Plan Review Details - Permit 99120815
Plan Review Stops For Permit 99120815
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2000-03-31 Cont ID  
Sent By lsmith Date 2000-03-31 Time 11:24 Rev Time 0.25
Received By lsmith Date   Time   Sent To  
Notes
2001-01-08 00:00:00PRODUCT APPROVALS STOREFRONT LS

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-03-15 Cont ID  
Sent By hpiskura Date 2000-03-06 Time 09:45 Rev Time 0.00
Received By sgraham Date   Time   Sent To Z
Notes
2001-01-08 00:00:00NEED FS DESIGN ON PLANS

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-03-15 Cont ID  
Sent By hpiskura Date 2000-02-24 Time 11:08 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2000-08-08 Cont ID  
Sent By dpalmer Date 2000-08-08 Time 07:56 Rev Time 0.00
Received By dpalmer Date 2000-08-08 Time 07:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-04-25 Cont ID  
Sent By dpalmer Date 2000-04-25 Time 14:25 Rev Time 0.00
Received By dpalmer Date 2000-04-25 Time 14:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2000-04-13 Cont ID  
Sent By dpalmer Date 2000-04-13 Time 17:02 Rev Time 0.00
Received By dpalmer Date 2000-04-13 Time 17:02 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT TWO COMPLETE SETS.
 THERE ARE PAGES MISSING FROM SET #1
  
 2)NOTE: ALSO, WHEN PLANS COME BACK THEY
 NEED TO BE SEEN BY FIRE ALSO. THEY DO
 HAVE FIRE ON THE ELECTRICAL SHEETS.
  
 PLEASE RE-SUB REVISIONS FOR REVIEW. IF
 THERE ARE ANY QUESTIONS PLEASE CALL.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-01-12 Cont ID  
Sent By jleahy Date 2000-01-12 Time 10:00 Rev Time 1.15
Received By jleahy Date 2000-01-12 Time 10:00 Sent To  
Notes
2001-01-08 00:00:00SHELL ONLY NO INTERIOR WORK

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2000-04-12 Cont ID  
Sent By mgonzale Date 2000-04-12 Time 15:23 Rev Time 1.00
Received By mgonzale Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLANS HAVE BEEN REVISED PER PROVISOS.

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2000-03-03 Cont ID  
Sent By hpiskura Date 2000-03-03 Time 16:41 Rev Time 0.50
Received By mgonzale Date   Time   Sent To  
Notes
2001-01-08 00:00:00 
 OK W/ PROVISOS ATTACHED TO PLANS PER
 RICHARD PITTMAN 3/3/00

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2000-03-06 Cont ID  
Sent By dlauderm Date 2000-03-02 Time 10:13 Rev Time 2.00
Received By mgonzale Date 2000-03-02 Time 10:12 Sent To  
Notes
2001-01-08 00:00:00 
 F. EVERY SIX MONTHS AFTER CONSTRUCTION A
 PE SHALL CERTIFY THAT THE PERMANENT
 POLLUTION PREVENTION STRUCTURES, DRY-WET
 WATER DETENTION FACILITIES, AND
 EXFILTRATION SYSTEMS ARE WORKING AS
 DESIGNED AND ARE IN GOOD OPERATING
 CONDITION. ALL CERTIFICATIONS MUST BE
 SUBMITTED TO:
 STORM WATER UTILITY ENGINEER
 CITY OF WEST PALM BEACH PUBLIC UTILITIES
 DEPARTMENT
 P.O. BOX 3366, WEST PALM BEACH, FL
 33402.
 THE CERTIFICATION MUST INCLUDE THE
 BUILDING PERMIT NUMBER, THE ADDRESS OF
 THE PROPERTY AND THE NAME OF THE
 ESTABLISHMENT/PROJECT CONSTRUCTED.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2000-03-06 Cont ID  
Sent By dlauderm Date 2000-03-02 Time 10:13 Rev Time 0.00
Received By mgonzale Date 2000-03-06 Time 14:04 Sent To  
Notes
2001-01-08 00:00:00FAILED.
 1. FIRE DEPT. APPROVED PLAN WITH HYDRANT
 ON SITE.IF IT IS INSTALLED THERE THEN
 IT NEEDS TO HAVE A 6" DOUBLE CHECK
 DETECTOR CHECK INSTALLED ON IT AS A
 PRIVATE FIRE LINE.
  
 I (DEAN LAUDERMILK) TALKED TO THE FIRE
 MARSHALL (RHETT TURNQUEST) AND HE AGREES
 THAT THE HYDRANT CAN BELONG TO THE CITY
 AND DOES NOT NEED A DETECTOR CHECK
 INSTALLED IF THE LOCATION IS MOVED SOUTH
 TO THE NORTH SIDE OF THE DRIVEWAY, BUT
 NO FURTHER THAN 150' FROM THE FDC (FIRE
 DEPT. CONNECTION) AND NOT IN THE WAY OF
 THE ENTRY SIDEWALK. THE HYDRANT SHOULD
 BE LOCATED IN THE EASEMENT. DECIDE WHICH
 WAY YOU WANT TO GO AND MAKE CORRECTIONS
 ON THE LNW PLAN.
  
 2. SHEET P2.1 DOES NOT MATCH 5 OF 8 BY
 LNW.THE SANITARY LATERAL IS 30' +-
 FROM WHERE THE SANITARY LINE EXITS THE
 BUILDING, AND THE 2" WATER SERVICE IS
 MORE THAN 80' FROM WHERE THE LINE EXITS
 THE OPPOSITE SIDE OF THE BUILDING.THIS
 NEEDS TO BE CORRECTED ON THE LNW PLAN,
 SINCE THIS IS A DEP APPROVED DESIGN.
  
 3.A SEPARATE EASEMENT WILL NOT BE
 REQUIRED FOR THE CITY METER, THE METER
 WILL NOT BE ON PRIVATE PROPERTY. IT WILL
 NEED TO BE IN THE 12' UTILITY EASEMENT
 AS SHOWN ON THE PLANS, AND THE FIRE LINE
 AND DOMESTIC BACKFLOW PREVENTERS NEED TO
 BE ON PRIVATE PROPERTY RIGHT OUTSIDE OF
 THE UTILITY EASEMENT.NEITHER SP-1 OR 5
 OF 8 FROM LNW SHOW IT THIS WAY AND LNW
 PLAN NEEDS TO BE CHANGED.SP-1 SHOWS
 THE BACKFLOW PREVENTERS NEXT TO THE
 DUMPSTER (25'+- FROM THE EDGE OF THE
 EASEMENT). LNW PLAN SHOWS AN EASEMENT
 15' AROUND THE BACKFLOW PREVENTERS,
 WHICH IS NOT REQUIRED SINCE THE BACKFLOW
 PREVENTERS BELONG TO THE PROPERTY OWNER,
 NOT THE CITY.
  
 4.THE PLAN SHOWS A TAPPING SADDLE FOR
 THE WATER SERVICE, THIS IS ALSO
 INCORRECT, THE TAP WILL BE DIRECT AS
 SHOWN ON OUR STANDARD DETAILS.
  
 5.ON SHEET SP-1 THE DUMPSTER MUST HAVE
 12'-6" BETWEEN THE OPEN GATES.
 ADDITIONALLY A 4 X 4 PRESSURE TREATED
 BOARD ANCHORED TO THE CONCRETE PAD WILL
 NOT HOLD THE DUMPSTER, CHANGE IT TO 10'
 WIDE CONCRETE.YOU CAN USE PRECAST
 CONCRETE WHEEL STOPS.THEY WILL NEED TO
 BE A MINIMUM OF 10' LONG.
  
 6. STORM WATER REQUIREMENTS:
 TO OBTAIN A CONSTRUCTION PERMIT THE
 FOLLOWING MUST BE SUBMITTED SIGNED AND
 SEALED BY A FLORIDA PROFESSIONAL
 ENGINEER (PE).
  
 A. CONSTRUCTION PLANS (SUBMITTED)
  
 B. DETAILS AND SPECIFICATIONS(SUBMITTED)
  
  
 C. HYDRAULIC COMPUTATIONS AND SUPPORTING
 DOCUMENTATION (NOT SUBMITTED)
  
 D. IMPERVIOUS AREA COMPUTATIONS (NOT
 SUBMITTED)
  
 E. POLLUTION PREVENTION PLAN (NOT
 SUBMITTED)
 THE POLLUTION PREVENTION PLAN SHALL BE
 KEPT ON SITE AT ALL TIMES DURING
 CONSTRUCTION. THE PLAN SHALL BE
 INSTALLED IN THE FIELD PRIOR TO ANY
 EARTHWORK. THE ENGINEER OF RECORD SHALL
 CERTIFY TO THE CITY, ON A MONTHLY BASIS,
 THAT THE PLAN IS WORKING PROPERLY AND AS
 DESIGNED. THE ENGINEER OF RECORD IS
 RESPONSIBLE TO CERTIFY IMPLEMENTATION OF
 THE PROVISIONS OF CITY ORDINANCE NO.
 3132-98 OF THE CITY CODE AT SUCH TIME
 THE PERMITTEE APPLIES FOR A CERTIFICATE
 OF OCCUPANCY FROM THE CITY BUILDING
 OFFICIAL.
 SEE SECOND REVIEW FOR REST OF THE
 COOMENTS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-01-05 Cont ID  
Sent By rturnque Date 2000-01-05 Time 14:45 Rev Time 0.20
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-12-29 Cont ID  
Sent By ndenmark Date 1999-12-29 Time 08:10 Rev Time 0.25
Received By ndenmark Date 1999-12-29 Time 08:10 Sent To  
Notes
2001-01-08 00:00:00MECHANICAL SHELL ONLY OK

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-05-12 Cont ID  
Sent By tlarge Date 2000-05-06 Time 09:00 Rev Time 0.33
Received By tlarge Date 2000-05-06 Time 09:00 Sent To  
Notes
2001-01-08 00:00:00REVISED SANITARY AND STORM.

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-02-15 Cont ID  
Sent By pschmitz Date 2000-02-15 Time 15:04 Rev Time 0.75
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00SEE ARCH NOTES ATTACHED REQ PLBG NOTEWS.

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-03-06 Cont ID  
Sent By tlarge Date 2000-01-25 Time 17:03 Rev Time 1.25
Received By bstaples Date 2000-01-25 Time 17:03 Sent To  
Notes
2001-01-08 00:00:00REQD.NUMBER OF PLUMBING FIXTURES PER SQ.
 FOOTAGE OF BUILDING SHALL COMPLY W/SPC
 SEC.407.1.3.(THE CORE RESTROOMS DO NOT
 CONTAIN THE CORRECT NUMBER OF PLBG.
 FIXTURES.)
  
 SUBMIT STORM DRAINAGE RISER DIAGRAM FOR
 REVIEW.SHOW SQ.FOOTAGE OF ROOF AREA
 DRAINED BY EACH DRAIN AND INCLUDE 1/2
 AREA OF VERTICAL WALL INTO DESIGN CALCS.
 PER SPC SEC.1108.3.
  
 CLEARLY SHOW DISCHARGE PT.OF OVERFLOW
 DRAINS.COMPLY W/SPC 301.2.
  
  
 SHT.PO.1-"M" COPPER NOT PERMITTED U/G
 COUNTYWIDE AMENDMENTS TO SPC SEC.611.3.
  
 A BACKFLOW PREVENTION DEVICE IS REQD.
 ON SUPPLY TO FOUNTAIN PER SPC SEC.606.1,
 606.2.
  
 A WATER PERMIT MAY BE REQD.FOR THE WATER
 SERVICE.CONTACT PALM BCH.COUNTY HEALTH
 DEPT.AND FLA.DEPT.OF ENVIRON.PROTECTION.
 PROOF OF REVIEW BY THESE DEPTS.SHALL BE
 SUBMITTED .COUNTYWIDE AMENDMENTS TO SPC
 SEC.101.4.7.
  
 INDICATE WATER SOURCE FOR IRRIG.SYSTEM.
 A WATER USE PERMIT MAY BE REQD.PER F.S.
 373.219.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-03-07 Cont ID  
Sent By hpiskura Date 2000-03-06 Time 09:46 Rev Time 0.15
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***