| Plan Review Stops For Permit 99121713 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2000-08-02 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-08-02 |
Time |
18:07 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-08-02 |
Time |
18:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-02-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-02-05 |
Time |
13:03 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-02-05 |
Time |
13:03 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE: NEED TO SUBMIT AIC RATING | | | OF EQUIPMENT MAINS.SHOW ON PLANS. | | | AS REQ`D BY ARTS:110-9/110-10/215-5 | | | | | | 2)NOTE:AS PER NFPA-72 2-2.1.1.1 SMOKE | | | DETECTORS ARE REQ`D INSIDE AND OUTSIDE | | | ALL SLEEPING ROOMS. | | | | | | 3)NOTEL SHOW MAIN NEXT TO METER ON PLANS | | | | | | 4)NOTE: AS REQ`D BY 210-8-A-6 ALL OUTLET | | | SERVING KITCHEN COUNTER SPACE ARE TO BE | | | GFI/GFI PROTECTED. | | | | | | 5)NOTE: PLEASE LIST THE DEDICATED BATH(S | | | CIRCUT ON PANEL SCHEDULE AS REQ`DBY | | | ART; 210-52D/215-5 | | | | | | NEED TO SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW AND APPROVAL. IF THERE ARE | | | ANY QUESTIONS PLEASE CALL 659-8096 | | | EXT 8372 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2000-08-08 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-08-08 |
Time |
11:50 |
Rev Time |
1.00 |
| Received By |
cthirben |
Date |
2000-08-08 |
Time |
11:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2000-02-03 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2000-02-03 |
Time |
15:05 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
2000-02-03 |
Time |
15:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2000-08-02 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-02 |
Time |
06:21 |
Rev Time |
0.33 |
| Received By |
tlarge |
Date |
2000-08-02 |
Time |
06:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2000-01-28 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-01-28 |
Time |
18:06 |
Rev Time |
0.33 |
| Received By |
tlarge |
Date |
2000-01-28 |
Time |
18:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
4 |
Status |
P |
Date |
2001-02-16 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2001-02-16 |
Time |
17:00 |
Rev Time |
0.25 |
| Received By |
jgomez |
Date |
2001-02-16 |
Time |
17:00 |
Sent To |
|
|
| Notes |
| 2001-02-16 00:00:00 | TRUSS DRAWINGS APPROVAL. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
3 |
Status |
F |
Date |
2001-01-12 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2001-01-12 |
Time |
08:52 |
Rev Time |
0.50 |
| Received By |
jgomez |
Date |
2001-01-12 |
Time |
08:51 |
Sent To |
|
|
| Notes |
| 2001-01-12 00:00:00 | TRUSS DRAWINGS CHECKLIST: | | | 1-TRUSS DRAWINGS GENERAL DETAILS AND | | | SPECIFICATIONS PACKAGE NEED TO BE | | | COORDINATED AND UPDATED. THERE ARE | | | DETAILS AND SPECIFICATIONS THAT ARE | | | TOO OLD AND REFERENCING OLD CODES. | | | -ENGINEER IS SIGNING AND SEALING | | | DOCUMENTS THAT HAVE THE NAME OF | | | ANOTHER ENGINEER. | | | -ENGINEER TO FOLLOW ALL REQUIREMENTS | | | OF CHAPTER 471 FLORIDA STATUTES WHEN | | | SUBMITTING DOCUMENTS FOR PUBLIC | | | RECORD3-SUPPORT REPORT INDICATES THAT | | | TRUSSES | | | WERE DESIGNED USING SBC 1991. CITY HAS | | | ADOPTED SBC 1997. | | | | | | | | | | | | | | | IF YOU HAVE ANY QUESTIONS, CALL JULIO | | | GOMEZ AT 659-8096 EXT. 8232. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2000-08-09 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2000-08-09 |
Time |
14:38 |
Rev Time |
4.00 |
| Received By |
rmcdouga |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO | | | | | | 1)FLOOD ELEVATION CERTIFICATE WILL BE | | | REQUIRED. | | | | | | 2)WIND ENGINEERING / STRUCTURAL NOTES ON | | | SHEET A-4 REFERS TO 1994 STANDARD | | | BUILDING CODE,WHICH IS NO LONGER CURRENT | | | PLEASE REVISE TO REFLECT 1997 SBC,WHICH | | | IS THE CURRENT VERSION OF THE CODE | | | ADOPTED BY PALM BEACH COUNTY AND THE | | | CITY OF WEST PALM BEACH. | | | | | | 3)REVISE WIRE LATHE APPLICATION DETAIL | | | ON SHEET A-3 WHICH INCORRECTLY GIVES | | | VERTICLE WALL FASTENER SIZE FOR CEILING | | | APPLICATION. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2000-06-20 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2000-06-20 |
Time |
15:07 |
Rev Time |
0.50 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | FAILED 6/19/00 TM |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2000-06-22 |
|
|
Cont ID |
|
| Sent By |
gjoyce |
Date |
2000-06-22 |
Time |
09:00 |
Rev Time |
0.25 |
| Received By |
gjoyce |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|