Plan Review Details - Permit 99121094
Plan Review Stops For Permit 99121094
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-03-01 Cont ID  
Sent By dpalmer Date 2000-03-01 Time 06:45 Rev Time 0.00
Received By dpalmer Date 2000-03-01 Time 06:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2000-02-28 Cont ID  
Sent By dpalmer Date 2000-02-28 Time 15:03 Rev Time 0.00
Received By dpalmer Date 2000-02-28 Time 15:03 Sent To  
Notes
2001-01-08 00:00:00SAME NOTES AS BEOFORE. ONLY TWO NOTES
 WERE ADDRESSED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-01-22 Cont ID  
Sent By dpalmer Date 2000-01-08 Time 12:55 Rev Time 0.00
Received By dpalmer Date 2000-01-08 Time 12:55 Sent To  
Notes
2001-01-08 00:00:00************UNSAT*******************
  
 1)NOTE: RISER DIAGRAM SHOWS MAIN DISC.
 PLANS DO NOT SHOW MAIN DISCONNECT NEXT
 TO METER.?? PLEASE CORRECT.215-5
  
 2)NOTE:PANEL SCHEDULE SHOWS 48 CIRCUT
 PANELBOARD. AS PER 384-15 NO MORE THAN
 42 CIRCUT PANEL ARE ALLOWED.
  
 3)NOTE: AS PER 210-52D/215-5 NEED TO
 SHOW DEDICATED BATH(S) CIRCUT REQ`D.NEED
 TO BE 20AMP #12 AWG.
  
 4)NOTE;AS REQ`D BY 210-8-A-6 ALL OUTLETS
 SERVING KITCHEN COUNTERSPACE ARE TO BE
 GFI/GFI PROTECTED.PLEASE SHOW.
  
 5)NOTE:NEED TO SUBMIT AIC RATING OF
 EQUIPMENT MAINS/BRKRS. AS REQ`D BY THE
 FOLLOWING ARTS:110-9/230-65/215-5
 AIC RATING IS FIGURED FROM FAULT CURRENT
 CALCULATIONS.
  
 6)NOTE: AS REQ`D BY 1993/1996 NFPA-72
 CHAPTER 2-2.1.1.1 SMOKE DETECTORS SHALL
 BE INSTALLED INSIDE AND OUTSIDE ALL
 SLEEPING ROOMS IN NEW DWELLINGS.
  
 PLEASE HAVE ALL THE ABOVE INFORAMTION
 SUBMITTED FOR REVIEW AND APPROVAL
 BEFORE FIRST ROUGH ELECTRIACL INSPECTION
 IS CALLED IN. IF THERE ARE ANY QUESTIONS
 CALL 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-07-21 Cont ID  
Sent By cthirben Date 2000-07-21 Time 07:20 Rev Time 1.00
Received By cthirben Date 2000-07-21 Time 07:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-05-09 Cont ID  
Sent By cthirben Date 2000-05-09 Time 13:12 Rev Time 1.00
Received By cthirben Date 2000-05-09 Time 13:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-12-27 Cont ID  
Sent By jleech Date 1999-12-27 Time 15:44 Rev Time 0.50
Received By jleech Date 1999-12-27 Time 15:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-03-01 Cont ID  
Sent By tlarge Date 2000-03-01 Time 06:56 Rev Time 0.33
Received By tlarge Date 2000-03-01 Time 06:56 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-12-27 Cont ID  
Sent By tlarge Date 1999-12-27 Time 07:43 Rev Time 0.50
Received By tlarge Date 1999-12-27 Time 07:43 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2000-03-01 Cont ID  
Sent By jgomez Date 2000-03-01 Time 08:48 Rev Time 2.00
Received By jgomez Date 2000-03-01 Time 08:48 Sent To  
Notes
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-FLOOD ZONE A8. PROVIDE ELEVATION
 CERTIFICATE.
 2-UPDATE/REVISE ALL DRAWINGS AS REQUIRED
 SEE PLANS FOR COMMENTS.
 3-ENGINEER TO SIGN, SEAL AND DATE SOIL
 TEST REPORT.
 4-STORM PANELS:
 -REVISE/UPDATE INSTALLATION SCHEDULE
 AND KEY PLAN TO MATCH FLOOR PLANS.
 NOTE: USE CITY SAMPLE INSTALLATION
 SCHEDULE, ATTACHED, AND FILL IN ALL
 THE INFORMATION.
 5-PROVIDE PRODUCT APPROVAL FOR ENTRY
 OUTSWING DOOR AND GARAGE DOOR.
 NOTE: CLEARLY SPECIFY THE FASTENERS
 TO BE USED ACCORDING TO THE PRODUCT
 APPROVAL AND DOOR FRAME DETAIL THAT
 WAS SPECIFIED IN DRAWING A6.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-01-29 Cont ID  
Sent By jgomez Date 2000-01-29 Time 16:14 Rev Time 2.50
Received By jgomez Date 2000-01-29 Time 16:14 Sent To  
Notes
2001-01-08 00:00:00CHECKLIST:
 1-PAY IMPACT FEES.
 2-UPDATE/REVISE ALL DRAWINGS. SEE
 COMMENTS ON PLANS.
 3-FLOOD ZONE A8. WILL NEED TO PROVIDE
 AN ELEVATION CERTIFICATE.
 4-ENGINEER TO SIGN, SEAL AND DATE THE
 SOIL TESTS REPORT.
 5-REVISE SIZE OF BEDROOM #2 WINDOW TO
 MEET THE EGRESS REQUIREMENTS. SEC
 1005.4.4 SBC 1997.
 6-STORM PANELS:
 -PRODUCT APPROVAL DOESN'T MATCH DWGS.
 -REVISE/UPDATE INSTALLATION SCHEDULE
 AND KEY PLAN TO MATCH FLOOR PLANS.
 COMPLETELY FILL THE INSTALLATION
 SCHEDULE AS PER CITY SAMPLE. ATTACHED.
 -NOTE: SPECIFY ANCHOR SPACING ACCORDING
 TO THE BUILDING CONSTRUCTION. THIS IS
 MASONRY CONSTRUCTION, NOT CONCRETE.
 HIGHLIGHT ALL MOUNTING CONDITIONS AND
 ANCHORS TO BE USED.
 7-PROVIDE COMPLETE BUCK DETAILS FOR
 EXTERIOR DOORS, WINDOWS AND GARAGE
 DOOR.
 8-PROVIDE PRODUCT APPROVAL FOR ENTRY
 DOOR WITH SIDELITES ASSEMBLY AND
 GARAGE DOOR.

Review Stop Z ZONING
Rev No 1 Status P Date 1999-12-23 Cont ID  
Sent By gjoyce Date 1999-12-23 Time 08:49 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***