Plan Review Details - Permit 99121519
Plan Review Stops For Permit 99121519
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-03-14 Cont ID  
Sent By lmartine Date 2000-03-14 Time 15:07 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-01-08 00:00:001]PLEASE REFERENCE 1997 SBC ON PG. A0.1
 2]SUBMIT FIRE SPRINKLER LAYOUT
 3]ALL CANOPIES MUST COMPLY WITH APPENDIX
 "F" REQUIREMENTS,SEE 102.2.6 AND 102.2
 .8
 4]EFIS SYSTEM MUST COMPLY WITH F102.2.6
 5]SUBMIT PRODUCT TEST REPORTS FOR ALL
 EXTERIOR GLAZING,DOORS,ROOF COVERING
 AND IMPACT PROTECTION DEVICES
 6]ADDTIONAL FEES OWED,COUNTY IMPACT AND
 CITY RADON

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-01-15 Cont ID  
Sent By dpalmer Date 2000-01-15 Time 09:37 Rev Time 0.00
Received By dpalmer Date 2000-01-15 Time 09:37 Sent To  
Notes
2001-01-08 00:00:00************** PROVISO *****************
  
 1)NOTE: PLEASE HAVE AIC RATINGS FROM
 SPEC BOOKLET SHOWN ON PAGE E-2 OF THE
 RISER DIAGARM FOR THE M.D.P
  
 REVISED E-2 TO BE SUBMITTED FOR REVIEW
 AND APPROVAL BEFORE ROUGH ELECTRICAL
 INSPECTION IS CALLED IN.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2000-03-16 Cont ID  
Sent By dlauderm Date 2000-03-16 Time 14:53 Rev Time 2.00
Received By dlauderm Date 2000-03-16 Time 14:52 Sent To  
Notes
2001-01-08 00:00:00PASSED WITH PROVISOS:
  
 1. ALL DRIVEWAY, HANDICAP RAMPS,
 SIDEWALKS, TREES, AND TREE GRATE PLANS
 AND DETAILS WILL NEED TO BE APPROVED BY
 FDOT FOR SOUTH DIXIE AND SOUTHERN
 BOULEVARD. PERMIT THRU THEIR MAINT.
 OFFICE.
  
 2. THE DRIVEWAYS ON MALVERNE MUST MEET
 CITY STANDARDS, NOT FDOT AS CALLED OUT
 ON SHEET 3 OF 9, PER THE CIVILS.THE
 PLANS NEED TO BE CHANGED ACCORDANTLY,
 SEE ATTACHED CITY DETAILS.
  
 3.BUILDER IS NOT ASKING FOR AN
 IRRIGATION METER OR A SEPARATE LINE WITH
 BACKFLOW FOR IRRIGATION.I SUGGEST A 1-
 /2" METER FOR IRRIGATION AND A 1" FOR
 THE BUILDING.THEY ONLY HAVE AN 1-1/4"
 LINE INTO THE BUILDING.
  
 4. AS SHOWN THE CITY WILL NOT BE PICKING
 UP GARBAGE AT THIS STORE.
  
 5. ROOF DRAINS SHOWN ON P1.1 DO NOT
 MATCH CIVIL 3 OF 9.THE DRAWINGS SHOULD
 MATCH.
  
 6. NO POLLUTION CONTROL PLAN SUBMITTED.
 CIVIL ENGINEER SAID HE WILL SUBMIT.
  
 7. NO CALCULATION FOR STORM WATER HAVE
 BEEN SUPPLIED.ENGINEER SAID HE WOULD
 SUBMIT.
  
 8. CALCULATIONS FOR IMPERVIOUS AREAS FOR
 THE SITE HAVE NOT BEEN SUPPLIED.
 ENGINEER SAID HE WOULD SUBMIT.
  
 9. WATER LINES AS DRAWN WILL REQUIRE A
 DEP PERMIT.MOVE THE TAP AND BACKFLOW
 PREVENTERS NORTH TO THE CORNER OF THE
 BUILDING.AND ENTER THE BUILDING WITH
 LESS THAN 50' OF PIPE AND A DEP PERMIT
 WILL NOT BE REQUIRED.
  
 10. SHEET P1.1 SHOWS THE WATER LINE
 TRAVELING THE FULL LENGTH OF THE
 BUILDING FROM SOUTH TO NORTH.THE CIVIL
 PLAN, SHEET 3 OF 9 SHOWS THE WATER LINE
 GOING FROM SOUTH TO NORTH PARALLELING
 THE BUILDING LINE.WHY NOT TIE BOTH IN
 AT THE SOUTH END WHERE THE METER WILL BE
 LOCATED?
  
 11. IT WOULD BE PREFERRED IF THE
 SANITARY TAP WERE MADE INTO THE EXISTING
 MANHOLE AND NOT TO HAVE THE LINE CUT AND
 A "WYE" INSERTED.
  
 12. A SANITARY CLEAN OUT NEEDS TO BE
 PLACED AT THE PROPERTY LINE OF SOUTHERN
 ON THE SEWER LATERAL.
  
 13. NO OUTFALL IS SHOWN FOR THE STORM
 WATER LINE.WHERE WILL THE OUTFALL BE
 LOCATED?

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-01-05 Cont ID  
Sent By rturnque Date 2000-01-05 Time 14:33 Rev Time 0.25
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-01-28 Cont ID  
Sent By ndenmark Date 2000-01-28 Time 10:49 Rev Time 1.00
Received By ndenmark Date 2000-01-28 Time 10:49 Sent To  
Notes
2001-01-08 00:00:00*************DENIED********************
 1)ERV-2 SHOWS EXHAUST DUCT TIED TO O/A
 OF UNIT AND FRESH AIR DUCT TIED TO EX-
 HAUST CONNECTION OF UNIT
 2)COSTGARD CONDENSATE DRAIN NOT APPROVE
 NO PRODUCT APPROVAL, PROVIDE DETAIL
 ON CONDENSATE
 3)NFPA 90A 4-4.4.2 REQUIRES NOTIFICA-
 TION TO BUILDING AS WELL AS TROUBLE TO
 PANEL
 4)PROVIDE OUTSIDE AIR CALCS PER ASHRAE
 62-89
 5)AREAS WITH 300CFM OR GREATER REQUIRES
 RETURN FROM AREA
 6)PROVIDE DETAIL ON ERV FOR 15' SEPARA-
 TION OF EXHAUST AIR FROM OUTSIDE AIR IN-
 TAKE

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-01-21 Cont ID  
Sent By tlarge Date 2000-01-21 Time 17:06 Rev Time 1.00
Received By tlarge Date 2000-01-21 Time 17:06 Sent To  
Notes
2001-01-08 00:00:00JOB SPECS.15400-3-SEC.2.06-RELIEF DRAIN
 SHALL BE PIPED TO EXTERIOR PER COUNTY-
 WIDE AMENDMENTS TO SPC SEC.507.6 (3).
  
 SUBMIT OCCUPANT LOAD FOR COMPLIANCE W/
 SPC SEC.407.1.3(ADD'L.PLBG.FIXTURES
 ARE REQD.)
  
 A DRINKING FOUNTAIN IS REQD.PER SPC
 TABLE 407.
  
 LOCATION OF BACKFLOW PREVENTION DEVICE
 SHALL BE DETERMINED BY CITY OF WPB
 UTILITIES.CALL 659-8000.
  
 DESIGN OF CIRCUIT AND LOOP VENTING
 SYSTEM SHALL COMPLY W/SPC SEC.914.1.
  
 SHT.P-21-DELETE FUNNEL DRAIN AND INSTALL
 FLOOR SINK PER SPC SEC.807.1.3.
  
 HOSE BIBBS SHALL BE VALVED PER SPC SEC.
 610.4.1.
  
 SUBMITDATA FOR PH OF EFFLUENT FROM
 PHOTO SINK PH SHALL BE BETWEEN 5.0-10.0.
 COMPLY W/SPC SEC.301.3.
  
 INDICATE ON PLANS HOW SILVER AND
 CHEMICALS FROM RECOVERY UNIT WILL BE
 DISPOSED.
  
 CLEARLY SHOW WATER SUPPLY SOURCE FOR
 IRRIG.SYSTEM.A WATER USE PERMIT MAY BE
 REQD.PER F.S.373.219.
  
 PHOTO SINK NOT SHOWN ON WATER RISER,
  
 SHT.A1.3 SHOWS VTR'S WITHIN 10' OF ROOF
 EXHAUST.COMPLY W/SPC 905.5.

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***