Plan Review Details - Permit 99121470
Plan Review Stops For Permit 99121470
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-01-08 Cont ID  
Sent By dpalmer Date 2000-01-08 Time 14:29 Rev Time 0.00
Received By dpalmer Date 2000-01-08 Time 14:29 Sent To  
Notes
2001-01-08 00:00:00************PROVISO********************
  
 1)NOTE:NEED TO SUBMIT AIC RATING OF
 EQUIPMENT MAINS/PANELS. AIC RATING IS
 FIGURED FROM FAULT CURRENT CALCULATIONS.
 THIS IS REQ`D BY THE FOLLOWING ARTS;
 110-9/230-65/215-5
  
 2)NOTE: ALL OUTLETS SERVING KITCHEN
 COUNTERSPACE ARE TO BE LABELED GFI/GFI
 PROTECTED AS REQ`D BY 210-8-A-6/215-5
  
 3)NOTE: PLEASE CHECK OUTLET SPACING
 FOR REQ`D OUTLETS SERVING COUNTERSPACE.
 REQ`D PER 210-52-C-1
  
 4)NOTE:CHECK ALL WALL SPACES EXCEEDING
 2`. OUTLET SPACING TO MEET NEC PER ART;
 210-52
  
 5)NOTE;SMOKE DETECTORS ARE REQ`D INSIDE
 AND OUTSIDE ALL SLEEPING ROOMS AS REQ`D
 BY 1993/1996 NFPA-72 2-2.1.1.1.IN NEW
 DWELLING UNITS.
  
 6)NOTE:PLEASE SHOW CONDUCTOR SIZE FOR
 RISER. ALSO PLEASE SHOW ON RISER DIAGRAM
 GROUNDING ELECTRODE CONDUCTOR GOING TO
 GRND.ROD AND BLDG.STEEL. AS REQ`D BY THE
 FOLLOWING ARTS:215-5/250-81
  
 7)NOTE:PLEASE SHOW ON PANEL SCHEDULE THE
 REQ`D DEDICATED BATH(S) CIRCUT(S) PER
 ART:210-52D/215-5
  
 8)NOTE:AIR CONDITIONING LOAD TABLE SHOW
 SECOND A/C`S AS N/A??? YET LOADYOU
 SHOW TWO A/C`S ON LOAD CALCULATION.
 PLEASE CORRELATE. 215-5
  
  
 PLEASE HAVE ALL THE ABOVE INFORMATION
 SUBMITTED FOR REVIEW AND APPROVAL
 BEFORE FIRST ROUGH ELECTRICAL INSPECTION
 IS CALLED IN. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8373

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-01-07 Cont ID  
Sent By jleech Date 2000-01-07 Time 08:23 Rev Time 0.35
Received By jleech Date 2000-01-07 Time 08:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-01-04 Cont ID  
Sent By tlarge Date 2000-01-04 Time 09:42 Rev Time 0.33
Received By tlarge Date 2000-01-04 Time 09:42 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2000-02-23 Cont ID  
Sent By fknapp Date 2000-02-23 Time 11:23 Rev Time 2.00
Received By fknapp Date 2000-02-23 Time 11:23 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-02-03 Cont ID  
Sent By fknapp Date 2000-02-03 Time 10:38 Rev Time 2.00
Received By fknapp Date 2000-02-03 Time 10:38 Sent To  
Notes
2001-01-08 00:00:00 
 *****************DENIED*****************
  
 SBC 104.2.2
  
 1)PROVIDE 2 CURRENT COPIES OF PRODUCT
 APPROVALS FOR FRONT DOOR ON PLANS.
  
 2)PROVIDE WALL SECTION DETAILS OF
 CONSTRUCTION AND MATERIALS TO BE USED.
  
 3)PROVIDE CURRENAT ENERGY CALCULATIONS
 AND MANUEL J.
  
 4)PROVIDE STORM PANEL INSTALLATION
 SCHEDULE AND KEY PLAN WITH SPECIFIC
 ANCHORS TO BE USED.
  
 5)BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH CO., THE PERMIT PLANS STAMPED BY
 THEM AND THE RECIEPT ATTACHED TO THE
 PERMIT APPLICATION.

Review Stop Z ZONING
Rev No 1 Status P Date 1999-12-29 Cont ID  
Sent By gjoyce Date 1999-12-29 Time 08:41 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***