Plan Review Details - Permit 99121238
Plan Review Stops For Permit 99121238
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-03-17 Cont ID  
Sent By bstaples Date 2000-03-17 Time 09:08 Rev Time 3.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00REVISIONS REVIEWED 3/17/00 WRS

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-01-26 Cont ID  
Sent By bstaples Date 2000-01-26 Time 15:27 Rev Time 5.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:001. SHEET A-1 NOTE #4 SHOWS TYPE VI CONST
 TYPE VI CONST. NOT ALLOWED IN FIRST FIRE
 DISTRICT SEE APPENDIX F, 1997 SBC.
 2. REVISE SHEET A-1 TO REFLECT OPEANINGS
 SIZE ALLOWED BASED ON TYPE OF
 CONSTRUCTION USED SEE TABLE 600, 1997SBC
 3. REVISE EXTERIOR WALL DESIGN FOR FIRE
 DESTRICT BASED ON FIRE DESTRICT AND
 TABLE 600, 1997 SBC.
 4. SHEET A-24 NOTES REFER TO SHEET A-27
 SHEET NOT IN PLANS.
 5. SUBMIT TRUSS DRAWINGS FOR REVIEW.
 6. PROVIDE PRODUCT APPROVAL INFORMATION
 FOR WINDOWS AND DOORS AS PER SHEET A-33.
 7. CANOPIES, FENCES, GATES, SIGNS AND
 FOUNTIANS REQUIRE SEPERATE PERMITS SEE
 SHEET A-41.
 8. SHEET A-28 MAILBOXES UNDER STAIRS
 COMPLY WITH 1006.1.4, 1997 SBC.
 9. SHEET A-29 SECTION A ETC. INDICATES
 WOOD FRAME ROOF SYSTEM ENERGY SHEET
 INDICATES CONCRETE ROOF WITH R10
 INSULATION.
 10. SHEET A-32 INDICATES IN NOTES THAT
 MISSLE IMPACT NOTES ARE ON SHEET A-27.
 A-27 DOES NOT CONTAIN THE INFORMATION
 PROPER REFRENCE IS A-33.
 11. SHEET A-32 DOOR SCHEDULE DOORS DO
 NOT MATCH ELEVATIONS SEE DOOR #7.
 12. SHEET A-33 CODE REFERENCE FOR MISSLE
 IMPACT AND WIND DESIGN IS NOT CORRECT
 PLAN INDICATES 1994 SBC SHOULD BE
 1997 SBC.
 13. SHEET A-35 REFERENCES THE WRONG
 EDITION OF THE FAIR HOUSING ACT.
 14. SHEET S-9 SECTION 7 INDICATES A
 1 1/2" OFFSET, SHEET A-32 SECTION 5
 INDICATES 1/2" AND COMPLIES WITH FAIR
 HOUSING ACT. (DOORS)
 15. SHEET S-12 DOES NOT INDICATE CODE
 EDITION (1997) OR METHOUD OF COMPLIANCE
 1606 OR ASCE 7-95 FOR BUILDING DESIGN.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-01-14 Cont ID  
Sent By jleahy Date 2000-01-14 Time 11:59 Rev Time 2.00
Received By jleahy Date 2000-01-14 Time 11:59 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-01-18 Cont ID  
Sent By bstaples Date 2000-01-18 Time 16:39 Rev Time 1.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00SEE PROVISO ON PLANS

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-12-28 Cont ID  
Sent By jleech Date 2000-12-28 Time 14:00 Rev Time 0.25
Received By jleech Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-03-21 Cont ID  
Sent By ndenmark Date 2000-03-21 Time 06:58 Rev Time 0.50
Received By ndenmark Date 2000-03-21 Time 06:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-03-21 Cont ID  
Sent By ndenmark Date 2000-01-27 Time 07:08 Rev Time 1.00
Received By ndenmark Date 2000-01-27 Time 07:08 Sent To  
Notes
2001-01-08 00:00:00CORRECTED BY REVISIONS 3/21/00**********
 1) SHT A-31 DETAIL 3 DYER VENT AND BATH
 EXHAUST DUCT TO BE ENCLOSED IN SHAFT TO
 BOTTOM OF ROOF STRUCTUR
 2) SHT A-31 DETAIL 2 DRYER VENT TO BE
 MIN. 4" NOT 3", DRYER VENT TO RUN FULL
 LENGTH OUT OF BUILDING
 3) SHT A-31 DETAIL 4 INDICATE WHICH SIZE
 CAP TO BE USED- 4" OR 2 1/2" NOTE: FLEX
 METAL DUCT NOT ALLOWED BY CODE
 4) CONDENSING UNIT SERVICE TO BE PER NEC
 AND 1997 SMC 304.7.2 WHICHEVER IS GREATE
 DISCONNECT TO BE WITHIN 6' OF THE SERVIC
 SIDE OF THE EQUIPMENT AND A 115V GFCI
 OUTLET REQUIRED
 5) SHT AC 5 OVERFLOW PROTECTION REQUIRED
 FOR AHU'S PER 1997 SMC 304.8.6

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-04-03 Cont ID  
Sent By tlarge Date 2000-04-03 Time 06:02 Rev Time 1.25
Received By tlarge Date 2000-04-03 Time 06:00 Sent To  
Notes
2001-01-08 00:00:00********************PROVISO*************
 SHOWERS IN COVERED UNITS SHALL BE
 SHANGED TO COMPLY W/FEDERAL FAIR HOUSING
 ACT 24 CFR 100.205.(SEE SIGNED AND
 SEALED LETTER FROM ARCHITECTURAL FIRM
 ATTACHED TO PLANS.)
  
 A PERMIT FOR THE WATER MAIN IS REQD.FROM
 THE DEPT.OF ENVIRONMENTAL PROTECTION
 AND PALM BEACH COUNTY HEALTH DEPT.SUBMIT
 COPIES OF APPROVALS FOR REVIEW.COUNTY-
 WIDE AMENDMENTS TO SPC SEC.101.4.7.

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-03-12 Cont ID  
Sent By tlarge Date 2000-03-12 Time 09:13 Rev Time 1.25
Received By tlarge Date 2000-03-12 Time 09:13 Sent To  
Notes
2001-01-08 00:00:00ALL BATHROOMS IN THECOVERED DWELL-
 ING UNITS SHALL COMPLY W/FEDERAL FAIR
 HOUSING ACT 24 CFR 100.205 (C)(3)(IV)
 REQ.#7(2),PARAGRAPH (A) OR (B).CLEAR
 FLOOR SPACE SHALL BE CLEARLY SHOWN ON
 THE PLANS AND DESIGNATE WHICH DESIGN
 SPECIFICATION ("A" OR "B") OF THE FAIR
 HOUSING ACT IS BEING USED.
 **NOTE:IF YOU CHOOSE SPECIFICATION "A"IT
 APPLIES TO ALL BATHROOMS AND CLEAR FLOOR
 SPACE IS REQD.AT THE SHOWER.IN
 SPECIFICATION "B"BATHROOMS,ONLY ONE
 BATHING FIXTURE SHALL BE PROVIDED W/THE
 REQUIRED CLEAR FLOOR SPACE.A 30"X 48"
 CLEAR FLOOR SPACE IS REQD.ADJACENT TO
 THE BATHTUB.AS DESIGNED THE SHOWERS IN
 UNITS "B" AND THE BATHTUBS IN UNITS"C"
 DO NOT COMPLY.
  
 A PERMIT FOR THE WATER MAIN IS REQD.FROM
 THE DEPT.OF ENVIRONMENTAL PROTECTION AND
 P.B.COUNTY HEALTH DEPT.SUBMIT COPIES OF
 APPROVALS.COUNTYWIDE AMENDMENTS TO SPC
 SEC.101.4.7.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-01-27 Cont ID  
Sent By tlarge Date 2000-01-14 Time 15:31 Rev Time 4.50
Received By tlarge Date 2000-01-14 Time 15:31 Sent To  
Notes
2001-01-08 00:00:00 
 CONDENSATE SYSTEM FOR MULTIPLE UNITS
 SHALL BE VENTED TO THE ATMOSPHERE PER
 COUNYUWIDE AMENDMENTS TO SPC SEC.804.3.
 (5).
  
 WATER RISER FOR UNIT "A"DOESN'T
 CORRELATE W/ARCH.FLOOR PLAN. COUNTYWIDE
 AMENDMENTS TO SPC SEC.104.2.1.
  
 SHT.A-35 NOTES THAT BATHROOMS WILL BE
 DESIGNED UNDER THE FEDERAL FAIR HOUSING
 ACT REQ.#7(2)(A).THIS SPECIFICATION
 APPLIES TO ALL BATHROOMS,AND ALL
 FIXTURES IN THOSE BATHROOMS MUST BE
 USABLE.CLEAR FLOOR SPACE FOR FIXTURES
 SHALL BE PROVIDED.UNITS "C" AND "D" DO
 NOT COMPLY FOR BATHROOMS WITH SHOWERS.
  
 A PERMIT FOR THE WATER MAIN IS REQD.FROM
 DEPT.OF ENVIRON.PROTECTION.SUBMIT COPY
 OF PERMIT FOR REVIEW.AN ADDITIONAL
 PERMIT MAY ALSO BE REQD.FROM P.B.COUNTY
 HEALTH DEPT.SUBMIT ALL REQD.APPROVALS.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-02-07 Cont ID  
Sent By bstaples Date 2000-01-25 Time 16:18 Rev Time 1.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00DENIED DENNIS CAMPBELL 1/25/2000
 APPROVED DENNIS CAMPBELL 2/7/00