Plan Review Details - Permit 99121526
Plan Review Stops For Permit 99121526
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-09-26 Cont ID  
Sent By hpiskura Date 2000-09-26 Time 14:56 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-01-08 00:00:00OWES IMPACT AND RADON FEES

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-07-28 Cont ID  
Sent By hpiskura Date 2000-07-28 Time 11:01 Rev Time 99.00
Received By hpiskura Date 2000-07-24 Time 16:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2001-06-12 Cont ID  
Sent By dpalmer Date 2001-06-12 Time 08:21 Rev Time 0.00
Received By dpalmer Date 2001-06-12 Time 08:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status N Date 2001-05-15 Cont ID  
Sent By dpalmer Date 2001-05-15 Time 07:50 Rev Time 0.00
Received By dpalmer Date 2001-05-15 Time 07:50 Sent To  
Notes
2001-05-15 00:00:00NO ELECTRICAL PLANS SUBMITTED FOR
 ADDING TWO OVERHEAD GARAGE DOORS.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2001-01-31 Cont ID  
Sent By dpalmer Date 2001-01-31 Time 15:51 Rev Time 0.00
Received By dpalmer Date 2001-01-31 Time 12:36 Sent To  
Notes
2001-01-31 00:00:00REVISIONS OK

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-10-27 Cont ID  
Sent By jleahy Date 2000-10-27 Time 14:29 Rev Time 1.30
Received By jleahy Date 2000-10-27 Time 14:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2000-09-25 Cont ID  
Sent By dpalmer Date 2000-09-25 Time 12:12 Rev Time 0.00
Received By jleahy Date 2000-10-27 Time 14:11 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT ****************
  
 1)NOTE:PLEASE SEE PP13 ON E-12. ALL
 CONTINUOUS LOADS TO BE SHOWN AT 125%
  
 2)NOTE: PLEASE SEE LOADS SHOWN ON PP14
 EM2,UPS PANEL. PLEASE SEE THAT ALL
 LOADS DO NOT COERRELATE. LOADS SHOWN ON
 UPS PANEL TOTAL AT 3KVA PER PHASE AND
 CONNECTED SHOWN HIGHER ON PANEL SCHEDULE
 PLEASE SEE PP14 CONNECTED SHOWN AT 28.42
 AND CONNECTED ON PANEL AT 29.42 AND
 TOTAL AT BOTTOM SHOWN AT 25.42.PLEASE
 CORRELATE THE ABOVE LOADS.
  
 3)NOTE: PLEASE SEE LP1 CONTINUOUS LOADS
 NEED TO BE SHOWN AT 125%. CONTINUOUS
 LOADSON OTHER PANELS SHOWN AT 125%???
  
 PLEASE SUBMIT THE ABOVE INFORMATON FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASECALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2000-09-22 Cont ID  
Sent By dpalmer Date 2000-06-29 Time 20:17 Rev Time 0.00
Received By dpalmer Date 2000-06-29 Time 20:17 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2000-10-20 Cont ID  
Sent By mgonzale Date 2000-10-20 Time 07:55 Rev Time 1.00
Received By mgonzale Date   Time   Sent To  
Notes
2001-01-08 00:00:00"THIS PERMIT IS APPROVED SUBJECT TO
 RESOLUTION OF THE ENVIRONMENTAL ISSUES
 OUTLINED IN THE FLORIDA DEPARTMENT OF
 ENVIRONMENTAL PROTECTION MEMORENDUM
 DATED JULY 25, 2000, ATTACHED HERETO,
 RELATING TO THE FORMER GOLF COURSE
 PROPERTY AND LETTER OF AGREEMENT BETWEEN
 BRANDSMART AND THE CITY OF WEST PALM
 BEACH"(RICHARD D. PITTMAN)
  
 THIS IS FOR THE BUILDING ONLY.
 THIS PERMIT DOES NOT INCLUDE THE PARKING
 LOT OR PARKING LOT DRAINAGE. ADDITIONAL
 PERMIT WILL BE REQUIRED FOR THE PARKING
 LOT AND PARKING LOT DRAINAGE.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2000-06-26 Cont ID  
Sent By mgonzale Date 2000-06-26 Time 13:51 Rev Time 1.00
Received By mgonzale Date   Time   Sent To  
Notes
2001-01-08 00:00:00REQUIRES WATER, SEWER, PAVING AND DRAINA
 GE PLANS.
 PLEASE SUBMITT 2 COPIES FOR REVIEW TO
 PUBLIC UTILITIES ENGINEERING SERVICES
 1000 45TH ST. SUITE 15, WPB FL 33415
 ATTENTION DEAN OR MANNY.
 COPIES MUST ALSO BE SUBMITTED AT P,B&Z
 WITH APPLICABLE FEES.
 PLEASE MAKE NOTICE OF STORM REQUIREMENTS
 THAT REQUIRE LETTER STATING PERVIOUS
 AND IMPERVIOUS CALCULATIONS, ETC.
  
 SEE GENERAL COMMENTS ATTACHED.
 IF ANY QUESTIONS FEEL FREE TO CONTACT
 MANNY OR DEAN AT 561 659 8040.

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2001-02-06 Cont ID  
Sent By mcarsill Date 2001-02-06 Time 09:12 Rev Time 0.00
Received By mcarsill Date 2001-02-06 Time 09:11 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2000-10-24 Cont ID  
Sent By mcarsill Date 2000-10-24 Time 15:16 Rev Time 0.00
Received By mcarsill Date 2000-10-24 Time 15:16 Sent To  
Notes
2001-01-08 00:00:001) OBTAINED A FIRE HYDRANT LOCATION
 MAP FROM KIMLEY HORN AND ASSOCIATES
 INDICATING FIRE HYDRANT LOCATIONS
 AND A FIRE LANE FOR THE BUILDING.
 2) RECEIVED LETTER FROM ARCHITECT
 ADDRESSING PLAN REVIEW COMMENTS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2000-09-07 Cont ID  
Sent By mcarsill Date 2000-09-07 Time 09:56 Rev Time 0.00
Received By mcarsill Date 2000-09-07 Time 09:51 Sent To  
Notes
2001-01-08 00:00:001) BUILDING ADDRESS TO BE PLACED ON
 BUILDING IN ACCORDANCE WITH CITY
 ORDINANCE.
 2) TRAVEL DISTANCE OF 250 FEET SHWON ON
 PLANS. SINCE THE BUILDING IS A MIXED
 OCCUPANCY THE MOST STRINGENT TRAVEL
 DISTANCE SHALL APPLY. MAXIMUM TRAVEL
 DISTANCE PERMITTED IS 150 FEET WITH
 SPRINKLER PROTECTION.
 3) INTERIOR FINISHES SHALL BE CLASS A
 OR B ON CEILING AND WALLS. AGAIN THE
 BUILDING IS A MIXED OCCUPANCY, THE
 MOST STRINGENT INTERIOR FINISH
 REQUIREMENTS ARE TO BE APPLIED.
 4) PLEASE PROVIDE MORE DETAILS ON FIRE
 SHUTTERS.
 5) PLEASE PROVIDE MORE DETAILS ON
 EMERGENCY GENERATOR. SINCE GENERATOR
 HAD A FUEL SUB-TANK, THE REQUIREMENTS
 OF NFPA 30 ARE TO APPLY. ROOM IS TO BE
 A MINIMUM OF TWO HOUR FIRE RATED.
 6) ELEVATOR TO COMPLY WITH ANSI A17.1.
 7) NO FIRE HYDRANTS SHOWN. WHERE ARE
 THE FIRE HYDRANTS LOCATED FOR THE STORE.
 ADDITIONAL FIRE HYDRANTS MAY BE NEEDED
 ON SITE.
 8) HANDRAILS AND GUARDS TO COMPLY WITH
 NFPA 101, THE LIFE SAFETY CODE, 1985
 EDITION.
 9) NO FIRE LANE SHOWN ON PLANS.
 10) ANY CHANGES IN ELEVATIONS GREATER
 THAN 21 INCHES SHALL BE BY RAMPS. STEPS
 WHEN INSTALLED SHALL HAVE A MINIMUM OF
 THREE STEPS AT 7 INCHES EACH.
 11) A KNOX-BOX IS TO BE PROVIDED FOR
 FIRE RESCUE ACCESS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2000-06-23 Cont ID  
Sent By rturnque Date 2000-06-23 Time 10:34 Rev Time 0.50
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-05-10 Cont ID  
Sent By rturnque Date 2000-05-10 Time 09:48 Rev Time 0.50
Received By rturnque Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVIDE FIRE SPRINKLER DRAWINGS.
 FIRE ALARM SYSTEM SHALL BE CLASS "A"
 OR ADDRESSABLE. FIRE ALARM SHALL BE
 MONITORED BY AN APPROVED CENTRAL STA.
 DOORS ENTERING STAIRWELL SHALL BE 1 HOUR
 SELF CLOSING FIRE DOORS.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2001-06-13 Cont ID  
Sent By pkrauss Date 2001-06-13 Time 08:24 Rev Time 0.45
Received By pkrauss Date 2001-06-12 Time 11:28 Sent To  
Notes
2001-06-13 00:00:00 
 REVISION - AS BUILT DRAWINGS M-1 THRU
 M-6.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2001-02-05 Cont ID  
Sent By ndenmark Date 2001-02-05 Time 14:03 Rev Time 1.00
Received By ndenmark Date 2001-02-05 Time 14:03 Sent To  
Notes
2001-02-05 00:00:00************DENIED**********************
 1. SMOKE FIRE DAMPERS INDICATED ON
 ELECTREICAL PLAN ARE NOT CLEARLY
 INDICATED ON MECHANICAL DRAWING. 1997
 SMC 610.6 REQUIRES LOCATION AND
 INSTALLATION DETAILS TO BE CLEARLY
 INDICATED ON THE PLAN BY THE DESIGNER.
 2. EXHAUST FAN # 16 SHOWS AIR EXHAUSTING
 INTO THE RETURN AIR PLENUM AREA. 1997
 SMC 501.4 REQUIRES AN INDEPENDANT
 SYSTEM FOR EXHAUST AND THAT THE AIR
 SHALL NOT BE RECIRCULATED. RUN EXHAUST
 FROM THIS SPACE OUT OF THE BUILDING.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-10-18 Cont ID  
Sent By ndenmark Date 2000-10-18 Time 12:49 Rev Time 1.00
Received By ndenmark Date 2000-10-18 Time 12:49 Sent To  
Notes
2001-01-08 00:00:00PRIOR COMMENTS ADDRESSED BY LETTER AND
 REVISED PLANS DATED 10/6/00 NCD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2000-09-19 Cont ID  
Sent By ndenmark Date 2000-09-19 Time 13:03 Rev Time 2.00
Received By ndenmark Date 2000-09-19 Time 13:03 Sent To  
Notes
2001-01-08 00:00:00***********DENIED***********************
  
 1.1997 SMC 406.2 REQUIRES FAN SHUT DOWN
 BY DUCT SMOKE DETECTOR FOR UNITS WITH A
 CAPACITY OF 2,000 CFM OR LESS BUT
 SERVING AREAS USED FOR EGRESS. RTU# 10
 W/ 600 CFM SERVICES AN AREA USED FOR
 EGRESS AND SHALL BE PROVIDED WITH FAN
 SHUT DOWN BY DUCT SMOKE DETECTOR.
 2.RTU'S # 9 AND #10 HAVE NO OUTSIDE AIR
 SHOWN. THESE UNITS APPEAR TO SERVE AREAS
 WITH OCCUPANCY AND ARE SEPARATE FROM
 COMMON AREAS OF THE BUILDING. OUTSIDE
 AIR PER ASHRAE 62-89 SHALL BE PROVIDED
 3.EF'S #5, #6, AND #7 ARE CONTROLLED BY
 THE CO2 SENSOR AND WOULD SHUT DOWN WHEN
 THE CO2 LEVEL IS BELOW 1000PPM. THIS
 WOULD PLACE THE PRESSURE IN THE BUILDING
 IN CONFLICT WITH THE REQUIREMENTS OF
 1997 SMC 501.2 REQUIRING PRESSURE EQUIL-
 IZATION PROVIDING FOR THE REMOVAL OF
 EXCESS AIR SUPPLIED. AIR BALANCE
 SCHEDULE AS SHOWN INDICATES AN AIR
 BALANCE IN ACCORDANCE WITH THE ABOVE
 SECTION. THE REMOVAL OF THESE FANS FROM
 THE BALANCE SCHEDULE IS NOT COMPLIANCE
 WITH THIS SECTION OF THE CODE
  
 NOTE:
 RTU'S SHOW A 0-25% MOTOR OPERATED
 OUTSIDE AIR DAMPER FOR EACH UNIT. THE
 QUANTITY OF OUTSIDE AIR PROVIDED IS THE
 MINIMUM REQUIRED BY ASHRAE 62-89 AND
 SHALL NOT BE REDUCED WHILE THE BUILDING
 IS OCCUPIED. SHOW SEQUENCE OF OPERATION
 FOR MOTORIZED DAMPERS INDICATING
 PROPOSED OPERATION.
 NOTE:
 RETURN AIR PLENUM AREAS (AS INDICATED ON
 PLAN AS ABOVE CEILING AREAS) ARE TO BE
 CONSTRUCTED ENTIRELY OF NONCOMBUSTIBLE
 MATERIAL PER 1997 SMC 609.1.
 NOTE:
 PROVIDE INFORMATION ON MAKE UP AIR FOR
 WAREHOUSE EXHAUST FANS (SOURCE/LOCATION)
 1997 SMC 501.2

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-08-01 Cont ID  
Sent By ndenmark Date 2000-08-01 Time 07:40 Rev Time 5.00
Received By ndenmark Date 2000-08-01 Time 07:40 Sent To  
Notes
2001-01-08 00:00:00***************DENIED*******************
  
 1.1997 SMC 610.6 REQUIRES THE SPECIFIC
 LOCATION AND INSTALLATION DETAILS OF EA
 FIRE DOOR, FIRE DAMPER, CEILING DAMPER,
 ETC. TO BE SHOWN AND PROPERLY IDENTIFIED
 ON BUILDING PLANS BY THE DESIGNER
 2.AIR BALANCE SCHEDULE SHOWING
 COMPLIANCE WITH 1997 SMC 501.2
 3.FAN SHUT DOWN BY DUCT SMOKE DETECTOR
 REQUIRED PER 1997 SMC 406 WITH NOTIFICA-
 TION PER 1996 NFPA 4-4.4.2 (TIED TO BLDG
 FIRE ALARM SYSTEM)
 4.PROVIDE CALCULATIONS SHOWING
 COMPLIANCE WITH REQUIREMENTS OF 1997 SBC
 411.4.2 (CONTINUOUS VENTILATION REQUIRED
 - NOT TO BE INTERVAL SWITCHED)
 5.PROVIDE INFORMATION ON PURPOSE OF CO2
 SENSOR SHOWN ON M-1 LEGEND

Review Stop P PLUMBING
Rev No 6 Status P Date 2001-05-24 Cont ID  
Sent By kstevens Date 2001-05-24 Time 17:29 Rev Time 0.50
Received By kstevens Date 2001-05-24 Time 17:29 Sent To  
Notes
2001-05-24 00:00:00REVIEW NOTES: PASSED
  
 REVISE LOCATION OF ROOF CONDENSATE LINES
  
 DETAIL OF SUPPORT FOR CONDENSATE LINES.
  
 REVIEW KSTEVENS

Review Stop P PLUMBING
Rev No 5 Status P Date 2001-01-21 Cont ID  
Sent By pschmitz Date 2001-01-21 Time 07:37 Rev Time 1.50
Received By pschmitz Date 2001-01-22 Time 18:23 Sent To  
Notes
2001-01-21 00:00:00IN ADDITION TO SIGNING, SEALING AND
 DATING EACH PAGE OF THE PLANS, THE
 ENGINEER IN RESPONSIBLE CHARGE MUST
 LEGIBLY INDICATE IN A TITLE BLOCK THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 PLAN SHEET. 61G15-23.002 F.A.C.

Review Stop P PLUMBING
Rev No 4 Status P Date 2000-10-17 Cont ID  
Sent By tlarge Date 2000-10-17 Time 18:46 Rev Time 2.75
Received By pschmitz Date 2000-10-17 Time 18:46 Sent To  
Notes
2001-01-08 00:00:00******************PROVISO***************
 THE PLANS HAVE BEEN REVIEWED FOR
 COMPLIANCE W/THE STANDARD PLUMBING CODE
 WITH THE FOLLOWING PROVISOS:
  
 1)INTERCEPTOR VENT SHALL BE TAKEN OFF
 INTERCEPTOR NOT MORE THAN 45 DEGREES
 FROM THE VERTICAL PER SPC SEC.906.2.1.
 UNLESS BASE OF VENT IS WASHED BY A
 FIXTURE.SEE SHT.P-3.
  
 2)SHT.P-5-MIN.AIR GAP FOR CONDENSATE
 DRAIN DISCHARGE TO LEADER SHALL COMPLY
 W/SPC SEC.806.
  
 3)SHT.P-5-EWH SHOWN ON PLATFORM.HEATER
 SHALL BE READILY ACCESSIBLE PER SPC
 SEC.501.7.SUPPLY SHIP'S LADDER AND PLAT-
 FORM OR RELOCATE EWH TO FLOOR.
  
 4)CONTACT R.COMPO AT CITY OF WPB
 WASTEWATER TREATMENT PLANT FOR APPROVAL
 OF SAND/OIL INTERCEPTOR.
 PHONE #561-835-7423
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 QUESTIONS.
  
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 3 Status F Date 2000-09-11 Cont ID  
Sent By tlarge Date 2000-09-11 Time 16:24 Rev Time 4.50
Received By pschmitz Date 2000-09-11 Time 16:23 Sent To  
Notes
2001-01-08 00:00:001)SUBMIT CIVIL DRAWINGS FOR REVIEW.
 PERMITS MAY BE REQD.FROM THE DEPT.OF
 ENVIRONMENTAL PROTECTION & PALM BEACH
 COUNTY HEALTH DEPT. FOR THE WATER AND
 SEWER INSTALLATIONS.COUNTYWIDE AMEND-
 MENTS TO SPC SECS.101.4.7,104.2.1.
  
 2)ROOM 133-DOOR CANNOT SWING INTO THE
 CLEAR FLOOR SPACE FOR THE URINAL PER
 FACBC SEC.4.22.2.
  
 3)SHT.P-1-CONNECTION OF CONDENSATE
 DRAINS TO STORM SYSTEM SHALL BE BY
 INDIRECT CONNECTIONS.SUBMIT DETAIL OF
 CONNECTION TO DOWNSPOUT.SPC SEC.807.2.
  
 4)WATER HEATERS SHALL BE READILY ACCESS-
 IBLE.(CAR STEREO INSTALLATION).IF ACCESS
 TO THE CONCRETE DECK REQUIRES THE USE
 OF A PORTABLE LADDER,THE HEATER IS NOT
 READILY ACCESSIBLE AS DEFINED BY THE
 SPC.SUBMIT ADDITIONAL INFO FOR THIS
 INSTALLATION.SEE SHT.P-5 ALSO.SPC 501.7.
  
 5)A VALVE IS REQD.ON THE HOT WATER
 BRANCH LINES PER SPC SEC.610.4.2.
 (SEE AUTO INSTALLATION AND EMPLOYEE
 AREAS.)
  
 6)SHT.P-6-CIRCUIT AND LOOP SYSTEM SHALL
 COMPLY W/SPC SEC.914.1.(MAX.OF 4 F.U.'S
 PERMITTED ON VENT DOWNSTREAM OF FIRST
 FIXTURE CONNECTION.)
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-06-21 Cont ID  
Sent By tlarge Date 2000-06-21 Time 10:34 Rev Time 5.75
Received By pschmitz Date 2000-06-21 Time 10:34 Sent To  
Notes
2001-01-08 00:00:00SUBMIT CIVIL DRAWINGS FOR REVIEW.PERMITS
 MAY BE REQD.FROM THE DEPT.OF ENVIRON.
 PROTECTION & PALM BEACH COUNTY HEALTH
 DEPT.FOR WATER AND SEWER INSTALLATIONS.
 COUNTYWIDE AMENDMENTS TO SPC SECS.
 101.4.7,104.2.1.
  
 SHT.A-2-NOTE #6-MEASUREMENT OF GRAB BARS
 A.F.F.SHALL BE TO THE CENTER OF THE BAR,
 NOT TO THE TOP.FACBC SEC.4.16.4 & FIGURE
 #29 & 30.
  
 SINK IN EMPLOYEE LOUNGE SHALL BE ACCESS-
 IBLE PER FACBC SECS.4.24.1.-4.24.7.
  
 A LAVATORY IS REQD.IN THE TOILET STALL
 IN ROOM #132 AND THE SIZE OF THE STALL
 SHALL COMPLY W/FACBC SEC.4.17.3.THE DOOR
 CANNOT SWING INTO THE CLEAR FLOOR SPACE
 REQD.FOR ANY FIXTURE.FACBC SEC.4.22.2.
  
 URINAL IN TOILET ROOM IN WAREHOUSE AND
 IN RETAIL AREA SHALL COMPLY W/FACBC SEC.
 4.18.MAX.17" AFF TO THE RIM & 30"X 48"
 CLEAR FLOOR SPACE.
  
 THE NUMBER OF EMPLOYEES PER SHIFT IN THE
 WAREHOUSE AREA SHALL BE SUBSTANTIATED BY
 OWNER PER SPC TABLE 407.
  
 THE MINIMUM NUMBER OF REQUIRED SANITARY
 FACILITIES SHALL COMPLY W/TABLE 407 OF
 SPC BASED ON THE TOTAL NUMBER OF PERSONS
 NOT 50% MALE, 50% FEMALE.ADDITIONAL
 FIXTURES ARE REQD.
  
 SUBMIT PIPING ISOMETRIC FOR "SIZZRDOK"&
 ELEVATOR SUMP AREAS.COMPLY W/SPC 717.2,
 717.9,717.11.
  
 SUBMIT INSTALLATION DETAILS ON PNEUMATIC
 TUBE SYSTEM.COUNTYWIDE AMENDMENTS TO SPC
 SEC.104.2.1.
  
 SUBMIT DETAILS FOR SECONDARY (EMERGENCY)
 DRAINAGE.COMPLY W/SPC SEC.1109.1-1109.3.
 AND APPENDIX "A" OF SPC.
  
 SHT.P-1-CONNECTION OF CONDENSATE DRAINS
 TO STORM SYSTEM SHALL BE BY INDIRECT
 CONNECTIONS PER SPC 807.2.
  
 WATER HEATERS SHALL BE READILY ACCESS-
 IBLE PER FACBC SEC.501.7.SUPPLY FIXED
 LADDER ORRELOCATE EWH TO FLOOR.
  
 SHT.P-4-SHOWS A 4" LINE DRAINING INTO A
 2" LINE.SPC SEC.307.5.
  
 HOT WATER SYSTEM SHALL BE VALVED PER SPC
 SECS.610.4.1,610.4.2.
  
 SHT.P-4.-OVER 4 FIXTURES CONNECTED TO
 1/2"HOT WATER.COUNTYWIDE AMENDMENTS TO
 SPC SEC.607.7.
  
 MECHANICAL SHOCK ABSORBERS REQUIRE
 ACCESS PER 607.8.3.
  
 SHT.P-6-LOCATION OF DRINKING FOUNTAINS
 ON SANITARY RISER DOESN'T MATCH FLOOR
 PLAN.
  
 TWO-WAY CLEANOUTS ARE REQD.ON THE INLET
 AND OUTLET OF THE OIL INTERCEPTOR PER
 SPC SEC.710.4.DELETE REFERENCE TO SFBC.
  
 SHOW WATER CONNECTION TO EWH ON P-6,
 GROUND FLOOR SALES AREA.
  
 SUBMIT DETAIL OF GREASE INTERCEPTOR.
 CAPACITY SHALL BE APPROVED BY CITY OF
 WPB UTILITIES.CONTACT R.COMPO AT (561)-
 835-7423 FOR APPROVAL.
  
 SUBMIT ENERGY CALCULATIONS FOR REVIEW.
 103.0,103.1.
  
 IF YOU HAVE ANY QUESTIONS I CAN BE
 REACHED AT (561)659-8096,EXT.8377.
 TIMOTHY LARGE,PLUMBING PLAN REVIEW.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-05-20 Cont ID  
Sent By tlarge Date 2000-05-20 Time 10:01 Rev Time 3.50
Received By pschmitz Date 2000-05-20 Time 10:01 Sent To  
Notes
2001-01-08 00:00:00SUBMIT CIVIL DRAWINGS FOR REVIEW.PERMITS
 MAY BE REQD.FROM DEPT.OF ENVIRON.PROT.
 AGENCY & PALM BEACH COUNTY HEALTH DEPT.
 FOR WATER AND SANITARY INSTALLATIONS.
 COUNTYWIDE AMENDMENTS TO SPC SEC.101.4.7
 104.2.1..
  
 SINK IN EMPLOYEE LOUNGE SHALL COMPLY W/
 FACBC SECS.4.24.1-4.24.7.
  
 SHT.A2.4-HEIGHT OF URINAL TO RIM SHALL
 BE A MAX.OF 17" TO RIM PER FACBC SEC.
 4.18.2.
  
 HEIGHT OF ACCESSIBLE WATER CLOSET SHALL
 BE 17"-19"AFF PER FACBC SEC.4.16.3.&
 FLUSH CONTROLS SHALL BE LOCATED ON THE
 WIDE SIDE OF THE WATER CLOSET MAX.44"AFF
  
 DRINKING FOUNTAINS SHALL COMPLY W/FACBC
 SEC.4.1.3(10)(B).(WHERE MORE THAN 1 IS
 PROVIDED ON A FLOOR,AT LEAST 50% SHALL
 COMPLY W/FACBC SEC.4.15)
  
 SHOW REQD.WHEELCHAIR TURNING SPACE IN
 TOILET ROOMS AND RESTROOMS PER FACBC
 SEC.4.2.3.
  
 ACCESSIBLE URINAL SHALL BE LOCATED ON AN
 ACCESSIBLE ROUTE PER FACBC SEC.4.1.2(2).
 (SEE MEN'S R.R.#138.)SHOW REQD.30"X 48"
 CLEAR FLOOR ACCESS FOR URINAL ON PLAN.
  
 A LAVATORY IS REQD.IN THE STALL IN THE
 MEN'S TOILET ROOM #132 PER FACBC SEC.
 4.1.2 (6),4.1.3.(11),4.17.3,4.22.
  
 WATER HEATER SHALL BE READILY ACCESSIBLE
 PER SPC SEC.501.7.PROVIDE FIXED LADDER
 OR RELOCATE EWH TO FLOOR.
  
 PLANS REFER TO SCUPPERS.SUBMIT DETAILS,
 DIMENSIONS,LOCATIONS ON PLANS.COMPLY W/
 SPC APPENDIX "A".
  
 TWO WAY CLEANOUTS ARE REQD.ON THE INLET
 AND OUTLETS AT THE OIL INTERCEPTOR PER
 SPC 710.4.
  
 INDICATE SLOPE OF STORM DRAINAGE PIPING
 ON PLANS.COMPLY W/SPC TABLE 1108.2.
  
 SUBMIT DETAIL OF GREASE TRAP FOR REVIEW.
 APPROVAL REQD.FROM CITY OF WEST PALM
 BEACH REGIONAL WASTEWATER TREATMENT
 PLANT.CONTACT R.COMPO AT 835-7423.SUBMIT
 COPY OF APPROVAL.
  
 SUBMIT PIPING DETAILS(ISOMETRICS)FOR ALL
 COMPRESSED AIR PIPING,PUMP DISCHARGE
 FROM TRUCK LIFT,ELEVATOR SUMP.COUNTY-
 WIDE AMENDMENTS TO SPC SEC.104.2.1.
  
 SHT.P-5-DELETE NOTE REFERRING S.F.B.C.
 DADE COUNTY EDITION.COUNTYWIDE AMENDMENT
 TO SPC SEC.101.1,101.2.
  
 WATER SUPPLY CONTROL SHALL COMPLY W/SPC
 SECS.610.4.1,610.4.2.
  
 SUBMIT COMPLETE ISOMETRIC FOR OILY WASTE
 AND GREASY WASTE SYSTEM.COUNTYWIDE AMEND
 MENTS TO SPC SEC.104.2.1.
  
 SUBMIT DOCUMENTATION OF OCCUPANT CONTENT
 PER SHIFT IN WAREHOUSE FOR COMPLIANCE W/
 TABLE 407 OF SPC FOR PLBG.FIXTURES.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-10-16 Cont ID  
Sent By gjoyce Date 2000-10-16 Time 14:41 Rev Time 0.15
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***