| 2001-04-23 00:00:00 | *************BUILDING UNSAT************* |
| | |
| | 1) STRUCTURE IS LOCATED IN AN "A8" FLOOD |
| | ZONE AN ELEVATION CERTIFICATE WILL BE |
| | REQUIRED PRIOR TO RECEIVING A C.O. |
| | |
| | 2) THE TYPICAL EXTERIOR CEILING DETAIL |
| | ON SHEETS A-1 & A-1B IS FOR VERTICLE |
| | APPLICATION. SECTION 2504.2.2 OF THE |
| | 1997 SBC REFERS TO ASTM C 1603, WHICH |
| | REQUIRES 1 3/4" PENETRATION INTO |
| | HORIZONTAL WOOD FRAMING MEMBERS FOR LATH |
| | ON CEILINGS. PLEASE CORRECT. |
| | |
| | 3) THE MAXIMUM HEIGHT OF THE PRIVACY |
| | WALL INDICATED ON SHEETS A-1 & A-1B IS |
| | 6'. PLEASE CORRECT. |
| | |
| | 4) THE PRESSURES LISTED IN THE WINDOW |
| | PRESSURE SCHEDULE ON SHEETS A-4A & A-4B |
| | FOR (J,S,&T) DO NOT CORRESPOND WITH |
| | THOSE LISTED ON THE ELEVATION DRAWINGS |
| | ON THE SAME SHEETS. PLEASE CORRECT. |
| | |
| | 5) SECTION 104.2.1 OF THE CITY OF W.P.B. |
| | AMENDMENTS TO THE 97 SBC REQUIRES |
| | INFORMATION TO BE SPECIFIC AND STATES |
| | THAT THE TECHINCAL CODES SHALL NOT BE |
| | CITED. ON SHEETS A-3A & A-8A THE STAIR |
| | DETAILS STATE THAT STAIRS ARE TO BE |
| | CONSTRUCTED IN ACCORDANCE W/SEC. 1007 OF |
| | 1997 SBC. PLEASE PROVIDE DETAILS OF |
| | HANDRAILS AND GUARDRAILS, INCLUDING |
| | SPACING OF INTERMEDIATE RAILS, ETC. |
| | |
| | 6) PER SEC.1007.3 OF 1997 SBC THE SUM OF |
| | 2 RISERS AND 1 TREAD IS TO BE NOT LESS |
| | THAN 24" NOR MORE THAN 25". THE |
| | DIMENSIONS GIVEN ON SHEETS A-3A & A-8A, |
| | DO NOT COMPLY. PLEASE CORRECT. |
| | |
| | 7) THE ALLOWABLE WINDLOADS LISTED IN THE |
| | PRODUCT APPROVAL FOR A 16'X7' GARAGE |
| | DOOR IS EXCEEDED BY THOSE GIVEN ON SHEET |
| | A-4A & A-4B. PLEASE CLARIFY. |
| | |
| | THESE SAME ISSUES ARE RECURRING ON THESE |
| | MODELS. PLEASE MAKE THESE CORRECTIONS TO |
| | THE ORIGIONALS TO HELP EXPEDIATE THE |
| | PLAN REVIEW PROCESS. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |