Plan Review Details - Permit 99121632
Plan Review Stops For Permit 99121632
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-01-16 Cont ID  
Sent By dpalmer Date 2001-01-16 Time 16:08 Rev Time 0.00
Received By dpalmer Date 2001-01-16 Time 16:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2000-11-14 Cont ID  
Sent By dpalmer Date 2000-11-14 Time 09:13 Rev Time 0.00
Received By dpalmer Date 2000-11-14 Time 09:13 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE SEE NOTES FROM FIRST RE-
 -VIEW. NOT ALL NOTES WERE ADDRESSED.
  
 2)NOTE: PLEASE SEE PANEL SCHEDULE,PLEASE
 LIST THE REQ`D BATH(S) CIRCUIT(S) PER
 210-11-C-3. #12, 20A.
  
 3)NOTE: PLEASE SEE 384-15. PANELS ARE
 NOT PERMITTED TO HAVE MORETHAN 42 SPACES
  
 4)NOTE: PLEASE SEE 210-8-A-6.ALL OUTLETS
 SERVING KITCHEN COUNTERSPACE ARE TO GFI/
 GFI PROTECTED. PLEASE SHOW AND PLEASE
 SHOW ON KITCHEN OPT PLAN ALSO.
  
 5)NOTE: PLEASE SEE 210-52H FOR OUTLET
 REQ`D IN MASTER BEDROOM HALLWAY.
  
 6)NOTE: PLEASE SHOW THE MAIN DISCONNECT
 ON THE PLAN AS IT IS SHOWN ON THE RISER
 DIAGRAM. 215-5
  
 7)NOTE: PLEASE SUBMIT SUBMIT CLARIFICAT-
 ION ON THE "DOUBLE TUB" WRIITEN ON RISER
 AND PANEL SCHEDULE??
  
  
 PLEASE MAKE THE ABOVE CHANGES AND SUBMIT
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-02-05 Cont ID  
Sent By dpalmer Date 2000-02-05 Time 15:48 Rev Time 0.00
Received By dpalmer Date 2000-02-05 Time 15:48 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE: PLEASE SHOW THE AIC RATING OF
 EQUIPMENT MAINS. MAINS ARE TO BE RATED
 FOR THE AVAILABLE FAULT CURRENT. AS REQ`
 -D BY ARTS: 110-9/110-10/215-5 OF THE
 NEC. PLEASE SHOW ON PLANS/
  
 2)NOTE:PLEASE CORRECT THE OPTIONAL
 KITCHEN PLAN.
  
 3)NOTE: RISER DIAGRAM SHOW MAIN DISC.
 PLEASE DRAW ON PLANS NEXT TO METERCAN.
  
 4)NOTE: SHOW THE OTHER GROUND AS BEING
 BLDG.STEEL.
  
 5)NOTE:AS REQ`D BY 210-52H NEED TO HAVE
 OUTLET IN THE MASTER BEDROOM HALL.10`
 OR MORE.
  
 6)NOTE:AS REQ`D BY NFPA-72 2-2.1.1.1
 SMOKE DETECTORS ARE REQ`D INSIDE AND
 OUTSIDE ALL SLEEPING ROOMS.
  
 7)NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED. AS REQ`D BY 210-8-A-6
  
  
 PLEASE HAVE ALL THE ABOVE INFORMATION
 SUBMITTED FOR REVIEW AND APPROVAL.
 IF THERE ARE ANY QUESTIONS PLEASE CALL
 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-02-05 Cont ID  
Sent By jleech Date 2000-02-05 Time 07:35 Rev Time 0.50
Received By jleech Date 2000-02-05 Time 07:34 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-01-28 Cont ID  
Sent By tlarge Date 2000-01-28 Time 18:03 Rev Time 0.33
Received By tlarge Date 2000-01-28 Time 18:03 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status F Date 2001-02-15 Cont ID  
Sent By jgomez Date 2001-02-14 Time 10:41 Rev Time 0.50
Received By jgomez Date 2001-02-14 Time 10:41 Sent To  
Notes
2001-02-14 00:00:00TRUSS DRAWINGS CHECKLIST:
  
 1-UNABLE TO IDENTIFY ENGINEER.
 -ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME ADDRESS AND NUMBER ON EACH SHEET
 AS REQUIRED BY CHAPTER 471 FLORIDA
 STATUTES.
  
  
  
  
  
  
 BUILDING PLAN REVIEWER: JULIO GOMEZ AT
 659-8096 EXT. 8232.

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2001-01-19 Cont ID  
Sent By jgomez Date 2001-01-19 Time 16:27 Rev Time 1.00
Received By jgomez Date 2001-01-19 Time 16:27 Sent To  
Notes
2001-01-19 00:00:00APPROVED WITH PROVISO:
  
 1-UPDATE ALL PLANS AS REQUIRED. SEE
 COMMENTS ON PLANS.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2000-11-30 Cont ID  
Sent By jgomez Date 2000-11-30 Time 13:53 Rev Time 1.50
Received By jgomez Date 2000-11-30 Time 13:53 Sent To  
Notes
2001-01-08 00:00:00CHECKLIST:
 1-SURVEY DOESN'T MATCH THE LAGUNA MODEL.
 2-REVISE ENERGY CALCULATIONS:
 -NEED THE LAGUNA MODEL
 -NEED ORIGINAL SIGNATURE AND DATE OF
 PERSON WHO PREPARED THE ENERGY CALCS.
 3-REVISE/UPDATE ALL DRAWINGS AS REQUIRED
 SEE NOTES ON REVIEWED SET.
 4-SEE COMMENTSBY ELECTRICAL PLAN
 REVIEWER.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-06-20 Cont ID  
Sent By lsmith Date 2000-06-20 Time 10:03 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
2001-01-08 00:00:00SEE NOTES PER TM

Review Stop Z ZONING
Rev No 1 Status P Date 2000-06-19 Cont ID  
Sent By gjoyce Date 2000-06-19 Time 16:35 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***