Plan Review Details - Permit 99121467
Plan Review Stops For Permit 99121467
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-07-10 Cont ID  
Sent By dpalmer Date 2000-07-10 Time 10:17 Rev Time 0.00
Received By dpalmer Date 2000-07-10 Time 10:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-01-08 Cont ID  
Sent By dpalmer Date 2000-01-08 Time 16:38 Rev Time 0.00
Received By dpalmer Date 2000-01-08 Time 16:38 Sent To  
Notes
2001-01-08 00:00:00************* PROVISO ******************
  
 1)NOTE: PLEASE CHECK AND CORRECT OUTLET
 SPACING ALONG KITCHEN COUNTERTS. AS PER
 210-52-C-1
  
 2)NOTE:AS PER 210-8-A-6 ALL OUTLETS
 SERVING KITCHEN COUNTERSPACE ARE TO BE
 GFI/GFI PROTECTED. PLEASE LABEL.
  
 3)NOTE: AS REQ`D BY 1993/1996 NFPA-72
 2-2.1.1.1 SMOKE DETECTORS ARE REQ`D
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS
 IN NEW DWELLINGS.
  
 4)NOTE: OUTLET SPACING TO MEET 210-52
 2`6`12` RULE. THIS INCLUDE KITCHEN.
  
 5)NOTE: AS REQ`D BY 215-5 PLEASE SHOW
 WIRE SIZES IN RISER.
  
 6)NOTE:PLEASE SHOW GROUND ROD AND BLDG.
 STEEL AS PART OF THE GROUNDING ELECTRODE
 SYSTEM.AS REQ`D PER 250-81/215-5
  
 7)NOTE:PLEASE LIST DEDICATED BATH(S)
 CIRCUT(S) ON PANEL SCHEDULE.20AMP #12
 AS REQ`D BY NEC ART;210-52D
  
 8)NOTE:PLEASE RE-DO LOAD CALCULATION
 TO CORRELATE. A/C LOAD TABLE SHOWS ONLY
 ONE A/C?? BUT PANEL LOAD CALC. INDICATES
 20,000 KW AS LOAD?? PLEASE CORRECT.
  
 9)NOTE: AS REQ`D BY NEC ARTS:110-9/215-5
 230-65. NEED TO SUBMIT AIC RATING OF
 MAINS/PANEL. AIC RATING IS FIGURED FROM
 FAULT CURRENT CALCULATIONS.
  
 PLEASE HAVE ALL THE ABOVE INFORMATION
 SUBMITTED FOR REVIEW AND APPROVAL
 BEFORE FIRST ROUGH ELECTRICAL INSPECTION
 IS CALLED IN. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT.8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-01-18 Cont ID  
Sent By jleech Date 2000-01-18 Time 15:50 Rev Time 0.35
Received By jleech Date 2000-01-18 Time 15:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-01-04 Cont ID  
Sent By tlarge Date 2000-01-04 Time 09:42 Rev Time 0.33
Received By tlarge Date 2000-01-04 Time 09:42 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2000-05-25 Cont ID  
Sent By rmcdouga Date 2000-05-25 Time 15:04 Rev Time 1.00
Received By rmcdouga Date 2000-05-25 Time 10:09 Sent To  
Notes
2001-01-08 00:00:00TRUSSES
  
 ***************DENIED*******************
  
 1)TRUSS DRAWINGS NOT REVIEWED BY
 DESIGNER OF RECORD.TRUSS LAYOUT MUST BE
 SIGNED AND DATED BY DESIGNER OF
 STRUCTURE AND SIGNED SEALED AND DATED BY
 TRUSS ENGINEER.
  
 2)PROVIDE TRUSS SHOP DRAWINGS SIGNED
 (WET SIGNATURE),SEALED AND DATED,EACH
 PAGE.
  
  
 3)DESIGN CRITERIA USED FOR TRUSS
 DRAWINGS IS ASCE7-93,THE DESIGN STANDARD
 FOR CURRENT CODE (97 SBC) IS ASCE7-95.
 PLEASE PROVIDE UPDATED DESIGN CRITERIA.
  
 4)ROOF LOADS SPECIFIED ON ARCHITECTURAL
 PLANS DO NOT COINCIDE WITH THE LOADS ON
 TRUSS LAYOUT. PLEASE REVISE.
  
 5)ENGINEERED ROOF TRUSS DRAWINGS NOTE #2
 GIVES HOUSE DIMENSIONS AS 45'X 24'.THESE
 DO NOT CORRESPOND WITH THE DIMENSIONS ON
 ARCHITECTURAL DRAWINGS.PLEASE REVISE.
  
 6)SPECIFY TRUSS TO TRUSS ANCHORS TO BE
 USED.
  
  
  
 IF YOU HAVE ANY QUESTIONS CALL ROBERT
 MCDOUGAL AT (561) 659-8096 EXT.8202

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2000-02-23 Cont ID  
Sent By fknapp Date 2000-02-23 Time 10:54 Rev Time 1.00
Received By fknapp Date 2000-02-23 Time 10:53 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-02-03 Cont ID  
Sent By fknapp Date 2000-02-03 Time 08:24 Rev Time 3.00
Received By fknapp Date 2000-02-01 Time 16:14 Sent To  
Notes
2001-01-08 00:00:00****************DENIED******************
 SBC 104.2.2
  
 1)PROVIDE 2 CURRENT COPIES OF PRODUCT
 APPROVALS FOR FRONT DOOR ON PLANS.
  
 2)PROVIDE WALL SECTION DETAILS OF
 CONSTRUCTION AND MATERIALS TO BE USED.
  
 3)PROVIDE CURRENT ENERGY CALCULATIONS
 AND MANUEL J.
  
 4)PROVIDE STORM PANEL INSTALLATION
 SCHEDULE AND KEY PLAN WITH SPECIFIC
 ANCHORS TO BE USED.
  
 5)BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH CO.,THE PERMIT PLANS STAMPED BY
 THEM AND THE RECIEPT ATTACHED TO THE
 PERMIT APPLICATION.

Review Stop Z ZONING
Rev No 1 Status P Date 1999-12-29 Cont ID  
Sent By gjoyce Date 1999-12-29 Time 08:41 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***