Plan Review Details - Permit 99121287
Plan Review Stops For Permit 99121287
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-03-20 Cont ID  
Sent By dpalmer Date 2000-03-20 Time 07:49 Rev Time 0.00
Received By dpalmer Date 2000-03-20 Time 07:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-02-05 Cont ID  
Sent By dpalmer Date 2000-02-05 Time 11:02 Rev Time 0.00
Received By dpalmer Date 2000-02-05 Time 11:02 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE: NEED TO SUBMIT AIC RATING OF
 EQUIPMENT MAINS. AIC RATING OF MAINS
 NEED TO RATED FOR THE AVAILABLE FAULT
 CURRENT. AIC RATING CAN BE FIGURED FROM
 FAULT CURRENT CALCULATIONS. AS PER ARTS;
 110-9/110-10 AND 215-5 OF THE NEC.
  
 2)NOTE: MISSING OUTLET IN HALL PER
 210-52H
  
 3)NOTE:NEED TO HAVE THE DEDICATED BATH(S
 CIRCUT LISTED ON PANEL SCHEDULE. CIRCUT
 IS TO BE 20AMP AND #12 AWG. AS PER ART;
 210-52D OF THE NEC.
  
 NEED TO SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW AND APPROVAL. AIC RATING ARE
 TO BE ON ALL PLANS!!! THIS IS SOMETHING
 THAT HAS BEEN PREVIOUSLY REQ`STED.IF
 THERE ARE ANY QUESTIONS PLEASE CALL 659-
 -8096 EXT 8372.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-01-22 Cont ID  
Sent By jleech Date 2000-01-22 Time 08:10 Rev Time 0.50
Received By jleech Date 2000-01-22 Time 08:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-06-01 Cont ID  
Sent By tlarge Date 2000-06-01 Time 06:35 Rev Time 0.25
Received By tlarge Date 2000-06-01 Time 06:35 Sent To  
Notes
2001-01-08 00:00:00REVISED SANITARY RISER.

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-01-04 Cont ID  
Sent By tlarge Date 2000-01-04 Time 17:11 Rev Time 0.50
Received By tlarge Date 2000-01-04 Time 17:11 Sent To  
Notes
2001-01-08 00:00:00 
 **************PROVISO****************
 SANITARY RISER DOESN'T CORRELATE W/FLOOR
 PLAN.SUBMIT REVISED SANITARY RISER PRIOR
 TO ROUGH PLBG.INSPECTION.
  
 SUBMIT GAS RISER FOR REVIEW.COUNTYWIDE
 AMENDMENTS TO SPC SEC.104.2.1.

Review Stop R ROOF PLAN REVIEW
Rev No 5 Status F Date 2000-06-16 Cont ID  
Sent By jgomez Date 2000-06-16 Time 16:56 Rev Time 0.50
Received By jgomez Date 2000-06-16 Time 16:56 Sent To  
Notes
2001-01-08 00:00:00CHECKLIST:
 1-TRUSS DRAWINGS:
 -TRUSS DRAWINGS TO HAVE EMBOSSED SEAL.
 -ANY DOCUMENT SUBMITTED FOR PUBLIC
 RECORDS TO BE SIGNED, SEALED AND DATED
 WHEN THE DOCUMENT IS SEALED.
 -UPDATE ALL GENERAL DETAILS ACCORDING
 SBC 1997 OR ASCE 7-95.
 -WHY ARE SOME DETAILS WITH DIFFERENT
 ENGINEER'S SEALS.
 2-PROVIDE COMPLETE FORM FOR SITE
 SPECIFIC PRODUCT APPROVAL FOR SLIDING
 GLASS DOORS WITH TRANSOM ABOVE UNIT.

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status F Date 2000-04-21 Cont ID  
Sent By jgomez Date 2000-04-21 Time 10:50 Rev Time 1.00
Received By jgomez Date 2000-04-21 Time 10:44 Sent To  
Notes
2001-01-08 00:00:00CHECKLIST:
  
  
 1-TRUSS DRAWINGS:
 -NEED EMBOSSED SEAL.
 -CLARIFY WHY THERE ARE TWO DIFFERENT
 DATES WRITTEN IN THE TRUSS DESIGN
 CERTIFICATION FOR BUILDING CODE
 COMPLIANCE FORM.
 -NEED ADDRESS OF ENGINEER.
 -NEED TO FILL IN THE PROJECT NAME AND
 ADDRESS ON TOP OF FORM ON PAGE ONE AND
 AT THE BOTTOM OF PAGE TWO OF THE TRUSS
 DESIGN CERTIFICATION.
 -TRUSS LAYOUT NEED EMBOSSED SEAL.
 2-DESIGN CERTIFICATION FOR BUILDING CODE
 COMPLIANCE IS SIGNED AND SEALED BY DR.
 KUONEN, P.E..IF THIS IS THE STRUCTURAL
 ENGINEER OF RECORD, THEN, HE NEEDS TO
 SIGN, SEAL AND DATE STRUCTURAL DWGS
 AS WELL.
 3-PROVIDE PRODUCT APPROVAL FOR SLIDING
 GLASS DOORS WITH TRANSOM ABOVE
 ASSEMBLY. PRODUCT APPROVAL SUBMITTED
 IS GOOD FOR SLIDING GLASS DOORS ONLY
 WITHOUT THE TRANSOM ABOVE.
  
  
 NOTE:
  
 PLEASE NOTE THAT MOST OF MY COMMENTS ARE
 FOR ITEMS THAT ARE MENTIONED OVER AND
 OVER.

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2000-04-08 Cont ID  
Sent By jgomez Date 2000-04-08 Time 17:45 Rev Time 0.25
Received By jgomez Date 2000-04-08 Time 17:45 Sent To  
Notes
2001-01-08 00:00:00SLIDING GLASS DOORS WITH TRANSOM ABOVE
 ASSEMBLY:
 -PROVIDE COMPLETE SITE SPECIFIC
 ENGINEERING ANALYSIS FOR THE TOTAL
 ASSEMBLY. BE SPECIFIC ABOUT DESIGN
 PRESSURES CALCULATIONS. WHAT BUILDING
 CODE, PROVIDE COMPLETE SPECIFICATIONS
 FOR ALL CONNECTIONS.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2000-03-19 Cont ID  
Sent By jgomez Date 2000-03-19 Time 13:56 Rev Time 1.00
Received By jgomez Date 2000-03-19 Time 13:56 Sent To  
Notes
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-TRUSS DRAWINGS TO BE DESIGNED AS PER
 SBC 1997 OR ASCE 7-95.
 NOTE: IT MUST BE CLEARLY INDICATED
 IN THE DESIGN CRITERIA.
 2-DESIGN CERTIFICATION FOR BUILDING
 CODE COMPLIANCE FORM WAS NOT REVISED.
 RE-SUBMIT.
 3-PROVIDE PRODUCT APPROVAL FOR ENTRY
 DOORS WITH SIDELITES ASSEMBLY.
 SLIDING GLASS DOORS PRODUCT APPROVAL
 IS GOOD FOR DOORS WITHOUT THE TRANSOM
 ABOVE. PROVIDE PRODUCT APPROVAL
 COMPLETE ASSEMBLY OR SITE SPECIFIC
 ENGINEERING, SIGNE AND SEALED.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2000-02-07 Cont ID  
Sent By jgomez Date 2000-02-07 Time 17:22 Rev Time 2.50
Received By jgomez Date 2000-02-07 Time 17:22 Sent To  
Notes
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-PROVIDE EXTERIOR ELEVATIONS FOR MODEL
 WITH 4 BEDROOM OPTION.
 2-TRUSS LAYOUT DOESN'T INCLUDE THE
 ADDITIONAL BEDROOM OPTION.
 -UPDATE ENGINEERED TRUSS DRAWINGS.
 CLEARLY SPECIFY THE DESIGN CRITERIA
 USED IS SBC 1997 OR ASCE 7-95.
 3-PROVIDE PRODUCT APPROVAL FOR ENTRY
 DOORS WITH SIDELITES ASSEMBLY, SLIDING
 GLASS DOORS WITH TRANSOM ABOVE
 ASSEMBLY, ROUND WINDOWS.
 4-SEE COMMENTS ON PLANS AND REVISE/
 UPDATE ALL INFORMATION AS REQUIRED.
 5-FAMILY ROOM NEED TWO CEILINGS FANS
 (48" EACH MINIMUM). TABLE 6-6 FLORIDA
 ENERGY CODE, 1997 EDITION.
 6-SPECIFY THE DESIGN PRESSURES AT ALL
 EXTERIOR OPENINGS.
 7-PROVIDE COMPLETE STORM PANELS INFO
 UNDER A SEPARATE PERMIT.
 8-ENGINEERED TRUSS DRAWINGS:
 -THERE IS ONLY ONE MEAN ROOF HEIGHT FOR
 EACH BUILDING. REVISE AS REQUIRED.
 -UPDATE DESIGN CRITERIA INFORMATION.
 SPECIFY THE YEAR OF SBC. (1997).
 -CLARIFY WHY ARE THE DESIGN LOADS FOR
 TRUSSES D4, D3 AND CJ1 DIFFERENT THAN
 THE REST OF THEM. (47 PSF TOTAL,RATHER
 THAN 55 PSF).
 -ENGINEER MECHANICAL SIGNATURE IS NOT
 ALLOWED. ONLY WET SIGNATURE.
 9-REVISE DESIGN CERTIFICATION FOR
 BUILDING CODE COMPLIANCE. MEAN ROOF
 HEIGHT IS 19'8" PLUS OR MINUS. SEE
 TABLE 1606.2A SBC 1997 FOR THE CORRECT
 VELOCITY PRESSURE.

Review Stop Z ZONING
Rev No 1 Status P Date 1999-12-27 Cont ID  
Sent By gjoyce Date 1999-12-27 Time 09:09 Rev Time 0.50
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***