Plan Review Details - Permit 99121294
Plan Review Stops For Permit 99121294
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-04-19 Cont ID  
Sent By hpiskura Date 2001-04-19 Time 10:01 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-04-19 00:00:00OWES IMPACT FEES
  
 REPLACE EXPIRED AND ILLEGIBLE PRODUCT
 REPORTS.
  
 PROVIDE REINFORCED MASONRY SPEC
 CHECKLIST

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-11-09 Cont ID  
Sent By hpiskura Date 2000-11-09 Time 14:56 Rev Time 0.00
Received By hpiskura Date 2000-11-09 Time 09:15 Sent To  
Notes
2001-01-08 00:00:00LETTER W/ APPLICATION

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-04-26 Cont ID  
Sent By dpalmer Date 2001-04-26 Time 19:55 Rev Time 0.00
Received By dpalmer Date 2001-04-26 Time 19:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2000-11-20 Cont ID  
Sent By dpalmer Date 2000-11-20 Time 23:12 Rev Time 0.00
Received By dpalmer Date 2000-11-20 Time 23:12 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE SEE F.A.C CHAPTER 481.221
 RAISED SEAL MUST BE CLEARLY VISIBLE
 WITH NAME/NUMBER ETC. SIGNATURE MUST
 BE DATED.
  
 2)NOTE: PLEASE SHOW BLDG STEEL AS PART
 OF THE GROUNDING ELECTRODE SYSTEM AS REQ
 -D BY 250-50.
  
 3)NOTE: PLEASE SEE HOUSE SERVICE. AIC
 RATING FOR MAIN DISCONNECT IS ALSO REQ`D
 PER 215-5 AND RATED PER 110-9.
  
 4)NOTE: PLEASE SEE 384-7 FOR PANEL LOCA-
 -TION.
  
 5)NOTE: PLEASE SEE F.H.A.R,24CFR 100.205
 FOR ALL THE REQ`MENTS OF DEVICE HEIGHTS.
 NOT ALL NOTES SHOWN ON EM-1 COMPLY.
  
 6)NOTE: PLEASE SEE LOCATION OF HWH.IN
 BATH AND MOUNTED ABOVE. THIS MUST REMAIN
 READILY ACCESS. FOR THE ELECTRICAL DISC-
 -ONNECT.
  
 7)NOTE: ALSO PLEASE NOTE GROUNDING ELEC-
 -TRODE CONDUCTOR TO BLDG STEEL AS PER
 250-50.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-02-12 Cont ID  
Sent By dpalmer Date 2000-02-12 Time 16:34 Rev Time 0.00
Received By dpalmer Date 2000-02-12 Time 16:34 Sent To  
Notes
2001-01-08 00:00:00************** UNSAT *****************
  
 1)NOTE: NEED TO SUBMIT AIC RATING OF ALL
 EQUIPMENT. MAINS MUST BE RATED FOR THE
 AVAILABLE FAULT CURRENT AS PER ARTS:
 110-9/110-10
  
 2)NOTE:SMOKE DETECTORS ARE REQ`D INSIDE
 AND OUTSIDE ALL SLEEPING ROOMS IN NEW
 DWELLINGS. IF FIRE ALARM SYSTEM IS BEING
 INSTALLED THEN PLEASE INDICATE.
  
 3)NOTE: PLEASE SHOW HEIGHTS OF ALL
 DEVICES IN UNITS. ALL MUST COMPLY WITH
 THE FEDERAL FAIR HOUSING ACT.
 24 CFR 100.205 CHAPTER 5.
  
 4)NOTE: PLEASE INDICATE THE DEDICTED
 BATH(S) CIRCUT(S) REQ`D BY 210-52D OF
 THE NEC.LIST ON PANEL SCHEDULE.
  
 5)NOTE; JUST FYI,,, YOU SHOW 3/0 ON
 RISER DIAGRAM WHICH IS GOOD FOR 225AMPS?
 YOUR LOAD IS ONLY 83 AMPS AND MAIN DISC.
 IS 150AMPS??? YOU CAN ADJUST YOUR WIRE
 SIZE FOR THE 150AMP OVERCURRENT DEVICE.
  
 6)NOTE: ALL OUTLETS SERVING KITCHEN
 COUNTERSPAACE MUST BE GFI/GFI PROTECTED.
 AS REQ`D BY ART;210-8-A-6
 PLEASE INDICATE THIS ON PLANS.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW AND APPROVAL. IF THERE ARE
 ANY QUESTIONS PLEASE CALL 659-8096 EXT
 8372

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2001-04-17 Cont ID  
Sent By mamini Date 2001-04-17 Time 09:10 Rev Time 3.00
Received By mamini Date 2001-04-17 Time 09:13 Sent To  
Notes
2001-04-17 00:00:00PASSED:
 1. RESPONSES TO PREVIOUS REVIEW COMMENTS
 DATED 11-27-00 SATISFACTORY.
 IF ANY QUESTION PLEASE CONTACT 561- 659-
 8096 EXT. 8492

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2000-11-27 Cont ID  
Sent By mgonzale Date 2000-11-27 Time 07:34 Rev Time 1.00
Received By mgonzale Date   Time   Sent To  
Notes
2001-01-08 00:00:00FAILED, WITH COMMENTS:
 PERVIOUS AND IMPERVIOUS CALCULATIONS
 MUST BE SHOWN ON PAVING AND DRAINAGE
 PLAN THE TOTAL AMOUNT MUST EQUAL 100%
 OF TOTAL SITE ACRES OR S.F.
 PLEASE STATE EITHER ADDRESSES OR
 PROPERTY CONTROL NUMBERS
 STORM CHARGES WILL BE CALCULATED FROM
 THESE.
 ON WATER AND SEWER PLAN
 YOU INDICATED 5 METERS CONNECTING OFF
 THE 2" SERVICE. THIS EXCEEDS THE
 AMOUNT.
 FOR A 2" SINGLE SERVICE LINE YOU MAY HAV
 E A MAXIMUM OF 4- 5/8" BY 3/4" METERS
 OR 4- 3/4" METERS.
 PLEASE STATE THE SIZE OF PROPOSED METERS
 MOVE CLEAN-OUTS SO THAT THEY FALL JUST
 OUTSIDE OF SIDEWALK AREAS SO THAT
 IT DOES NOT POSSES A TRIPPING HAZZARD.
 ONCE REVISED TWO SETS OF PLANS MUST BE
 SUBMITTED TO PUABLIC UTILITIES
 ENGINEERING SERVICES DEPARTMENT FOR
 REVIEW. ATTENTION MANNY GONZALEZ
 PLEASE INCLUDE STORM CALCULATIONS SO
 THAT I MAY PASS THEM TO JOSE DEL RIOS
 OUR STORM WATER ENGINEER.
 1000 45TH ST, SUITE 15 WPB FL 33407
 561 659 8040 EXT. 2306
 HAVE A GREAT DAY.
 18" MIN CLR MUST BE MAINTAINED WHERE
 WATER AND SANITARY SEWER CROSSES.
 DRIVEWAYS ENTERING EACH UNIT MUST BE BUI
 LT PER CITY OF WEST PALM BEACH STANDARD
 DRIVEWAY APPROCHDETAIL.
 SEE ATTACHED. IT MAY BE REQUESTED THROUG
 H EMAIL AT [email protected].
 FL.US
 WORK PERFORMED ALONG ROW REQUIRES A
 CITY ROW PERMIT AT NO COST.
 IT CAN BE OBTAIN AT THE SAME ADDRESS
 WRITTEN ABOVE.IT MUST BE SIGN APPROVED
 BY RICHARD D. PITTMAN, CITY ENGINEER.
 HAVE A GREAT DAY IF YOU HAVE ANY QUESTIO
 NS FEEL FREE TO CONTACT MY OFFICE.
 WHEN SUBMITTING TO PUBLIC UTILITIES AGAI
 N WE JUST NEED THE PLANS MADE BY CALVIN
 GIORDANO AND ASSOCIATES. ARCHITECT PLANS
 NOT REQUIRED.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By dlauderm Date 2000-02-14 Time 14:01 Sent To  
Notes
2001-01-08 00:00:00STREETS AND SIDEWALKS:
 1. DRIVEWAY DETAILS WILL BE TO CITY
 STANDARDS.SEE ATTACHED DETAILS.
 2. WORK IN STREET AND SIDEWALK WILL NEED
 TO BE PERMITTED AND INSPECTED THROUGH
 THE ENGINEERING DEPARTMENT. SEE COPY OF
 BLANK ROW PERMIT.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2000-02-14 Cont ID  
Sent By dlauderm Date 2000-02-14 Time 12:04 Rev Time 2.00
Received By dlauderm Date 2000-02-14 Time 12:03 Sent To  
Notes
2001-01-08 00:00:00FAILED, WITH COMMENTS:
 A.STORM WATER REQUIREMENTS:
 TO OBTAIN A CONSTRUCTION PERMIT THE
 FOLLOWING MUST BE SUBMITTED SIGNED AND
 SEALED BY A FLORIDA PROFESSIONAL
 ENGINEER (PE).
 1.CONSTRUCTION PLANS (WHERE WILL THE
 DRIVEWAYS DRAIN TO? INTO THE LANDSCAPED
 AREAS? EXPLAIN)
 2.DETAILS AND SPECIFICATIONS (NOT
 SUPPLIED)
 3.HYDRAULIC COMPUTATIONS AND SUPPORTING
 DOCUMENTATION (NOT SUPPLIED).
 4.IMPERVIOUS AREA COMPUTATIONS (NOT
 SUPPLIED).
 5.POLLUTION PREVENTION PLAN (NOT
 SUPPLIED).THE POLLUTION PREVENTION
 PLAN SHALL BE KEPT ON SITE AT ALL TIMES
 DURING CONSTRUCTION. THE PLAN SHALL BE
 INSTALLED IN THE FIELD PRIOR TO ANY
 EARTHWORK. THE ENGINEER OF RECORD SHALL
 CERTIFY TO THE CITY, ON A MONTHLY BASIS,
 THAT THE PLAN IS WORKING PROPERLY AND AS
 DESIGNED. THE ENGINEER OF RECORD IS
 RESPONSIBLE TO CERTIFY IMPLEMENTATION OF
 THE PROVISIONS OF CITY ORDINANCE NO.
 3132-98 OF THE CITY CODE AT SUCH TIME
 THE PERMITTEE APPLIES FOR A CERTIFICATE
 OF OCCUPANCY FROM THE CITY BUILDING
 OFFICIAL.
 6.EVERY SIX MONTHS AFTER CONSTRUCTION A
 PE SHALL CERTIFY THAT THE PERMANENT
 POLLUTION PREVENTION STRUCTURES, DRY-WET
 WATER DETENTION FACILITIES, AND
 EXFILTRATION SYSTEMS ARE WORKING AS
 DESIGNED AND ARE IN GOOD OPERATING
 CONDITION. ALL CERTIFICATIONS MUST BE
 SUBMITTED TO:
 STORM WATER UTILITY ENGINEER
 CITY OF WEST PALM BEACH PUBLIC UTILITIES
 DEPARTMENT
 P.O. BOX 3366, WEST PALM BEACH, FL
 33402.
 THE CERTIFICATION MUST INCLUDE THE
 BUILDING PERMIT NUMBER, THE ADDRESS OF
 THE PROPERTY AND THE NAME OF THE
 ESTABLISHMENT/PROJECT CONSTRUCTED.
 B.WATER SANITARY COMMENTS:
 PLANS HAVE BEEN MARKED UP AS TO THE
 CHANGES THAT WILL BE REQUIRED.
 1.NO SIZE GIVEN FOR THE METERS.UNITS
 OF THIS SIZE USUALLY HAVE 5/8 BY 3/4"
 METERS WHICH WILL GIVE YOU 10 GALLONS A
 MINUTE. YOU MUST CALL OUT SIZE OF METER.
 2. DETAILED PLANS WILL NEED TO BE
 SUBMITTED SHOWING TAPS INTO THE EXISTING
 SANITARY MAIN BY YOUR CONTRACTOR.
 CONTACT 659-8079 AND HAVE THE CREW CHECK
 TO SEE IF THERE ARE EXISTING LATERALS
 YOU CAN USE PRIOR TO DRAWING UP NEW
 PLANS.
 3.OUR STANDARD DETAILS WILL NEED TO BE
 USED FOR 6" HOUSE LATERALS TO THE
 PROPERTY LINE, WITH CLEAN-OUTS AT THE
 POINT OF CONNECTION.PIPING ON SITE
 NEEDS TO MEET PLUMBING CODE, 4" MAY BE
 ALLOWED, CHECK WITH THE PLUMBING
 INSPECTOR.
 4.WATER METERS MUST BE IN THE
 SIDEWALK.DUAL SERVICES WITH 1" COPPER
 IS REQUIRED FOR ANY TWO METERS (5/8 BY
 3/4 OR 3/4").ANYTHING ELSE WILL NEED
 TO BE A 2" EXTENDED SERVICE (WITH A
 MAXIMUM OF TWO METERS (5/8 BY 3/4 OR
 3/4") ALL BY YOUR CONTRACTOR.CONTACT
 659-8079 AND HAVE THE CREW CHECK TO SEE
 IF THERE ARE EXISTING SERVICES YOU CAN
 USE PRIOR TO DRAWING UP NEW PLANS.
 5.A SEPARATE IRRIGATION METER IS NOT
 CALLED OUT FOR THE PUBLIC AREAS, NO
 SEPARATE METER IS CALLED OUT FOR THE
 POOL EITHER.IN EITHER CASE THE METER
 TO THE POOL OR THE IRRIGATION SYSTEM
 WILL HAVE TO HAVE A BACKFLOW PREVENTER
 INSTALLED AT THE PROPERTY LINE, AFTER
 THE METER.
 6.NO LATERAL IS SHOWN FOR THE POOL.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2001-04-18 Cont ID  
Sent By mcarsill Date 2001-04-18 Time 13:32 Rev Time 0.00
Received By mcarsill Date 2001-04-18 Time 13:32 Sent To  
Notes
2001-04-18 00:00:001) BUILDING ADDRESSES REQUIRED PER
 CITY CODE REQUIREMENTS.
 2) PREVIOUS PLAN REVIEW COMMENTS
 NOTED A FIRE ALARM SYSTEM REQUIREMENT
 PER CAPTAIN RHETT TURNQUEST. PLEASE
 ADDRESS THIS PREVIOUS PLAN REVIEW
 COMMENT.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-10-25 Cont ID  
Sent By rturnque Date 2000-10-25 Time 10:41 Rev Time 0.20
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-01-26 Cont ID  
Sent By rturnque Date 2000-01-26 Time 11:50 Rev Time 0.20
Received By rturnque Date   Time   Sent To  
Notes
2001-01-08 00:00:001. PROVIDE APPROVED WIRED-IN SMOKE
 DETECTORS IN EACH LIVING UNIT.
 2. PROVIODE AN APPROVED CLASS "A" OR
 ADDRESSABLE FIRE ALARM SYSTEM THROUGHOUT

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-04-26 Cont ID  
Sent By pkrauss Date 2001-04-26 Time 11:17 Rev Time 1.00
Received By pkrauss Date 2001-04-26 Time 11:16 Sent To  
Notes
2001-04-26 00:00:00MECH PERMIT 99121299.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2000-11-27 Cont ID  
Sent By ndenmark Date 2000-11-27 Time 14:29 Rev Time 0.50
Received By ndenmark Date 2000-11-27 Time 14:29 Sent To  
Notes
2001-01-08 00:00:00***************DENIED*******************
  
 1.TENANT SEPARATION DETAIL SHOWS MIN. 4'
 FROM WALL W/ REQUIRED ASSEMBLY. SEE A-4
 DETAIL B-A-4. DRYER VENT AND BATHROOM
 EXHAUST VENT SHALL NOT PENETRATE ROOF
 WITHIN THIS 4' SPACE.
 2.CABANA EXHAUST FANS TO TERMINATE OUT
 OF DOORS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-01-22 Cont ID  
Sent By jleech Date 2000-01-22 Time 07:39 Rev Time 0.75
Received By jleech Date 2000-01-22 Time 07:39 Sent To  
Notes
2001-01-08 00:00:00DENIED;
 1.SIZE A/C RETURN AIR GRILL AND DUCT.
 2.LAUNDRY AREA REQUIRED.
 3.EQUIPMENT MANUFACTOR, MODEL NUMBER
 AND HEAT STRIP SIZE REQUIRED ON APPROVED
 DRAWINGS.

Review Stop P PLUMBING
Rev No 3 Status F Date 2001-05-01 Cont ID  
Sent By kstevens Date 2001-05-01 Time 12:54 Rev Time 3.50
Received By kstevens Date 2001-05-01 Time 12:39 Sent To  
Notes
2001-05-01 00:00:00REVIEW NOTES:
  
 (1) ALL BATHROOMS AND KITCHENS IN THE
 COVERED DWELLING UNIT SHALL COMPLY W/THE
 REQUIREMENTS OF THE FEDERAL FAIR HOUSING
 ACT 24 CFR 100.205 (C) (3) (I-IV) REQ #7
 (2) PARAGRAPH (A) OR (B). CLEAR FLOOR
 SPACE SHALL BE PROVIDED AT FIXTURES. THE
 REQD. CLEAR FLOOR SPACE SHALL BE SHOWN
 ON THE PLANS AND THE DESIGN OPTION A OR
 B SHALL ALSO BE NOTED ON THE PLANS.
  
 (2) WASHERS AND DRYERS FOR DWELLING
 UNITS SHALL BE ON AN ACCESSIBLE ROUTE
 PER FEDERAL FAIR HOUSING ACT 24 CFR
 100.205.
  
 (3) SHEET EM-1 GENERAL PLUMBING NOTES:
 AIR CHAMBERS SHALL COMPLY WITH
 SPC-94 607.8.2 & 607.8.3 THEY
 WILL BE ACCESSABLE & RECHARGEABLE.
  
 (4) CABANA OK. SUBMIT SEPARATE PLANS TO
 GET PERMIT OR WAIT UNTIL PLANS ARE
 APPROVED.
  
 REVIEW BY KEN STEVENS (561) 659-8096
 EXT. 8377

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-10-29 Cont ID  
Sent By tlarge Date 2000-10-29 Time 06:40 Rev Time 2.50
Received By tlarge Date 2000-10-29 Time 05:36 Sent To  
Notes
2001-01-08 00:00:001)SUBMIT DETAILS OF REINFORCEMENT OF
 WALLS IN BATHROOMS FOR FUTURE INSTALL-
 ATION OF GRAB BARS AS REQUIRED BY THE
 FEDERAL FAIR HOUSING ACT 24 CFR 100.205
 SEC.3,REQUIREMENT #6.
 NOTE:ALL BATHROOMS IN THE COVERED
 DWELLING UNIT SHALL COMPLY.
  
 2)ALL BATHROOMS AND KITCHENS IN THE
 COVERED DWELLING UNIT SHALL COMPLY W/THE
 REQUIREMENTS OF THE FEDERAL FAIR HOUSING
 ACT 24 CFR 100.205 (C)(3)(I-IV)REQ.#7(2)
 PARAGRAPH (A) OR (B).CLEAR FLOOR SPACE
 SHALL BE PROVIDED AT FIXTURES TO ALLOW A
 PERSON IN A WHEELCHAIR OR OTHER MOBILITY
 AID USE OF THE FIXTURES.THE REQD.CLEAR
 FLOOR SPACE SHALL BE SHOWN ON THE PLANS
 AND THE DESIGN OPTION (A OR B)SHALL ALSO
 BE NOTED ON THE PLANS.
  
 3)PERMITS ARE REQD.FROM P.B.COUNTY
 HEALTH DEPT.& DEPT. OF ENVIRONMENTAL
 PROTECTION FOR THE WATER SYSTEM. COUNTY-
 WIDE AMENDMENTS TO SPC SEC.101.4.7.
  
 4)WATER SERVICES SHALL BE EQUIPPED W/
 APPROVED BFP DEVICES.CONTACT CITY OF WPB
 UTILITIES FOR REQS.
  
 5)SHT.A-2-PLBG.PLAN NOTES-GENERAL
 REFERENCE TO CODE IS NOT PERMITTED PER
 COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1
  
 6)A-2-NOTE #8-INSERT"STANDARD PLUMBING
 CODE 1994 ED."INSTEAD OF NATIONAL PLBG.
 CODE.COUNTYWIDE AMENDMENTS TO SPC SEC.
 101.1.
  
 7)DRINKING FOUNTAIN FOR CABANA SHALL
 COMPLY W/FACBC SEC.4.1.3(10)(A).
 PROVISIONS SHALL BE MADE FOR PEOPLE WHO
 HAVE TROUBLE BENDING OR STOOPING.
  
 8)FLOOR S AND WALLS IN CABANA SHALL BE
 NONABSORBENT TO A HEIGHT OF 4' PER SBC
 SEC.1204.2.
  
 9)WASHERS AND DRYERS FOR DWELLING UNITS
 SHALL BE ON AN ACCESSIBLE ROUTE PER
 FEDERAL FAIR HOUSING ACT 24 CFR 100.205
 (C)(3)(I)
  
 10)WATER HEATERS SHALL BE READILY
 ACCESSIBLE PER SPC SEC.501.7.SUPPLY
 SHIP'S LADDER AND PLATFORM OR RELOCATE
 EWH TO FLOOR.
  
 11)HEATER PANS SHALL BE EQUIPPED W/
 DRAINS AND COMPLY W/SPC SEC.507.8.2.
  
 12)PAN DRAINS AND EWH RELIEF VALVE SHALL
 BE PIPED TO AN APPROVED POINT OF
 DISPOSAL PER SPC SECS.507.8.3,507.8.4.
  
 13)WATER SUPPLY CONTROL FOR FIXTURES IN
 DWELLING UNITS SHALL COMPLY W/SPC SEC.
 610.3.1.
  
 14)PLUMBING FIXTURES SHALL BE OF WATER
 CONSERVATION TYPE AND COMPLY W/SPC SEC.
 406.
  
 15)WATER RISER SHOWS 1/2"LINE SUPPLYING
 A 3/4"LINE TO THE FIXTURES.MAX.OF 4
 FIXTURES SHALL BE SUPPLIED BY A 1/2"
 LINE PER COUNTYWIDE AMENDMENTS TO SPC
 SEC.607.7.
  
 16)SUBMIT IRRIGATION PLANS FOR REVIEW.
 A WATER USE PERMIT WILL BE REQD.FROM
 SO.FLA.WATER MNGMT.AND A PERMIT FROM
 PB COUNTY HEALTH DEPT.WILL BE REQD.FOR
 THE WELL.COUNTYWIDE AMENDMENTS TO SPC
 SEC.101.4.7.
  
 CALL IF YOU HAVE QUESTIONS.
 561-659-8096,EXT.8377.
  
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-01-04 Cont ID  
Sent By tlarge Date 2000-01-04 Time 18:14 Rev Time 1.50
Received By tlarge Date 2000-01-04 Time 18:14 Sent To  
Notes
2001-01-08 00:00:00SUBMIT DETAILS OF REINFORCEMENT OF WALLS
 IN BATHROOMS FOR FUTURE INSTALLATION OF
 GRAB BARS AS REQUIRED BY THE FEDERAL
 FAIR HOUSING ACT 24 CFR 100.205 SEC.3,
 REQUIRREMENT #6.
 NOTE:ALL BATHROOMS IN THE COVERED
 DWELLING UNIT SHALL COMPLY.
  
 ALL BATHROOMS AND KITCHENS IN THE
 COVERED DWELLING UNIT SHALL COMPLY W/THE
 PROVISIONS OF THE FEDERAL FAIR HOUSING
 ACT 24 CFR 100.205 (C)(3)(I- IV)REQ.#7,
 (2) PARAGRAPH (A) OR (B).CLEAR FLOOR
 SPACE SHALL BE PROVIDED AT FIXTURES TO
 ALLOW A PERSON IN A WHEELCHAIR OR OTHER
 MOBILITY AID USE OF THE FIXTURES.CLEAR
 FLOOR SPACE SHALL BE SHOWN ON THE PLANS
 AND DESIGNATE WHICH OPTION OF REQ.#7
 (A OR B)IS BEING USED.
  
 DRY VENT NOT PERMITTED ON WASTE STACK
 PER SPC SEC.901.2.(BASE OF STACK SHALL
 BE WASHED.

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***