Plan Review Details - Permit 99121448
Plan Review Stops For Permit 99121448
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-11-20 Cont ID  
Sent By dpalmer Date 2000-11-20 Time 19:47 Rev Time 0.00
Received By dpalmer Date 2000-11-20 Time 19:47 Sent To  
Notes
2001-01-08 00:00:00********** REVISION REQ`ESTED ********
  
 1)NOTE: PLEASE SEE RISER DIAGRAM AND
 PANEL DETAIL.?? ONE SHOWS MLO AND THE
 OTHER MCB. PLEASE CORRELATE.
  
 2)NOTE: PLEASE SHOW MAIN DISCONNECT ON
 PLAN. MAIN NOT SHOWN NEXT TO METER??
 215-5
  
 3)NOTE: PLEASE CLARIFY EQUIPMENT GROUND-
 -ING CONDUCTOR FROM FIRST MEANS OF DISC
 TO PANEL. SIZE PER 250-122
  
 PLEASE SUBMIT THE ABOVE INFORMATTION FOR
 REVIEW BEFORE FINAL ELECTRICAL INSPECT-
 -ION IS CALLED IN. IF THERE ARE ANY
 QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-11-14 Cont ID  
Sent By jleech Date 2000-11-14 Time 19:50 Rev Time 0.33
Received By jleech Date 2000-11-14 Time 19:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-11-14 Cont ID  
Sent By jleech Date 2000-11-14 Time 19:50 Rev Time 0.33
Received By jleech Date 2000-11-14 Time 19:50 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2001-02-14 Cont ID  
Sent By jgomez Date 2001-02-14 Time 16:42 Rev Time 0.50
Received By jgomez Date 2001-02-14 Time 16:40 Sent To  
Notes
2001-02-14 00:00:00TRUSS DRAWINGS CHECKLIST:
 1-
 TRUSS DRAWINGS CHECKLIST:
 1-CLARIFY WHO IS THE ENGINEER FOR THESE
 TRUSS DRAWINGS. THERE ARE TWO
 DIFFERENT ENGINEERED TRUSS PACKAGES.
 2-IT'S NOT CLEAR WHO'S THE ENGINEER WHO
 SEALED AND DATED DRAWINGS ON JANUARY
 23, 2001.
 -ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS, AND NUMBER ON EACH
 SHEET AS REQUIRED BY CHAPTER 471 OF
 FLORIDA STATUTES.
 3-MEAN ROOF HEIGHT IS +/- 23'-8".
 REVISE ENGINEERED TRUSS DRAWINGS AS
 REQUIRED.
 -SBC 1997 DOESN'T USE "WALL HEIGHT". IT
 USES THE MEAN ROOF HEIGHT. REVISE
 ENGINEERED TRUSSES AS REQUIRED.
 4-CHECK IF CONNECTORS SPECIFIED WILL BE
 ADEQUATE TO RESIST THE LOADS AS
 CALCULATED ON THE REVISED ENGINEERED
 TRUSS DRAWINGS PRIOR TO SUBMITTAL TO
 THIS OFFICE.
  
  
  
  
  
 IF YOU HAVE QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 659-8096 EXT. 8232.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2000-12-01 Cont ID  
Sent By jgomez Date 2000-12-01 Time 14:20 Rev Time 3.00
Received By jgomez Date 2000-12-01 Time 14:20 Sent To  
Notes
2001-01-08 00:00:00APPROVED WITH PROVISO:
  
 1-FLOOD ZONE "A8". NEED TO PROVIDE
 ELEVATION CERTIFICATE.
 2-GARAGE DOOR PRODUCT APPROVAL DOESN'T
 MEET THE DESIGN PRESSURES CALCULATED
 BY THE ENGINEER. RESUBMIT.
 3-PROVIDE PRODUCT APPROVAL FOR:
 -FLAT ROOF SYSTEM.
 -FRENCH DOORS.
 4-SEE COMMENTS ON PLANS AND REVISE/
 UPDATE/CLARIFY AS REQUIRED.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-06-20 Cont ID  
Sent By lsmith Date 2000-06-20 Time 14:58 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
2001-01-08 00:00:00FAILED PER TM 6/19/00

Review Stop Z ZONING
Rev No 1 Status P Date 2000-02-10 Cont ID  
Sent By gjoyce Date 2000-02-10 Time 15:52 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***