Plan Review Details - Permit 99121739
Plan Review Stops For Permit 99121739
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-03-31 Cont ID  
Sent By dpalmer Date 2000-03-31 Time 15:18 Rev Time 0.00
Received By dpalmer Date 2000-03-31 Time 15:18 Sent To  
Notes
2001-01-08 00:00:00***************PROVISO *****************
  
 1)NOTE: STILL SHOWING MAIN ON RISER BUT
 NOT ON PLANS?????
  
 2)NOTE: BATH DEDICATED CIRCUT IS NOT
 SHOWN ON PANEL SCHEDULE.
  
 3)NOTE: AS PER 210-8-A-6 ALL OUTLETS
 SERVING KITCHEN COUNTER SPACE ARE TO BE
 GFI/GFI PROTECTED!! PLEASE INDICATE ON
 PLANS,,,,ALL.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-02-24 Cont ID  
Sent By dpalmer Date 2000-02-24 Time 07:10 Rev Time 0.00
Received By dpalmer Date 2000-02-24 Time 07:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-01-22 Cont ID  
Sent By dpalmer Date 2000-01-22 Time 13:42 Rev Time 0.00
Received By dpalmer Date 2000-01-22 Time 13:41 Sent To  
Notes
2001-01-08 00:00:00************* UNSAT *******************
  
 THESE ARE NOTES THAT WERE ALREADY GIVEN
 AT OTHER TIMES.
  
 1)NOTE: PLEASE SUBMIT AIC RATING OF
 EQUIPMENT MAINS!! AND OR PANELS.
 AIC RATING IS FIGURED FROM FAULT CURRENT
 CALCULATIONS. REQ`D BY ARTS;230-65.110-9
 AND 215-5
  
 2)NOTE;AS PER NFPA-72 2-2.1.1.1 SMOKE
 DETECTORS ARE REQ`D INSIDE AND OUTSIDE
 ALL SLEEPING ROOMS. PLEASE CORRECT.
  
 3)NOTE: AS REQ`D BY ART;210-8-A-6 ALL
 OUTLETS SERVING KITCHEN COUNTERSPACE
 ARE TO BE GFI/GFI PROTECTED. ALL NEED TO
 BE LABELED THAT WAY.
  
 4)NOTE:PLEASE CORRECT OPTIONAL KITCHEN
 PLAN.
  
 5)NOTE:PLANS DON`T SHOW MAIN DISC.ON THE
 SIDE OF THE HOUSE. WHICH IS CORRECT?
 PLAN OR RISER DIAGRAM?
  
 6)NOTE: AS REQ`D BY 250-81/215-5
 PLEASE SHOW BLDG.STEEL AS THE OTHER
 METHOD OF GROUNDING ELECTRODE CONDUCTOR.
  
 7)NOTE:AS REQ`D BY 210-52D/215-5 PLEASE
 HAVE LISTED ON PANEL SCHEDULE THE DED-
 -ICATED BATH(S) CIRCUT(S) REQ`D TO BE
 20AMP AND #12 AWG.
  
 PLEASE HAVE ALL THE ABOVE INFORMATION
 CORRECTED AND SUBMITTED FOR REVIEW AND
 APPROVAL. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-02-24 Cont ID  
Sent By jleech Date 2000-01-18 Time 15:12 Rev Time 0.00
Received By bstaples Date 2000-02-24 Time 11:32 Sent To  
Notes
2001-01-08 00:00:00************PROVISO*******************
 1. 4 TON UNIT IS NOT CAPABLE OF
 PROVIDING 1740 CFM. REVISE DRAWINGS.
 2. ELECTRIC EXHAUST FAN IS REQUIRED IN
 MASTER TOILET ROOM.

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-01-04 Cont ID  
Sent By tlarge Date 2000-01-04 Time 19:15 Rev Time 0.33
Received By tlarge Date 2000-01-04 Time 19:15 Sent To  
Notes
2001-01-08 00:00:00**************PROVISO*******************
 SANITARY RISER DOESN'T MATCH FLOOR PLAN.
 SUBMIT REVISED RISER PRIOR TO RGH.PLBG.
 INSP.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2000-02-25 Cont ID  
Sent By jgomez Date 2000-02-25 Time 13:08 Rev Time 2.00
Received By jgomez Date 2000-02-25 Time 13:08 Sent To  
Notes
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-FLOOD ZONE A8. PROVIDE ELEVATION
 CERTIFICATE.
 2-SEE COMMENTS ON PLANS AND REVISE/
 UPDATE AS REQUIRED.
 3-SEE PROVISOS BY OTHER TRADES.
 4-RE-SUBMIT GARAGE DOOR PRODUCT APPROVAL
 DRAWINGS DON'T MATCH PRODUCT APPROVAL.
 WHY FINAL PRODUCT APPROVAL BY SBCCI
 DOESN'T HAVE A NUMBER ASSIGNED?
 5-STORM PANELS:
 -INSTALLATION SCHEDULE AND KEY PLAN
 DON'T MATCH PLANS. REVISE AS REQUIRED
 AND COMPLETE ALL THE INFORMATION AS
 REQUESTED ON CITY SAMPLE FOR
 INSTALLATION SCHEDULE ATTACHED.
 -SEE NOTE #4 ON SHEET 3 OF 5 OF STORM
 PANELS DRAWINGS. INSTALLATION SCHED.
 CALLS FOR A 33" STORM PANEL AND THIS
 NOTE LIMITS THE STORM PANELS TO 40"
 REVISE AS REQUIRED.
 6-ENTRY DOOR:
 -CLEARLY SPECIFY FASTENERS TO BE USED
 ACCORDING TO THE PRODUCT APPROVAL AND
 FRAME DETAIL SPECIFIED BY ENGINEER ON
 SHEET A-6.
 -DRAWINGS IN PRODUCT APPROVAL ARE NOT
 CLEAR OR IMCOMPLETE.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2000-02-24 Cont ID  
Sent By jgomez Date 2000-01-29 Time 16:12 Rev Time 2.50
Received By jgomez Date 2000-01-29 Time 16:12 Sent To  
Notes
2001-01-08 00:00:00CHECKLIST:
 1-PAY IMPACT FEES.
 2-UPDATE/REVISE ALL DRAWINGS. SEE
 COMMENTS ON PLANS.
 3-FOOTING F2 TO BE 16" DEEP MIN.
 SEC 1804.1.3 SBC 1997.
 4-REVISE ELEVATIONS TO MATCH FLOOR PLAN.
 5-REVISE SURVEY. THIS PROPERTY IS ON
 FLOOD ZONE "A8' NOT FLOOD ZONE B.
 6-PROVIDE COMPLETE BUCK DETAILS FOR
 EXTERIOR DOORS, WINDOWS AND GARAGE
 DOOR.
 7-REVISE ENERGY CALCULATIONS. SOUTH IS
 THE REGION NOT THE CLIMATE ZONE. THE
 CLIMATE ZONE IS #8.
 8-PROVIDE PRODUCT APPROVAL FOR ENTRY
 DOOR WITH SIDELITES ASSEMBLY.
 9-GARAGE DOOR PRODUCT APPROVAL:
 -THERE IS NO A LISTING FOR THIS DOORS
 WITH SBCCI.
 -DESIGN PRESSURES DON'T MEET THE DESIGN
 PRESSURES CALCULATED BY THE ENGINEER
 -DRAWINGS DON'T MATCH REPORT.
 10-PROVIDE COMPLETE INFORMATION FOR
 STORM PANELS (OR INFORMATION MAY BE
 SUBMITTED LATER UNDER A SEPARATE
 PERMIT.

Review Stop Z ZONING
Rev No 1 Status P Date 1999-12-30 Cont ID  
Sent By gjoyce Date 1999-12-30 Time 11:15 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***