Plan Review Details - Permit 99121713
Plan Review Stops For Permit 99121713
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-08-02 Cont ID  
Sent By dpalmer Date 2000-08-02 Time 18:07 Rev Time 0.00
Received By dpalmer Date 2000-08-02 Time 18:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-02-05 Cont ID  
Sent By dpalmer Date 2000-02-05 Time 13:03 Rev Time 0.00
Received By dpalmer Date 2000-02-05 Time 13:03 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE: NEED TO SUBMIT AIC RATING
 OF EQUIPMENT MAINS.SHOW ON PLANS.
 AS REQ`D BY ARTS:110-9/110-10/215-5
  
 2)NOTE:AS PER NFPA-72 2-2.1.1.1 SMOKE
 DETECTORS ARE REQ`D INSIDE AND OUTSIDE
 ALL SLEEPING ROOMS.
  
 3)NOTEL SHOW MAIN NEXT TO METER ON PLANS
  
 4)NOTE: AS REQ`D BY 210-8-A-6 ALL OUTLET
 SERVING KITCHEN COUNTER SPACE ARE TO BE
 GFI/GFI PROTECTED.
  
 5)NOTE: PLEASE LIST THE DEDICATED BATH(S
 CIRCUT ON PANEL SCHEDULE AS REQ`DBY
 ART; 210-52D/215-5
  
 NEED TO SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW AND APPROVAL. IF THERE ARE
 ANY QUESTIONS PLEASE CALL 659-8096
 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-08-08 Cont ID  
Sent By cthirben Date 2000-08-08 Time 11:50 Rev Time 1.00
Received By cthirben Date 2000-08-08 Time 11:50 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-02-03 Cont ID  
Sent By jleech Date 2000-02-03 Time 15:05 Rev Time 0.50
Received By jleech Date 2000-02-03 Time 15:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-08-02 Cont ID  
Sent By tlarge Date 2000-08-02 Time 06:21 Rev Time 0.33
Received By tlarge Date 2000-08-02 Time 06:07 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-01-28 Cont ID  
Sent By tlarge Date 2000-01-28 Time 18:06 Rev Time 0.33
Received By tlarge Date 2000-01-28 Time 18:06 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status P Date 2001-02-16 Cont ID  
Sent By jgomez Date 2001-02-16 Time 17:00 Rev Time 0.25
Received By jgomez Date 2001-02-16 Time 17:00 Sent To  
Notes
2001-02-16 00:00:00TRUSS DRAWINGS APPROVAL.

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2001-01-12 Cont ID  
Sent By jgomez Date 2001-01-12 Time 08:52 Rev Time 0.50
Received By jgomez Date 2001-01-12 Time 08:51 Sent To  
Notes
2001-01-12 00:00:00TRUSS DRAWINGS CHECKLIST:
 1-TRUSS DRAWINGS GENERAL DETAILS AND
 SPECIFICATIONS PACKAGE NEED TO BE
 COORDINATED AND UPDATED. THERE ARE
 DETAILS AND SPECIFICATIONS THAT ARE
 TOO OLD AND REFERENCING OLD CODES.
 -ENGINEER IS SIGNING AND SEALING
 DOCUMENTS THAT HAVE THE NAME OF
 ANOTHER ENGINEER.
 -ENGINEER TO FOLLOW ALL REQUIREMENTS
 OF CHAPTER 471 FLORIDA STATUTES WHEN
 SUBMITTING DOCUMENTS FOR PUBLIC
 RECORD3-SUPPORT REPORT INDICATES THAT
 TRUSSES
 WERE DESIGNED USING SBC 1991. CITY HAS
 ADOPTED SBC 1997.
  
  
  
  
 IF YOU HAVE ANY QUESTIONS, CALL JULIO
 GOMEZ AT 659-8096 EXT. 8232.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2000-08-09 Cont ID  
Sent By rmcdouga Date 2000-08-09 Time 14:38 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVISO
  
 1)FLOOD ELEVATION CERTIFICATE WILL BE
 REQUIRED.
  
 2)WIND ENGINEERING / STRUCTURAL NOTES ON
 SHEET A-4 REFERS TO 1994 STANDARD
 BUILDING CODE,WHICH IS NO LONGER CURRENT
 PLEASE REVISE TO REFLECT 1997 SBC,WHICH
 IS THE CURRENT VERSION OF THE CODE
 ADOPTED BY PALM BEACH COUNTY AND THE
 CITY OF WEST PALM BEACH.
  
 3)REVISE WIRE LATHE APPLICATION DETAIL
 ON SHEET A-3 WHICH INCORRECTLY GIVES
 VERTICLE WALL FASTENER SIZE FOR CEILING
 APPLICATION.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-06-20 Cont ID  
Sent By lsmith Date 2000-06-20 Time 15:07 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
2001-01-08 00:00:00FAILED 6/19/00 TM

Review Stop Z ZONING
Rev No 1 Status P Date 2000-06-22 Cont ID  
Sent By gjoyce Date 2000-06-22 Time 09:00 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***