| Plan Review Stops For Permit 99121526 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2000-09-26 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2000-09-26 |
Time |
14:56 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | OWES IMPACT AND RADON FEES |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-07-28 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2000-07-28 |
Time |
11:01 |
Rev Time |
99.00 |
| Received By |
hpiskura |
Date |
2000-07-24 |
Time |
16:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
P |
Date |
2001-06-12 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-06-12 |
Time |
08:21 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-06-12 |
Time |
08:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
N |
Date |
2001-05-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-05-15 |
Time |
07:50 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-05-15 |
Time |
07:50 |
Sent To |
|
|
| Notes |
| 2001-05-15 00:00:00 | NO ELECTRICAL PLANS SUBMITTED FOR | | | ADDING TWO OVERHEAD GARAGE DOORS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2001-01-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-01-31 |
Time |
15:51 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-01-31 |
Time |
12:36 |
Sent To |
|
|
| Notes |
| 2001-01-31 00:00:00 | REVISIONS OK |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2000-10-27 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2000-10-27 |
Time |
14:29 |
Rev Time |
1.30 |
| Received By |
jleahy |
Date |
2000-10-27 |
Time |
14:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2000-09-25 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-09-25 |
Time |
12:12 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2000-10-27 |
Time |
14:11 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | **************** UNSAT **************** | | | | | | 1)NOTE:PLEASE SEE PP13 ON E-12. ALL | | | CONTINUOUS LOADS TO BE SHOWN AT 125% | | | | | | 2)NOTE: PLEASE SEE LOADS SHOWN ON PP14 | | | EM2,UPS PANEL. PLEASE SEE THAT ALL | | | LOADS DO NOT COERRELATE. LOADS SHOWN ON | | | UPS PANEL TOTAL AT 3KVA PER PHASE AND | | | CONNECTED SHOWN HIGHER ON PANEL SCHEDULE | | | PLEASE SEE PP14 CONNECTED SHOWN AT 28.42 | | | AND CONNECTED ON PANEL AT 29.42 AND | | | TOTAL AT BOTTOM SHOWN AT 25.42.PLEASE | | | CORRELATE THE ABOVE LOADS. | | | | | | 3)NOTE: PLEASE SEE LP1 CONTINUOUS LOADS | | | NEED TO BE SHOWN AT 125%. CONTINUOUS | | | LOADSON OTHER PANELS SHOWN AT 125%??? | | | | | | PLEASE SUBMIT THE ABOVE INFORMATON FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASECALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
N |
Date |
2000-09-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-06-29 |
Time |
20:17 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-06-29 |
Time |
20:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
P |
Date |
2000-10-20 |
|
|
Cont ID |
|
| Sent By |
mgonzale |
Date |
2000-10-20 |
Time |
07:55 |
Rev Time |
1.00 |
| Received By |
mgonzale |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | "THIS PERMIT IS APPROVED SUBJECT TO | | | RESOLUTION OF THE ENVIRONMENTAL ISSUES | | | OUTLINED IN THE FLORIDA DEPARTMENT OF | | | ENVIRONMENTAL PROTECTION MEMORENDUM | | | DATED JULY 25, 2000, ATTACHED HERETO, | | | RELATING TO THE FORMER GOLF COURSE | | | PROPERTY AND LETTER OF AGREEMENT BETWEEN | | | BRANDSMART AND THE CITY OF WEST PALM | | | BEACH"(RICHARD D. PITTMAN) | | | | | | THIS IS FOR THE BUILDING ONLY. | | | THIS PERMIT DOES NOT INCLUDE THE PARKING | | | LOT OR PARKING LOT DRAINAGE. ADDITIONAL | | | PERMIT WILL BE REQUIRED FOR THE PARKING | | | LOT AND PARKING LOT DRAINAGE. |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2000-06-26 |
|
|
Cont ID |
|
| Sent By |
mgonzale |
Date |
2000-06-26 |
Time |
13:51 |
Rev Time |
1.00 |
| Received By |
mgonzale |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | REQUIRES WATER, SEWER, PAVING AND DRAINA | | | GE PLANS. | | | PLEASE SUBMITT 2 COPIES FOR REVIEW TO | | | PUBLIC UTILITIES ENGINEERING SERVICES | | | 1000 45TH ST. SUITE 15, WPB FL 33415 | | | ATTENTION DEAN OR MANNY. | | | COPIES MUST ALSO BE SUBMITTED AT P,B&Z | | | WITH APPLICABLE FEES. | | | PLEASE MAKE NOTICE OF STORM REQUIREMENTS | | | THAT REQUIRE LETTER STATING PERVIOUS | | | AND IMPERVIOUS CALCULATIONS, ETC. | | | | | | SEE GENERAL COMMENTS ATTACHED. | | | IF ANY QUESTIONS FEEL FREE TO CONTACT | | | MANNY OR DEAN AT 561 659 8040. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
P |
Date |
2001-02-06 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-02-06 |
Time |
09:12 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-02-06 |
Time |
09:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2000-10-24 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-10-24 |
Time |
15:16 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-10-24 |
Time |
15:16 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) OBTAINED A FIRE HYDRANT LOCATION | | | MAP FROM KIMLEY HORN AND ASSOCIATES | | | INDICATING FIRE HYDRANT LOCATIONS | | | AND A FIRE LANE FOR THE BUILDING. | | | 2) RECEIVED LETTER FROM ARCHITECT | | | ADDRESSING PLAN REVIEW COMMENTS. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2000-09-07 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-09-07 |
Time |
09:56 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-09-07 |
Time |
09:51 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) BUILDING ADDRESS TO BE PLACED ON | | | BUILDING IN ACCORDANCE WITH CITY | | | ORDINANCE. | | | 2) TRAVEL DISTANCE OF 250 FEET SHWON ON | | | PLANS. SINCE THE BUILDING IS A MIXED | | | OCCUPANCY THE MOST STRINGENT TRAVEL | | | DISTANCE SHALL APPLY. MAXIMUM TRAVEL | | | DISTANCE PERMITTED IS 150 FEET WITH | | | SPRINKLER PROTECTION. | | | 3) INTERIOR FINISHES SHALL BE CLASS A | | | OR B ON CEILING AND WALLS. AGAIN THE | | | BUILDING IS A MIXED OCCUPANCY, THE | | | MOST STRINGENT INTERIOR FINISH | | | REQUIREMENTS ARE TO BE APPLIED. | | | 4) PLEASE PROVIDE MORE DETAILS ON FIRE | | | SHUTTERS. | | | 5) PLEASE PROVIDE MORE DETAILS ON | | | EMERGENCY GENERATOR. SINCE GENERATOR | | | HAD A FUEL SUB-TANK, THE REQUIREMENTS | | | OF NFPA 30 ARE TO APPLY. ROOM IS TO BE | | | A MINIMUM OF TWO HOUR FIRE RATED. | | | 6) ELEVATOR TO COMPLY WITH ANSI A17.1. | | | 7) NO FIRE HYDRANTS SHOWN. WHERE ARE | | | THE FIRE HYDRANTS LOCATED FOR THE STORE. | | | ADDITIONAL FIRE HYDRANTS MAY BE NEEDED | | | ON SITE. | | | 8) HANDRAILS AND GUARDS TO COMPLY WITH | | | NFPA 101, THE LIFE SAFETY CODE, 1985 | | | EDITION. | | | 9) NO FIRE LANE SHOWN ON PLANS. | | | 10) ANY CHANGES IN ELEVATIONS GREATER | | | THAN 21 INCHES SHALL BE BY RAMPS. STEPS | | | WHEN INSTALLED SHALL HAVE A MINIMUM OF | | | THREE STEPS AT 7 INCHES EACH. | | | 11) A KNOX-BOX IS TO BE PROVIDED FOR | | | FIRE RESCUE ACCESS. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2000-06-23 |
|
|
Cont ID |
|
| Sent By |
rturnque |
Date |
2000-06-23 |
Time |
10:34 |
Rev Time |
0.50 |
| Received By |
rturnque |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2000-05-10 |
|
|
Cont ID |
|
| Sent By |
rturnque |
Date |
2000-05-10 |
Time |
09:48 |
Rev Time |
0.50 |
| Received By |
rturnque |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVIDE FIRE SPRINKLER DRAWINGS. | | | FIRE ALARM SYSTEM SHALL BE CLASS "A" | | | OR ADDRESSABLE. FIRE ALARM SHALL BE | | | MONITORED BY AN APPROVED CENTRAL STA. | | | DOORS ENTERING STAIRWELL SHALL BE 1 HOUR | | | SELF CLOSING FIRE DOORS. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2001-06-13 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-06-13 |
Time |
08:24 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2001-06-12 |
Time |
11:28 |
Sent To |
|
|
| Notes |
| 2001-06-13 00:00:00 | | | | REVISION - AS BUILT DRAWINGS M-1 THRU | | | M-6. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
F |
Date |
2001-02-05 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2001-02-05 |
Time |
14:03 |
Rev Time |
1.00 |
| Received By |
ndenmark |
Date |
2001-02-05 |
Time |
14:03 |
Sent To |
|
|
| Notes |
| 2001-02-05 00:00:00 | ************DENIED********************** | | | 1. SMOKE FIRE DAMPERS INDICATED ON | | | ELECTREICAL PLAN ARE NOT CLEARLY | | | INDICATED ON MECHANICAL DRAWING. 1997 | | | SMC 610.6 REQUIRES LOCATION AND | | | INSTALLATION DETAILS TO BE CLEARLY | | | INDICATED ON THE PLAN BY THE DESIGNER. | | | 2. EXHAUST FAN # 16 SHOWS AIR EXHAUSTING | | | INTO THE RETURN AIR PLENUM AREA. 1997 | | | SMC 501.4 REQUIRES AN INDEPENDANT | | | SYSTEM FOR EXHAUST AND THAT THE AIR | | | SHALL NOT BE RECIRCULATED. RUN EXHAUST | | | FROM THIS SPACE OUT OF THE BUILDING. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2000-10-18 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-10-18 |
Time |
12:49 |
Rev Time |
1.00 |
| Received By |
ndenmark |
Date |
2000-10-18 |
Time |
12:49 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PRIOR COMMENTS ADDRESSED BY LETTER AND | | | REVISED PLANS DATED 10/6/00 NCD |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2000-09-19 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-09-19 |
Time |
13:03 |
Rev Time |
2.00 |
| Received By |
ndenmark |
Date |
2000-09-19 |
Time |
13:03 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ***********DENIED*********************** | | | | | | 1.1997 SMC 406.2 REQUIRES FAN SHUT DOWN | | | BY DUCT SMOKE DETECTOR FOR UNITS WITH A | | | CAPACITY OF 2,000 CFM OR LESS BUT | | | SERVING AREAS USED FOR EGRESS. RTU# 10 | | | W/ 600 CFM SERVICES AN AREA USED FOR | | | EGRESS AND SHALL BE PROVIDED WITH FAN | | | SHUT DOWN BY DUCT SMOKE DETECTOR. | | | 2.RTU'S # 9 AND #10 HAVE NO OUTSIDE AIR | | | SHOWN. THESE UNITS APPEAR TO SERVE AREAS | | | WITH OCCUPANCY AND ARE SEPARATE FROM | | | COMMON AREAS OF THE BUILDING. OUTSIDE | | | AIR PER ASHRAE 62-89 SHALL BE PROVIDED | | | 3.EF'S #5, #6, AND #7 ARE CONTROLLED BY | | | THE CO2 SENSOR AND WOULD SHUT DOWN WHEN | | | THE CO2 LEVEL IS BELOW 1000PPM. THIS | | | WOULD PLACE THE PRESSURE IN THE BUILDING | | | IN CONFLICT WITH THE REQUIREMENTS OF | | | 1997 SMC 501.2 REQUIRING PRESSURE EQUIL- | | | IZATION PROVIDING FOR THE REMOVAL OF | | | EXCESS AIR SUPPLIED. AIR BALANCE | | | SCHEDULE AS SHOWN INDICATES AN AIR | | | BALANCE IN ACCORDANCE WITH THE ABOVE | | | SECTION. THE REMOVAL OF THESE FANS FROM | | | THE BALANCE SCHEDULE IS NOT COMPLIANCE | | | WITH THIS SECTION OF THE CODE | | | | | | NOTE: | | | RTU'S SHOW A 0-25% MOTOR OPERATED | | | OUTSIDE AIR DAMPER FOR EACH UNIT. THE | | | QUANTITY OF OUTSIDE AIR PROVIDED IS THE | | | MINIMUM REQUIRED BY ASHRAE 62-89 AND | | | SHALL NOT BE REDUCED WHILE THE BUILDING | | | IS OCCUPIED. SHOW SEQUENCE OF OPERATION | | | FOR MOTORIZED DAMPERS INDICATING | | | PROPOSED OPERATION. | | | NOTE: | | | RETURN AIR PLENUM AREAS (AS INDICATED ON | | | PLAN AS ABOVE CEILING AREAS) ARE TO BE | | | CONSTRUCTED ENTIRELY OF NONCOMBUSTIBLE | | | MATERIAL PER 1997 SMC 609.1. | | | NOTE: | | | PROVIDE INFORMATION ON MAKE UP AIR FOR | | | WAREHOUSE EXHAUST FANS (SOURCE/LOCATION) | | | 1997 SMC 501.2 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2000-08-01 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-08-01 |
Time |
07:40 |
Rev Time |
5.00 |
| Received By |
ndenmark |
Date |
2000-08-01 |
Time |
07:40 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ***************DENIED******************* | | | | | | 1.1997 SMC 610.6 REQUIRES THE SPECIFIC | | | LOCATION AND INSTALLATION DETAILS OF EA | | | FIRE DOOR, FIRE DAMPER, CEILING DAMPER, | | | ETC. TO BE SHOWN AND PROPERLY IDENTIFIED | | | ON BUILDING PLANS BY THE DESIGNER | | | 2.AIR BALANCE SCHEDULE SHOWING | | | COMPLIANCE WITH 1997 SMC 501.2 | | | 3.FAN SHUT DOWN BY DUCT SMOKE DETECTOR | | | REQUIRED PER 1997 SMC 406 WITH NOTIFICA- | | | TION PER 1996 NFPA 4-4.4.2 (TIED TO BLDG | | | FIRE ALARM SYSTEM) | | | 4.PROVIDE CALCULATIONS SHOWING | | | COMPLIANCE WITH REQUIREMENTS OF 1997 SBC | | | 411.4.2 (CONTINUOUS VENTILATION REQUIRED | | | - NOT TO BE INTERVAL SWITCHED) | | | 5.PROVIDE INFORMATION ON PURPOSE OF CO2 | | | SENSOR SHOWN ON M-1 LEGEND |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
6 |
Status |
P |
Date |
2001-05-24 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-05-24 |
Time |
17:29 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2001-05-24 |
Time |
17:29 |
Sent To |
|
|
| Notes |
| 2001-05-24 00:00:00 | REVIEW NOTES: PASSED | | | | | | REVISE LOCATION OF ROOF CONDENSATE LINES | | | | | | DETAIL OF SUPPORT FOR CONDENSATE LINES. | | | | | | REVIEW KSTEVENS |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2001-01-21 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-01-21 |
Time |
07:37 |
Rev Time |
1.50 |
| Received By |
pschmitz |
Date |
2001-01-22 |
Time |
18:23 |
Sent To |
|
|
| Notes |
| 2001-01-21 00:00:00 | IN ADDITION TO SIGNING, SEALING AND | | | DATING EACH PAGE OF THE PLANS, THE | | | ENGINEER IN RESPONSIBLE CHARGE MUST | | | LEGIBLY INDICATE IN A TITLE BLOCK THEIR | | | NAME, ADDRESS AND LICENSE NUMBER ON EACH | | | PLAN SHEET. 61G15-23.002 F.A.C. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2000-10-17 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-10-17 |
Time |
18:46 |
Rev Time |
2.75 |
| Received By |
pschmitz |
Date |
2000-10-17 |
Time |
18:46 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ******************PROVISO*************** | | | THE PLANS HAVE BEEN REVIEWED FOR | | | COMPLIANCE W/THE STANDARD PLUMBING CODE | | | WITH THE FOLLOWING PROVISOS: | | | | | | 1)INTERCEPTOR VENT SHALL BE TAKEN OFF | | | INTERCEPTOR NOT MORE THAN 45 DEGREES | | | FROM THE VERTICAL PER SPC SEC.906.2.1. | | | UNLESS BASE OF VENT IS WASHED BY A | | | FIXTURE.SEE SHT.P-3. | | | | | | 2)SHT.P-5-MIN.AIR GAP FOR CONDENSATE | | | DRAIN DISCHARGE TO LEADER SHALL COMPLY | | | W/SPC SEC.806. | | | | | | 3)SHT.P-5-EWH SHOWN ON PLATFORM.HEATER | | | SHALL BE READILY ACCESSIBLE PER SPC | | | SEC.501.7.SUPPLY SHIP'S LADDER AND PLAT- | | | FORM OR RELOCATE EWH TO FLOOR. | | | | | | 4)CONTACT R.COMPO AT CITY OF WPB | | | WASTEWATER TREATMENT PLANT FOR APPROVAL | | | OF SAND/OIL INTERCEPTOR. | | | PHONE #561-835-7423 | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | QUESTIONS. | | | | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2000-09-11 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-09-11 |
Time |
16:24 |
Rev Time |
4.50 |
| Received By |
pschmitz |
Date |
2000-09-11 |
Time |
16:23 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)SUBMIT CIVIL DRAWINGS FOR REVIEW. | | | PERMITS MAY BE REQD.FROM THE DEPT.OF | | | ENVIRONMENTAL PROTECTION & PALM BEACH | | | COUNTY HEALTH DEPT. FOR THE WATER AND | | | SEWER INSTALLATIONS.COUNTYWIDE AMEND- | | | MENTS TO SPC SECS.101.4.7,104.2.1. | | | | | | 2)ROOM 133-DOOR CANNOT SWING INTO THE | | | CLEAR FLOOR SPACE FOR THE URINAL PER | | | FACBC SEC.4.22.2. | | | | | | 3)SHT.P-1-CONNECTION OF CONDENSATE | | | DRAINS TO STORM SYSTEM SHALL BE BY | | | INDIRECT CONNECTIONS.SUBMIT DETAIL OF | | | CONNECTION TO DOWNSPOUT.SPC SEC.807.2. | | | | | | 4)WATER HEATERS SHALL BE READILY ACCESS- | | | IBLE.(CAR STEREO INSTALLATION).IF ACCESS | | | TO THE CONCRETE DECK REQUIRES THE USE | | | OF A PORTABLE LADDER,THE HEATER IS NOT | | | READILY ACCESSIBLE AS DEFINED BY THE | | | SPC.SUBMIT ADDITIONAL INFO FOR THIS | | | INSTALLATION.SEE SHT.P-5 ALSO.SPC 501.7. | | | | | | 5)A VALVE IS REQD.ON THE HOT WATER | | | BRANCH LINES PER SPC SEC.610.4.2. | | | (SEE AUTO INSTALLATION AND EMPLOYEE | | | AREAS.) | | | | | | 6)SHT.P-6-CIRCUIT AND LOOP SYSTEM SHALL | | | COMPLY W/SPC SEC.914.1.(MAX.OF 4 F.U.'S | | | PERMITTED ON VENT DOWNSTREAM OF FIRST | | | FIXTURE CONNECTION.) | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2000-06-21 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-06-21 |
Time |
10:34 |
Rev Time |
5.75 |
| Received By |
pschmitz |
Date |
2000-06-21 |
Time |
10:34 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | SUBMIT CIVIL DRAWINGS FOR REVIEW.PERMITS | | | MAY BE REQD.FROM THE DEPT.OF ENVIRON. | | | PROTECTION & PALM BEACH COUNTY HEALTH | | | DEPT.FOR WATER AND SEWER INSTALLATIONS. | | | COUNTYWIDE AMENDMENTS TO SPC SECS. | | | 101.4.7,104.2.1. | | | | | | SHT.A-2-NOTE #6-MEASUREMENT OF GRAB BARS | | | A.F.F.SHALL BE TO THE CENTER OF THE BAR, | | | NOT TO THE TOP.FACBC SEC.4.16.4 & FIGURE | | | #29 & 30. | | | | | | SINK IN EMPLOYEE LOUNGE SHALL BE ACCESS- | | | IBLE PER FACBC SECS.4.24.1.-4.24.7. | | | | | | A LAVATORY IS REQD.IN THE TOILET STALL | | | IN ROOM #132 AND THE SIZE OF THE STALL | | | SHALL COMPLY W/FACBC SEC.4.17.3.THE DOOR | | | CANNOT SWING INTO THE CLEAR FLOOR SPACE | | | REQD.FOR ANY FIXTURE.FACBC SEC.4.22.2. | | | | | | URINAL IN TOILET ROOM IN WAREHOUSE AND | | | IN RETAIL AREA SHALL COMPLY W/FACBC SEC. | | | 4.18.MAX.17" AFF TO THE RIM & 30"X 48" | | | CLEAR FLOOR SPACE. | | | | | | THE NUMBER OF EMPLOYEES PER SHIFT IN THE | | | WAREHOUSE AREA SHALL BE SUBSTANTIATED BY | | | OWNER PER SPC TABLE 407. | | | | | | THE MINIMUM NUMBER OF REQUIRED SANITARY | | | FACILITIES SHALL COMPLY W/TABLE 407 OF | | | SPC BASED ON THE TOTAL NUMBER OF PERSONS | | | NOT 50% MALE, 50% FEMALE.ADDITIONAL | | | FIXTURES ARE REQD. | | | | | | SUBMIT PIPING ISOMETRIC FOR "SIZZRDOK"& | | | ELEVATOR SUMP AREAS.COMPLY W/SPC 717.2, | | | 717.9,717.11. | | | | | | SUBMIT INSTALLATION DETAILS ON PNEUMATIC | | | TUBE SYSTEM.COUNTYWIDE AMENDMENTS TO SPC | | | SEC.104.2.1. | | | | | | SUBMIT DETAILS FOR SECONDARY (EMERGENCY) | | | DRAINAGE.COMPLY W/SPC SEC.1109.1-1109.3. | | | AND APPENDIX "A" OF SPC. | | | | | | SHT.P-1-CONNECTION OF CONDENSATE DRAINS | | | TO STORM SYSTEM SHALL BE BY INDIRECT | | | CONNECTIONS PER SPC 807.2. | | | | | | WATER HEATERS SHALL BE READILY ACCESS- | | | IBLE PER FACBC SEC.501.7.SUPPLY FIXED | | | LADDER ORRELOCATE EWH TO FLOOR. | | | | | | SHT.P-4-SHOWS A 4" LINE DRAINING INTO A | | | 2" LINE.SPC SEC.307.5. | | | | | | HOT WATER SYSTEM SHALL BE VALVED PER SPC | | | SECS.610.4.1,610.4.2. | | | | | | SHT.P-4.-OVER 4 FIXTURES CONNECTED TO | | | 1/2"HOT WATER.COUNTYWIDE AMENDMENTS TO | | | SPC SEC.607.7. | | | | | | MECHANICAL SHOCK ABSORBERS REQUIRE | | | ACCESS PER 607.8.3. | | | | | | SHT.P-6-LOCATION OF DRINKING FOUNTAINS | | | ON SANITARY RISER DOESN'T MATCH FLOOR | | | PLAN. | | | | | | TWO-WAY CLEANOUTS ARE REQD.ON THE INLET | | | AND OUTLET OF THE OIL INTERCEPTOR PER | | | SPC SEC.710.4.DELETE REFERENCE TO SFBC. | | | | | | SHOW WATER CONNECTION TO EWH ON P-6, | | | GROUND FLOOR SALES AREA. | | | | | | SUBMIT DETAIL OF GREASE INTERCEPTOR. | | | CAPACITY SHALL BE APPROVED BY CITY OF | | | WPB UTILITIES.CONTACT R.COMPO AT (561)- | | | 835-7423 FOR APPROVAL. | | | | | | SUBMIT ENERGY CALCULATIONS FOR REVIEW. | | | 103.0,103.1. | | | | | | IF YOU HAVE ANY QUESTIONS I CAN BE | | | REACHED AT (561)659-8096,EXT.8377. | | | TIMOTHY LARGE,PLUMBING PLAN REVIEW. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-05-20 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-05-20 |
Time |
10:01 |
Rev Time |
3.50 |
| Received By |
pschmitz |
Date |
2000-05-20 |
Time |
10:01 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | SUBMIT CIVIL DRAWINGS FOR REVIEW.PERMITS | | | MAY BE REQD.FROM DEPT.OF ENVIRON.PROT. | | | AGENCY & PALM BEACH COUNTY HEALTH DEPT. | | | FOR WATER AND SANITARY INSTALLATIONS. | | | COUNTYWIDE AMENDMENTS TO SPC SEC.101.4.7 | | | 104.2.1.. | | | | | | SINK IN EMPLOYEE LOUNGE SHALL COMPLY W/ | | | FACBC SECS.4.24.1-4.24.7. | | | | | | SHT.A2.4-HEIGHT OF URINAL TO RIM SHALL | | | BE A MAX.OF 17" TO RIM PER FACBC SEC. | | | 4.18.2. | | | | | | HEIGHT OF ACCESSIBLE WATER CLOSET SHALL | | | BE 17"-19"AFF PER FACBC SEC.4.16.3.& | | | FLUSH CONTROLS SHALL BE LOCATED ON THE | | | WIDE SIDE OF THE WATER CLOSET MAX.44"AFF | | | | | | DRINKING FOUNTAINS SHALL COMPLY W/FACBC | | | SEC.4.1.3(10)(B).(WHERE MORE THAN 1 IS | | | PROVIDED ON A FLOOR,AT LEAST 50% SHALL | | | COMPLY W/FACBC SEC.4.15) | | | | | | SHOW REQD.WHEELCHAIR TURNING SPACE IN | | | TOILET ROOMS AND RESTROOMS PER FACBC | | | SEC.4.2.3. | | | | | | ACCESSIBLE URINAL SHALL BE LOCATED ON AN | | | ACCESSIBLE ROUTE PER FACBC SEC.4.1.2(2). | | | (SEE MEN'S R.R.#138.)SHOW REQD.30"X 48" | | | CLEAR FLOOR ACCESS FOR URINAL ON PLAN. | | | | | | A LAVATORY IS REQD.IN THE STALL IN THE | | | MEN'S TOILET ROOM #132 PER FACBC SEC. | | | 4.1.2 (6),4.1.3.(11),4.17.3,4.22. | | | | | | WATER HEATER SHALL BE READILY ACCESSIBLE | | | PER SPC SEC.501.7.PROVIDE FIXED LADDER | | | OR RELOCATE EWH TO FLOOR. | | | | | | PLANS REFER TO SCUPPERS.SUBMIT DETAILS, | | | DIMENSIONS,LOCATIONS ON PLANS.COMPLY W/ | | | SPC APPENDIX "A". | | | | | | TWO WAY CLEANOUTS ARE REQD.ON THE INLET | | | AND OUTLETS AT THE OIL INTERCEPTOR PER | | | SPC 710.4. | | | | | | INDICATE SLOPE OF STORM DRAINAGE PIPING | | | ON PLANS.COMPLY W/SPC TABLE 1108.2. | | | | | | SUBMIT DETAIL OF GREASE TRAP FOR REVIEW. | | | APPROVAL REQD.FROM CITY OF WEST PALM | | | BEACH REGIONAL WASTEWATER TREATMENT | | | PLANT.CONTACT R.COMPO AT 835-7423.SUBMIT | | | COPY OF APPROVAL. | | | | | | SUBMIT PIPING DETAILS(ISOMETRICS)FOR ALL | | | COMPRESSED AIR PIPING,PUMP DISCHARGE | | | FROM TRUCK LIFT,ELEVATOR SUMP.COUNTY- | | | WIDE AMENDMENTS TO SPC SEC.104.2.1. | | | | | | SHT.P-5-DELETE NOTE REFERRING S.F.B.C. | | | DADE COUNTY EDITION.COUNTYWIDE AMENDMENT | | | TO SPC SEC.101.1,101.2. | | | | | | WATER SUPPLY CONTROL SHALL COMPLY W/SPC | | | SECS.610.4.1,610.4.2. | | | | | | SUBMIT COMPLETE ISOMETRIC FOR OILY WASTE | | | AND GREASY WASTE SYSTEM.COUNTYWIDE AMEND | | | MENTS TO SPC SEC.104.2.1. | | | | | | SUBMIT DOCUMENTATION OF OCCUPANT CONTENT | | | PER SHIFT IN WAREHOUSE FOR COMPLIANCE W/ | | | TABLE 407 OF SPC FOR PLBG.FIXTURES. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2000-10-16 |
|
|
Cont ID |
|
| Sent By |
gjoyce |
Date |
2000-10-16 |
Time |
14:41 |
Rev Time |
0.15 |
| Received By |
gjoyce |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|