Plan Review Details - Permit 99121095
Plan Review Stops For Permit 99121095
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-02-28 Cont ID  
Sent By dpalmer Date 2000-02-28 Time 16:51 Rev Time 0.00
Received By dpalmer Date 2000-02-28 Time 16:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-01-22 Cont ID  
Sent By dpalmer Date 2000-01-08 Time 13:36 Rev Time 0.00
Received By dpalmer Date 2000-01-08 Time 13:36 Sent To  
Notes
2001-01-08 00:00:00***************UNSAT*****************
  
 1)NOTE:PLEASE LABEL ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE GFI/GFI PROTECTED.
 REQ`D BY 210-8-A-6
  
 2)NOTE:PLEASE SHOW MEANS OF DISC. FOR
 A/C COND. UNIT. PER 440-11
  
 3)NOTE: SMOKE DETECTORS ARE REQ`D INSIDE
 AND OUTSIDE ALL SLEEPING ROOMS.IF ROOM
 ON SECOND FLOOR HAS CLOSET INSTALLED
 THEN A SMOKE DETECTOR WILL BE REQ`D.
 THEY ARE REQ`D BY 1993/1996 NFPA-72
 2-2.1.1.1
  
 4)NOTE: NEED TO SHOW DEDICATED BATH(S)
 CIRCUT(S) ON PANEL SCHEDULE. THEY MUST
 BE 20 AMP #12 AWG. THIS IS REQ`D BY
 NEC.ART;210-52D/215-5
  
 5)NOTE: NEED TO SUBMIT AIC RATING OF
 EQUIPMENT MAINS/PANEL. AIC RATING IS
 FIGURED FROM FAULT CURRENT CALCULATIONS.
 THIS IS REQ`D BY ARTS:110-9/230-65/215-5
  
 6)NOTE:PLEASE SIZE AND SHOW EQUIPMENT
 GROUNDING CONDUCTOR AS REQ`D BY THE
 FOLLOWING ARTS:250-92/250-95 AND 215-5
  
 PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW AND APPROVAL BEFORE FIRST
 ROUGH ELECTRICAL INSPECTION IS CALLED IN
 IF THERE ARE ANY QUESTIONS,,PLEASE CALL
 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-01-05 Cont ID  
Sent By jleech Date 2000-01-05 Time 08:33 Rev Time 0.50
Received By jleech Date 2000-01-05 Time 08:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-02-29 Cont ID  
Sent By tlarge Date 2000-02-29 Time 17:16 Rev Time 0.50
Received By tlarge Date 2000-02-29 Time 17:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2000-02-29 Cont ID  
Sent By tlarge Date 2000-02-29 Time 06:42 Rev Time 0.33
Received By tlarge Date 2000-02-29 Time 06:42 Sent To  
Notes
2001-01-08 00:00:00SANITARY RISER SHALL CORRELATE W/FLOOR
 PLAN.COUNTYWIDE AMENDMENTS TO SPC SEC.
 104.2.1.
  
 MAIN VENT THRU ROOF REQD.PER SPC SEC.
 904.3.1.
  
 WATER CLOSETS AND FIXTURE BRANCHES NOT
 PERMITTED ON WET VENTS PER COUNTYWIDE
 AMENDMENTS TO SPC SEC.911.1.1.
  
 FIXTURES DOWNSTREAM OF WATER CLOSETS
 SHALL BE VENTED PER SPC 913.2.

Review Stop P PLUMBING
Rev No 1 Status N Date 2000-02-29 Cont ID  
Sent By tlarge Date 2000-01-04 Time 08:49 Rev Time 0.50
Received By tlarge Date 2000-01-04 Time 08:49 Sent To  
Notes
2001-01-08 00:00:00LOCATION OF FIXTURES ON SANITARY RISER
 DIAGRAM SHALL MATCH FLOOR PLAN PER
 COUNTYWIDE AMENDMENTS TO STD.PLBG.CODE
 SEC.104.2.1.(SANITARY RISER SHALL SHOW
 ALL OPTIONS.)

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2000-03-01 Cont ID  
Sent By jgomez Date 2000-03-01 Time 14:49 Rev Time 2.50
Received By jgomez Date 2000-03-01 Time 14:49 Sent To  
Notes
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-FLOOD ZONE A8. PROVIDE ELEVATION
 CERTIFICATE.
 2-REVISE/UPDATE ALL DRAWINGS AS REQUIRED
 SEE PLANS FOR COMMENTS.
 3-ENGINEER TO SIGN, SEAL AND DATE THE
 SOIL TEST REPORT.
 4-STORM PANELS:
 -REVISE/UPDATE INSTALLATION SCHEDULE
 AND KEY PLANS TO MATCH FLOOR PLANS.
 NOTE: USE CITY SAMPLE AND COMPLETE ALL
 THE INFORMATION.
 5-PROVIDE PRODUCT APPROVAL FOR ENTRY
 OUTSWING DOOR AND FOR GARAGE DOOR.
 NOTE: CLEARLY SPECIFY THE FASTENERS TO
 BE USED ACCORDING TO THE PRODUCT
 APPROVAL AND DOOR FRAME DETAIL THAT
 WAS SPECIFIED IN ACHITECTURAL DWGS.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-01-29 Cont ID  
Sent By jgomez Date 2000-01-29 Time 16:16 Rev Time 2.50
Received By jgomez Date 2000-01-29 Time 16:16 Sent To  
Notes
2001-01-08 00:00:00CHECKLIST:
 1-PAY THE IMPACT FEES.
 2-PROVIDE COMPLETE HANGING DETAILS FOR
 AHU SUSPENDED FROM FLOOR TRUSSES.
 3-IN ORDER TO FACILITATE THE REVIEW
 PROCESS, PLEASE SPECIFY THE DESIRED
 OPTIONS FOR THIS HOUSE AND CROSS OUT
 THE OTHER OPTIONS.
 4-FLOOD ZONE "A8" AN ELEVATION
 CERTIFICATE WILL BE REQUIRED.
 5-EGRESS WINDOWS AT SECOND FLOOR TO
 COMPLY WITH THE MINIMUM REQUIREMENTS
 OF SECTION 1005.4.4 SBC 1997. REVISE
 SIZE OF WINDOWS AS REQUIRED.
 6-PROVIDE ATTIC ACCESS AT GARAGE AREA.
 -REVISE SIZE OF ATTIC ACCESS SPECIFIED
 AT MASTER BEDROOM CLOSET.
 7-PROVIDE FIRE CUTS AT TRUSSES TO BE
 SUPPORTED ON MASONRY WALL. SECTION
 2305.4 SBC 1997 OR PROVIDE ANOTHER
 WAY TO COMPLY WITH THIS SECTION.
 NOTE: IF SOLUTION IS TO PROVIDE THE
 FIRE CUT, THEN FLOOR TRUSSES NEED TO
 BE REVISED ACCORDINGLY.
 8-REVISE/UPDATE ALL DRAWINGS. SEE
 COMMENTS ON PLANS.
 9-FOOTING F2 TO BE 16"
 SECTION 1804.1.3 SBC 1997.
 10-PROVIDE PRODUCT APPROVAL FOR ENTRY
 DOOR WITH SIDELITES ASSEMBLY, GARAGE
 DOOR
 11-STORM PANELS:
 -DRAWINGS DON'T MATCH PRODUCT APPROVAL.
 -UPDATE/REVISE INSTALLATION SCHEDULE
 AND KEY PLAN. USE CITY SAMPLE ATTACHED
 -SPECIFY ANCHOR SPACING AS REQUIRED
 FOR MASONRY AND WOOD CONSTRUCTION.
 12-COMPLETELY SPECIFY CEILING
 CONSTRUCTION AT FRONT AND BACK PORCH.
 SECTION 104.2 CITY AMENDMENTS.

Review Stop Z ZONING
Rev No 1 Status P Date 1999-12-23 Cont ID  
Sent By gjoyce Date 1999-12-23 Time 08:54 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***