| 2001-01-08 00:00:00 | *************** UNSAT ****************** |
| | |
| | THE FOLLOWING IS A LIST FOR WHICH NEEDS |
| | TO BE COMPLETELY TAKEN CARE OF! |
| | |
| | 1)NOTE:NEED TO SHOW BLDG.STEEL AS PART |
| | OF THE GORUNDING ELECTRODE SYSTEM. AS |
| | REQ`D BY ART;250-81/215-5 |
| | |
| | 2)NOTE: A 18 POLE PANEL IS SHOWN! THIS |
| | PANEL DOES NOT HAVE ENOUGH SPACES!!! |
| | PLEASE COUNT BRKRS AND INCLUDE TWO |
| | SPARE SPACES AS REQ`D BY NEC. |
| | |
| | 3)NOTE:PLEASE CHECK A/C HEAT THAT IS |
| | GOING TO BE INSTALLED?? MOST ARE 7500KW |
| | IN WHICH CASE,,PLEASE CHANG LOAD CALC. |
| | |
| | 4)NOTE:#8 IS NOT REQ`D FOR DRYER AND HOT |
| | WATER HEATER BUT MAY BE INSTALLED. |
| | |
| | 5)NOTE:PLANS SHOW 3310 SQ.FT OF LIVING |
| | SPACE BEING BUILT!! THE LOAD CALCULATION |
| | -S DO NOT MATCH. PLEASE REFIGURE TO |
| | NEC. |
| | |
| | 6)NOTE:PANEL SCHEDULE NEED TO SHOW |
| | DEDICATED BATH(S) CIRCUT AND NEEDS TO BE |
| | 20AMP #12 AWG. AS REQ`D BY ART;210-52D/ |
| | 215-5 |
| | |
| | 7)NOTE:PLANS NEED TO SHOW A/C COND.UNIT |
| | WITH MEANS OF DISC. PER 440-1 AND WP |
| | GFI REC. REQ`D BY 210-63 |
| | |
| | 8)NOTE:PLANS ARE MISSING REC. AS REQ`D |
| | BY ART;210-52E OF THE NEC. |
| | |
| | 9)NOTE:AS REQ`D BY ART;210-52-C-1 |
| | NEED TO SPACE OUTLETS TO MEET CODE ALONG |
| | KITCHEN COUNTERSPACE. |
| | |
| | 10)NOTE: PLANS SHOW NOOK??? IN KITCHEN?? |
| | IS THIS AN ISLAND? IF SO THEN OUTLETS |
| | MUST CONFORM TO ART;210-52-C-3 OF THE |
| | NEC. |
| | 11)NOTE:ALSO AS REQ`D BY ART;210-8-A-6 |
| | OF THE NEC. ALL OUTLETS SERVING KITCHEN |
| | COUNTERSPACE ARE TO BE GFI/GFI PROTECTED |
| | PLEASE SHOW!!! |
| | |
| | 12)NOTE:PLANS SHOW NO MEANS OF EGRESS |
| | LIGHTING WHICH IS REQ`D BY ART;210-70 |
| | AT THE FRONT DOOR.??? |
| | |
| | 13)NOTE:AS REQ`D BY ART;210-8-A-2 RECEPT |
| | -S IN UTILITY ROOM MUST BE GFI. |
| | |
| | 14)NOTE:BEDROOM #3 SHOWS NO DOOR??? |
| | AS REQ`D BY 1993.1996 NFPA-72 2-2.1.1.1 |
| | SMOKE DETECTORS ARE REQ`D INSIDE AND |
| | OUTSIDE ALL SLEEPING ROOMS OF NEW |
| | DWELLINGS.ALL,,, |
| | |
| | PLEASE HAVE ALL THE ABOVE INFORMATION |
| | SUBMITTED FOR REVIEW AND APPROVAL. |
| | ALSO PLEASE HAVE ELECTRICAL DRAWN ON |
| | THERE OWN SHEET FOR BETTER CLARITY OF |
| | WORK TO BE DONE. 215-5 |
| | IF THERE ARE ANY QUESTIONS ABOUT COMMENT |
| | -S. PLEASE CALL 659-8096 EXT 8372 TO SET |
| | UP A MEETING. |