTENERS ACCORDING TO THE PRODUCT |
| | APPROVALS FOR SLIDING GLASS DOORS, |
| | STRUCTURAL MULLIONS AND FIXED WINDOWS. |
| | 5-CLARIFY SHEET A-6. CLEARLY COORDINATE |
| | ALL KEYED DETAILS. |
| | 6-NEED SURVEY SIGNED, SEALED AND DATED. |
| | SEC 104.2 CITY AMENDMENTS. |
| | 7-REVISE DESIGN CERTIFICATION FOR |
| | BUILDING CODE COMPLIANCE FORM. SEE |
| | TABLE 1606.2A FOR THE VELOCITY |
| | PRESSURE AT 18'-0" MEAN ROOF HEIGHT. |
| | 8-SPECIFY CEILING FAN SIZES AS PER TABLE |
| | 6-6 OF FLORIDA ENERGY CODE, 1997 ED. |
| | AND CREDIT TAKEN IN ENERGY CALCULATION |
| | 9-RE-SUBMIT GARAGE DOOR PRODUCT APPROVAL |
| | DESIGN LOADS SPECIFIED BY THE |
| | ARCHITECT ARE HIGHER THAN THOSE IN THE |
| | PRODUCT APPROVAL SUBMITTED. |
| | 10-PROVIDE PRODUCT APPROVAL FOR ARCHED |
| | WINDOWS AS WELL. |
| | 11-PROVIDE COMPLETE INFORMATION FOR |
| | STORM PANELS UNDER A SEPARATE PERMIT. |
| | NOTE: PLEASE USE INSTALLATION SCHEDULE |
| | SAMPLE, ATTACHED, AND FILL IN ALL THE |
| | INFORMATION. |