| Plan Review Stops For Permit 99121287 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2000-03-20 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-03-20 |
Time |
07:49 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-03-20 |
Time |
07:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-02-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-02-05 |
Time |
11:02 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-02-05 |
Time |
11:02 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE: NEED TO SUBMIT AIC RATING OF | | | EQUIPMENT MAINS. AIC RATING OF MAINS | | | NEED TO RATED FOR THE AVAILABLE FAULT | | | CURRENT. AIC RATING CAN BE FIGURED FROM | | | FAULT CURRENT CALCULATIONS. AS PER ARTS; | | | 110-9/110-10 AND 215-5 OF THE NEC. | | | | | | 2)NOTE: MISSING OUTLET IN HALL PER | | | 210-52H | | | | | | 3)NOTE:NEED TO HAVE THE DEDICATED BATH(S | | | CIRCUT LISTED ON PANEL SCHEDULE. CIRCUT | | | IS TO BE 20AMP AND #12 AWG. AS PER ART; | | | 210-52D OF THE NEC. | | | | | | NEED TO SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW AND APPROVAL. AIC RATING ARE | | | TO BE ON ALL PLANS!!! THIS IS SOMETHING | | | THAT HAS BEEN PREVIOUSLY REQ`STED.IF | | | THERE ARE ANY QUESTIONS PLEASE CALL 659- | | | -8096 EXT 8372. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2000-01-22 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2000-01-22 |
Time |
08:10 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
2000-01-22 |
Time |
08:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2000-06-01 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-06-01 |
Time |
06:35 |
Rev Time |
0.25 |
| Received By |
tlarge |
Date |
2000-06-01 |
Time |
06:35 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | REVISED SANITARY RISER. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2000-01-04 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-01-04 |
Time |
17:11 |
Rev Time |
0.50 |
| Received By |
tlarge |
Date |
2000-01-04 |
Time |
17:11 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | | | | **************PROVISO**************** | | | SANITARY RISER DOESN'T CORRELATE W/FLOOR | | | PLAN.SUBMIT REVISED SANITARY RISER PRIOR | | | TO ROUGH PLBG.INSPECTION. | | | | | | SUBMIT GAS RISER FOR REVIEW.COUNTYWIDE | | | AMENDMENTS TO SPC SEC.104.2.1. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
5 |
Status |
F |
Date |
2000-06-16 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2000-06-16 |
Time |
16:56 |
Rev Time |
0.50 |
| Received By |
jgomez |
Date |
2000-06-16 |
Time |
16:56 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | CHECKLIST: | | | 1-TRUSS DRAWINGS: | | | -TRUSS DRAWINGS TO HAVE EMBOSSED SEAL. | | | -ANY DOCUMENT SUBMITTED FOR PUBLIC | | | RECORDS TO BE SIGNED, SEALED AND DATED | | | WHEN THE DOCUMENT IS SEALED. | | | -UPDATE ALL GENERAL DETAILS ACCORDING | | | SBC 1997 OR ASCE 7-95. | | | -WHY ARE SOME DETAILS WITH DIFFERENT | | | ENGINEER'S SEALS. | | | 2-PROVIDE COMPLETE FORM FOR SITE | | | SPECIFIC PRODUCT APPROVAL FOR SLIDING | | | GLASS DOORS WITH TRANSOM ABOVE UNIT. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
4 |
Status |
F |
Date |
2000-04-21 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2000-04-21 |
Time |
10:50 |
Rev Time |
1.00 |
| Received By |
jgomez |
Date |
2000-04-21 |
Time |
10:44 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | CHECKLIST: | | | | | | | | | 1-TRUSS DRAWINGS: | | | -NEED EMBOSSED SEAL. | | | -CLARIFY WHY THERE ARE TWO DIFFERENT | | | DATES WRITTEN IN THE TRUSS DESIGN | | | CERTIFICATION FOR BUILDING CODE | | | COMPLIANCE FORM. | | | -NEED ADDRESS OF ENGINEER. | | | -NEED TO FILL IN THE PROJECT NAME AND | | | ADDRESS ON TOP OF FORM ON PAGE ONE AND | | | AT THE BOTTOM OF PAGE TWO OF THE TRUSS | | | DESIGN CERTIFICATION. | | | -TRUSS LAYOUT NEED EMBOSSED SEAL. | | | 2-DESIGN CERTIFICATION FOR BUILDING CODE | | | COMPLIANCE IS SIGNED AND SEALED BY DR. | | | KUONEN, P.E..IF THIS IS THE STRUCTURAL | | | ENGINEER OF RECORD, THEN, HE NEEDS TO | | | SIGN, SEAL AND DATE STRUCTURAL DWGS | | | AS WELL. | | | 3-PROVIDE PRODUCT APPROVAL FOR SLIDING | | | GLASS DOORS WITH TRANSOM ABOVE | | | ASSEMBLY. PRODUCT APPROVAL SUBMITTED | | | IS GOOD FOR SLIDING GLASS DOORS ONLY | | | WITHOUT THE TRANSOM ABOVE. | | | | | | | | | NOTE: | | | | | | PLEASE NOTE THAT MOST OF MY COMMENTS ARE | | | FOR ITEMS THAT ARE MENTIONED OVER AND | | | OVER. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
3 |
Status |
F |
Date |
2000-04-08 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2000-04-08 |
Time |
17:45 |
Rev Time |
0.25 |
| Received By |
jgomez |
Date |
2000-04-08 |
Time |
17:45 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | SLIDING GLASS DOORS WITH TRANSOM ABOVE | | | ASSEMBLY: | | | -PROVIDE COMPLETE SITE SPECIFIC | | | ENGINEERING ANALYSIS FOR THE TOTAL | | | ASSEMBLY. BE SPECIFIC ABOUT DESIGN | | | PRESSURES CALCULATIONS. WHAT BUILDING | | | CODE, PROVIDE COMPLETE SPECIFICATIONS | | | FOR ALL CONNECTIONS. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2000-03-19 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2000-03-19 |
Time |
13:56 |
Rev Time |
1.00 |
| Received By |
jgomez |
Date |
2000-03-19 |
Time |
13:56 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | APPROVED WITH PROVISO: | | | 1-TRUSS DRAWINGS TO BE DESIGNED AS PER | | | SBC 1997 OR ASCE 7-95. | | | NOTE: IT MUST BE CLEARLY INDICATED | | | IN THE DESIGN CRITERIA. | | | 2-DESIGN CERTIFICATION FOR BUILDING | | | CODE COMPLIANCE FORM WAS NOT REVISED. | | | RE-SUBMIT. | | | 3-PROVIDE PRODUCT APPROVAL FOR ENTRY | | | DOORS WITH SIDELITES ASSEMBLY. | | | SLIDING GLASS DOORS PRODUCT APPROVAL | | | IS GOOD FOR DOORS WITHOUT THE TRANSOM | | | ABOVE. PROVIDE PRODUCT APPROVAL | | | COMPLETE ASSEMBLY OR SITE SPECIFIC | | | ENGINEERING, SIGNE AND SEALED. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2000-02-07 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2000-02-07 |
Time |
17:22 |
Rev Time |
2.50 |
| Received By |
jgomez |
Date |
2000-02-07 |
Time |
17:22 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | APPROVED WITH PROVISO: | | | 1-PROVIDE EXTERIOR ELEVATIONS FOR MODEL | | | WITH 4 BEDROOM OPTION. | | | 2-TRUSS LAYOUT DOESN'T INCLUDE THE | | | ADDITIONAL BEDROOM OPTION. | | | -UPDATE ENGINEERED TRUSS DRAWINGS. | | | CLEARLY SPECIFY THE DESIGN CRITERIA | | | USED IS SBC 1997 OR ASCE 7-95. | | | 3-PROVIDE PRODUCT APPROVAL FOR ENTRY | | | DOORS WITH SIDELITES ASSEMBLY, SLIDING | | | GLASS DOORS WITH TRANSOM ABOVE | | | ASSEMBLY, ROUND WINDOWS. | | | 4-SEE COMMENTS ON PLANS AND REVISE/ | | | UPDATE ALL INFORMATION AS REQUIRED. | | | 5-FAMILY ROOM NEED TWO CEILINGS FANS | | | (48" EACH MINIMUM). TABLE 6-6 FLORIDA | | | ENERGY CODE, 1997 EDITION. | | | 6-SPECIFY THE DESIGN PRESSURES AT ALL | | | EXTERIOR OPENINGS. | | | 7-PROVIDE COMPLETE STORM PANELS INFO | | | UNDER A SEPARATE PERMIT. | | | 8-ENGINEERED TRUSS DRAWINGS: | | | -THERE IS ONLY ONE MEAN ROOF HEIGHT FOR | | | EACH BUILDING. REVISE AS REQUIRED. | | | -UPDATE DESIGN CRITERIA INFORMATION. | | | SPECIFY THE YEAR OF SBC. (1997). | | | -CLARIFY WHY ARE THE DESIGN LOADS FOR | | | TRUSSES D4, D3 AND CJ1 DIFFERENT THAN | | | THE REST OF THEM. (47 PSF TOTAL,RATHER | | | THAN 55 PSF). | | | -ENGINEER MECHANICAL SIGNATURE IS NOT | | | ALLOWED. ONLY WET SIGNATURE. | | | 9-REVISE DESIGN CERTIFICATION FOR | | | BUILDING CODE COMPLIANCE. MEAN ROOF | | | HEIGHT IS 19'8" PLUS OR MINUS. SEE | | | TABLE 1606.2A SBC 1997 FOR THE CORRECT | | | VELOCITY PRESSURE. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
1999-12-27 |
|
|
Cont ID |
|
| Sent By |
gjoyce |
Date |
1999-12-27 |
Time |
09:09 |
Rev Time |
0.50 |
| Received By |
gjoyce |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|