Plan Review Details - Permit 99121697
Plan Review Stops For Permit 99121697
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-08-06 Cont ID  
Sent By dpalmer Date 2001-08-06 Time 15:51 Rev Time 0.00
Received By dpalmer Date 2001-08-06 Time 15:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-02-05 Cont ID  
Sent By dpalmer Date 2000-02-05 Time 12:42 Rev Time 0.00
Received By dpalmer Date 2000-02-05 Time 12:41 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT ****************
  
 1)NOTE: NEED TO SUBMIT AIC RATING OF
 EQUIPMENT MAINS.ALL SERVICE EQUIPMENT
 MAINS TO BE RATED TO HANDLE AVAILABLE
 FAULT CURRENT. CAN BE FIGURED FROM
 FAULT CURRENTCALCULATIONS. ALL AS PER
 ARTS:110-9/110-10/215-5
  
 2)NOTE: AS PER NFPA-72 2-2.1.1.1 SMOKE
 DETECTORS ARE REQ`D INSIDE AND OUTSIDE
 ALL SLEEPING ROOMS.
  
 3)NOTE: PLEASE SHOW THE DEDICATED BATH(S
 CIRCUT ON PANEL SCHEDULE. AS REQ`D BY
 ART;210-52D OF THE NEC.
  
 4)NOTE:SHOW MAIN DISC. ON PLANS AS IT
 IS SHOWN ON RISER DIAGRAM.
 5)NOTE: ALL OUTLETS SERVING KITCHEN
 COUNTERSPACE ARE TO BE GFI/GFI PROTECTED
 AS PER 210-8-A-6
  
 ALL THE ABOVE INFORMATION NEED TO BE
 SUBMITTED FOR REVIEW AND APPROVAL. IF
 THERE ARE ANY QUESTIONS PLEASE CALL
 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-08-01 Cont ID  
Sent By hmoser Date 2001-08-01 Time 18:23 Rev Time 0.33
Received By hmoser Date 2001-08-01 Time 18:22 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-02-03 Cont ID  
Sent By jleech Date 2000-02-03 Time 15:14 Rev Time 0.50
Received By jleech Date 2000-02-03 Time 15:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-07-28 Cont ID  
Sent By jleech Date 2001-07-28 Time 11:46 Rev Time 0.25
Received By jleech Date 2001-07-28 Time 11:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-01-28 Cont ID  
Sent By tlarge Date 2000-01-28 Time 18:15 Rev Time 0.50
Received By tlarge Date 2000-01-28 Time 18:14 Sent To  
Notes
2001-01-08 00:00:00SANITARY RISER IS NOT TO CODE AND NUMBER
 & TYPE OF FIXTURES ON SANITARY DOESN'T
 MATCH FLOOR PLAN.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2001-08-22 Cont ID  
Sent By jgomez Date 2001-08-22 Time 19:47 Rev Time 3.50
Received By jgomez Date 2001-08-22 Time 19:47 Sent To  
Notes
2001-08-22 00:00:00APPROVED WITH PROVISO:
 1-FLOOD ZONE A8. WILL NEED TO PROVIDE
 THE ELEVATION CERTIFICATE.
 2-REVISE HANDRAIL HEIGHT TO COMPLY WITH
 SECTION 1007.5.1 SBC 1997.HANDRAIL
 IS NOT PART OF THE GUARDRAIL.
 3-SEE COMMENTS ON PLANS. REVISE AS REQ'D
 4-SPECIFY SAFETY GLASS AT BEDROOM OPTION
 PLAN. SEE SHEET A-8.
 5-UPDATE STORM SHUTTERS KEY PLAN AND
 INSTALLATION SCHEDULE TO MATCH THE
 ARCHITECTURAL PLANS AND ELEVATIONS.
 6-PROVIDE LEGIBLE DRAWINGS FOR GARAGE
 AND FRENCH DOORS PRODUCT APPROVALS.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-06-20 Cont ID  
Sent By lsmith Date 2000-06-20 Time 15:39 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
2001-01-08 00:00:00FAILED PER TM 6/19/00

Review Stop Z ZONING
Rev No 1 Status P Date 2000-06-22 Cont ID  
Sent By gjoyce Date 2000-06-22 Time 08:50 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
2001-01-08 00:00:00STREET SIDE MUST BE 12'5" NOT 10'