Plan Review Details - Permit 99120813
Plan Review Stops For Permit 99120813
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-01-21 Cont ID  
Sent By lmartine Date 2000-01-21 Time 08:18 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1900-01-08 Cont ID  
Sent By dpalmer Date 2000-01-08 Time 18:49 Rev Time 0.00
Received By dpalmer Date 2000-01-08 Time 18:49 Sent To  
Notes
2001-01-08 00:00:00************** PROVISO ****************
  
 1)NOTE: FOR NEW BATH BEING INSTALLED
 TO COMPLY WITH ADA. PLEASE HAVE SWITCH
 HEIGHTS INDICATED ON PLANS.
  
 2)NOTE: PLEASE SHOW SHOW A MORE DETAILED
 LAYOUT OF NEW LIGHTS AND HOW THEY ARE
 GOING TO BE CONTROLLED. INCLUDING LIGHTS
 IN ADA BATH.
  
 PLEASE HAVE THE ABOVE INFORMATION
 SUBMITTED FOR REVIEW AND APPROVAL
 BEFORE FIRST ROUGH ELECTRICAL INSPECTION
 IS CALLED IN.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-01-14 Cont ID  
Sent By rturnque Date 2000-01-14 Time 14:07 Rev Time 0.15
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-02-24 Cont ID  
Sent By tlarge Date 2000-02-24 Time 18:31 Rev Time 0.50
Received By tlarge Date 2000-02-24 Time 18:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2000-02-24 Cont ID  
Sent By tlarge Date 2000-02-20 Time 08:38 Rev Time 0.33
Received By tlarge Date 2000-02-20 Time 08:37 Sent To  
Notes
2001-01-08 00:00:00SUBMIT SANITARY AND WATER ISOMETRICS FOR
 REVIEW WHICH REFLECT THE SCOPE OF
 PLUMBING WORK BEING DONE.ISOMETRICS
 SHALL BE SIGNED AND SEALED PER COUNTY-
 WIDE AMENDMENTS TO SPC SEC.104.2.3.
 (A WATER ISOMETRIC WAS NOT SUBMITTED,
 ONLY SANITARY WHICH BORE NO SIGNATURE OR
 SEAL.)

Review Stop P PLUMBING
Rev No 1 Status N Date 2000-02-24 Cont ID  
Sent By tlarge Date 2000-01-08 Time 07:34 Rev Time 0.50
Received By tlarge Date 2000-01-08 Time 07:34 Sent To  
Notes
2001-01-08 00:00:00SUBMIT SANITARY AND WATER ISOMETRICS FOR
 REVIEW WHICH REFLECT SCOPE OF PLBG.WORK
 BEING DONE.COUNTYWIDE AMENDMENTS TO SPC
 SEC.104.2.1.
  
 SHOW ALL MOUNTING HEIGHTS/DIMENSIONS OF
 ALL HANDICAP FIXTURES AND APPURTENANCES
 COMPLY W/FACBC.
  
 BREAKROOM SINK SHALL COMPLY W/FACBC SEC.
 4.24.1-4.24.7.
  
 SHOW TOILET ROOM DIMENSIONS.(LXW) AND
 FIXTURE CLEARANCES PER FACBC.