| 2001-01-08 00:00:00 | DENIED |
| | |
| | 1)DETAIL OF FLOOR TRUSS,SHOWN ON SHEET |
| | A-5,ENTERING AND TERMINATING IN MASONRY |
| | WALL HAS NO PROVISION FOR FIRE CUT.1997 |
| | SBC SEC.2305.4. |
| | |
| | 2)FLOOD ELEVATION CERTIFICATE WILL BE |
| | REQUIRED. |
| | |
| | 3)SURVEY INDICATES RIGHT SIDE OF |
| | STRUCTURE IS LOCATED ON PROPERTY LINE. |
| | TABLE 600 OF 1997 SBC DOES NOT ALLOW ANY |
| | OPENINGS IN A WALL LOCATED ON ZERO LOT |
| | LINES. THE PLANS SHOW A SLIDING GLASS |
| | DOOR AND 2 WINDOWS IN THIS WALL.OPTIONAL |
| | WALL & GATE, A/C EQUIPMENT & PAD, PAD |
| | OUTSIDE SGD AND CONC. FOOTER FOR COLUMN |
| | ARE ALL ENCROACHING ON ADJACENT LOT. |
| | PLEASE CORRECT. |
| | |
| | 4)SUBMIT REVISED STORM PANEL KEY PLAN |
| | AND SCHEDULE THAT CORRESPONDS TO THE |
| | OPTIONS THAT WILL BE USED. |
| | |
| | 5)PROVIDE 2 CURRENT COPIES OF METRO-DADE |
| | OR SBCCI PRODUCT APPROVALS FOR EXTERIOR |
| | OUTSWING STEEL DOOR WITH SIDELITES AS |
| | INDICATED ON PLANS. PRODUCT APPROVALS |
| | ARE REQUIRED FOR SPECIFIC PRODUCT THAT |
| | WILL BE INSTALLED. |
| | |
| | 6)THE VALUES LISTED IN THE WIND PRESSURE |
| | SCHEDULE ON SHEET A-4A DO NOT AGREE WITH |
| | THE PRESSURES LISTED ON THE DRAWING FOR |
| | WINDOWS J,S & T. PLEASE CORRECT. |
| | |
| | 7)ADDITIONAL IMPACT FEES ARE OWED TO THE |
| | COUNTY FOR THE ADDITIONAL 268 SQFT UNDER |
| | A/C WHEN LOFT OPTION IS ADDED AS |
| | INDICATED ON PRINTS. |
| | |
| | 8)SPECIFICATIONS FOR GARAGE DOOR |
| | INCLUDED WITH PRODUCT APPROVAL INDICATE |
| | A NEGATIVE DESIGN PRESSURE OF -33PSF FOR |
| | 16'X 7' DOOR, WIND LOADS SHOWN ON PLANS |
| | SHEET A-4A LISTS NEG. PRESSURE OF -34PSF |
| | PLEASE CORRECT. |