Plan Review Details - Permit 99121189
Plan Review Stops For Permit 99121189
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-02-05 Cont ID  
Sent By dpalmer Date 2000-02-05 Time 10:44 Rev Time 0.00
Received By dpalmer Date 2000-02-05 Time 10:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2000-07-03 Cont ID  
Sent By cthirben Date 2000-07-03 Time 12:17 Rev Time 1.00
Received By cthirben Date 2000-07-03 Time 12:14 Sent To  
Notes
2001-01-08 00:00:00DENIED:
 NO MECHANICAL PLANS SUBMITTED FOR REVIEW

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2000-01-20 Cont ID  
Sent By cthirben Date 2000-01-20 Time 14:24 Rev Time 1.00
Received By cthirben Date 2000-01-20 Time 14:24 Sent To  
Notes
2001-01-08 00:00:00NO A/C PLANS SUBMITTED OWNER/BUILDER
 WILL SUBMIT ON A LATER DATE

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-01-08 Cont ID  
Sent By tlarge Date 2000-01-08 Time 15:17 Rev Time 0.33
Received By tlarge Date 2000-01-08 Time 15:17 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2000-04-21 Cont ID  
Sent By fknapp Date 2000-04-21 Time 12:37 Rev Time 2.00
Received By fknapp Date 2000-04-20 Time 11:51 Sent To  
Notes
2001-01-08 00:00:00****************DENIED******************
  
 SBC 104.2.2
  
 1)PROVIDE OWNER SIGNATURE ON BOTH ENERGY
 CALCULATIONS.
  
 2)PROVIDE ENGINEER APPROVAL OF PILINGS
 BEFORE ANY CONCRETE IS POURED.
  
 3)PROVIDE FLOOD ZONE ELEVATION
 CERTIFICATE.
  
 4)PROVIDE AC PLAN WITH MECHANICAL PERMIT
 APPLICATION.
  
 5)PROVIDE 2 CURRENT COPIES OF SBCCI OR
 METRO DADE PRODUCT APPROVALS WITH
 APPROVED DRAWINGS FOR:
 EXTERIOR DOORS AND WINDOWS
 ROOF COVERING
 STORM PANELS WITH INSTALLATION
 SCHEDULE AND KEY PLAN WITH SPECIFIC
 ANCHORS TO BE USED.
  
 6)PROVIDE SPECIFICATIONS FOR UL LISTED
 FIREPLACE.
  
 7)PROVIDE DETAILS OF SPIRAL STAIRS TO
 COMPLY WITH SBC 1007.8.2
  
 8)PROVIDE HANDRAILS AND GUARDRAILS TO
 COMPLY WITH SBC 1015
  
 9)PROVIDE SAFETY GLASS PER SBC 2405.2.1
  
 10)PROVIDE DETAILS OF ALL STRUCTUAL
 COMPONETS. MUST COMPLY WITH TBL 600,
 TYPE VI 1 HR PROTECTED.
  
 11)PROVIDE APPROVED ASSEMBLIES TO MEET
 FIRE RESISTANCE REQUIREMENTS SBC 701.5
  
 11)SHOW FINISH FLOOR ELEVATIONS RELATIVE
 TO NGVD.
  
 ******************NOTE******************
 ALL CHANGES ON PLANS MUST BE NOTED BY
 TRIANGLES OR CLOUDS.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-02-09 Cont ID  
Sent By fknapp Date 2000-02-09 Time 14:52 Rev Time 5.00
Received By fknapp Date 2000-02-09 Time 09:15 Sent To  
Notes
2001-01-08 00:00:00 
  
 ****************DENIED******************
  
 SBC 104.2.2
  
 1)PROVIDE OWNER SIGNATURE ON ENERGY
 CALCULATIONS.
  
 2)PROVIDE ENGINEER APPROVAL OF PILINGS
 BEFORE ANY CONCRETE IS POURED.
  
 3)PROVIDE FLOOD ZONE ELEVATION
 CERTIFICATE.
  
 4)PROVIDE AC PLAN WITH MECHANICAL PERMIT
 APPLICATION.
  
 5)PROVIDE 2 CURRENT COPIES OF PRODUCT
 APPROVALS FOR:
 EXTERIOR DOORS AND WINDOWS
 STORM PANELS
 ROOF COVERING
 FIREPLACE UL LISTED
  
 6)BUILDING SHOWN IS TYPE VI CONSTRUCTION
 AND DOES NOT COMPLY WITH SBC TABLE 500
 REVISE DESIGN TO COMPLY.
  
 7)PROVIDE CONSTRUCTION DETAILS OF FIRE
 RATED ASSEMBLY FOR ELEVATOR HOISTWAY
 SBC 705.1.2
  
 8)PROVIDE DETAILS OF SPIRAL STAIRS TO
 COMPLY WITH SBC 1007.8.2
  
 9)PROVIDE ATTIC ACCESS PER SBC 2309.6
  
 10)PROVIDE GUARDRAILS TO COMPLY WITH
 SBC 1015
  
 11)PROVIDE SAFETY GLASS PER SBC 2405.2.1
  
 12)PROVIDE CONSTRUCTION DETAILS OF FIRE
 RATED ASSEMBLY FOR LAUNDRY CHUTE
 SBC 705.1.2
  
 **************NOTE**********************
 BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH CO.,THE PERMIT PLANS STAMPED BY
 THEM AND THE RECIEPT ATTACHED TO THE
 PERMIT APPLICATION.

Review Stop Z ZONING
Rev No 3 Status F Date 2000-07-11 Cont ID  
Sent By gjoyce Date 2000-07-11 Time 14:41 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
2001-01-08 00:00:00NO SURVEY OR SITE PLAN

Review Stop Z ZONING
Rev No 2 Status P Date 1999-12-30 Cont ID  
Sent By gjoyce Date 1999-12-30 Time 11:29 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 1999-12-29 Cont ID  
Sent By gjoyce Date 1999-12-29 Time 08:06 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
2001-01-08 00:00:00NEEDS SITE PLAN