| Plan Review Stops For Permit 99120645 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2000-04-25 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2000-04-25 |
Time |
12:11 |
Rev Time |
99.00 |
| Received By |
hpiskura |
Date |
2000-04-24 |
Time |
13:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-02-29 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2000-02-29 |
Time |
07:42 |
Rev Time |
99.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
Z |
|
| Notes |
| 2001-01-08 00:00:00 | CHECKLIST WITH APPLICATION 2/29/00 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2000-05-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-05-31 |
Time |
08:55 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-05-31 |
Time |
08:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2000-04-25 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2000-04-25 |
Time |
15:29 |
Rev Time |
1.30 |
| Received By |
jleahy |
Date |
2000-04-25 |
Time |
15:29 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | REVISION HAD WRONG PERMIT NUMBER WHEN IT | | | CAME IN!!!!! |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2000-04-25 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-04-25 |
Time |
09:51 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-04-25 |
Time |
09:51 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PER JAKE LEAHY |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
P |
Date |
2000-02-14 |
|
|
Cont ID |
|
| Sent By |
dlauderm |
Date |
2000-02-14 |
Time |
10:17 |
Rev Time |
2.00 |
| Received By |
dlauderm |
Date |
2000-02-14 |
Time |
10:17 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PASSED WITH PROVISOS: | | | | | | STORMWATER COMMENTS: | | | | | | 1.THE ENGINEER OF RECORD SHOULD PUT | | | TOGETHER A LIST OF EXISTING IMPERVIOUS | | | AND PERVIOUS AREAS AS WELL AS A LIST OF | | | NEW IMPERVIOUS AND IMPERVIOUS ARES, TO | | | SHOW WHAT THE NEW ERU RATE WILL BE. | | | PLEASE SUBMIT PLANS SHOWING PRIOR TO | | | DEMOLITION AND FINAL DESIGN SO WE CAN | | | COMPARE THE TWO. | | | | | | 4.THE STORMWATER SYSTEM ON THE HOSPITAL | | | PROPERTY IS ALL PRIVATE AND AS SUCH WE | | | HAVE NO COMMENTS ABOUT THE DESIGN, | | | EXCEPT WHAT IS WRITTEN ABOVE. | | | | | | WATER AND SANITARY: | | | | | | 1.ALL ON SITE PIPING IS A PRIVATE | | | DISTRIBUTION SYSTEM METERED AND | | | PROTECTED WITH BACKFLOW PREVENTERS AT | | | 45TH AND GREENWOOD AVENUES. ALL OF THE | | | GRAVITY SYSTEM FROM 45TH STREET NORTH | | | AND GREENWOOD WEST IS PRIVATE OWNED BY | | | ST. MARY'S.AS SUCH WE DO NOT NEED TO | | | REVIEW THIS DESIGN FOR COMPLIANCE TO OUR | | | STANDARDS. BUT I MAKE THE FOLLOWING | | | COMMENTS FOR ITEMS THAT I SEE AS | | | POSSIBLY INCORRECT: | | | | | | 2.A 4" METER IS SHOWN AT THE NORTHWEST | | | CORNER OF THE BUILDING, IT IS NOT | | | REQUIRED BY THE PUBLIC UTILITY | | | DEPARTMENT SINCE WE MASTER METER THE | | | SITE. | | | | | | 3.SINCE ALL OF THE SANITARY SEWER SYSTEM | | | IS A PRIVATE, ONE OWNER SYSTEM, A DEP | | | PERMIT MAY NOT BE REQUIRED.CONTACT | | | JAMES L. (DUTCH) HOLLAND, ENVIRONMENTAL | | | ENGINEER (PLAN REVIEWER), AT | | | W-561:355-4045, EX. 1134F-561:355-2442 | | | AND DISCUSS IT WITH HIM OR ONE OF THE | | | OTHER PLAN REVIEWERS. | | | | | | 4.THE FIRE LINE THAT COME OFF OF THE | | | MASTER METERED DOMESTIC DISTRIBUTION | | | MAIN DOES NOT APPEAR TO HAVE AN APPROVED | | | DOUBLE CHECK BACKFLOW PREVENTER ON IT, | | | IT SHOULD HAVE ONE TO STOP ANY WATER | | | FROM COMING INTO THE SYSTEM WHEN PUMPED | | | INTO THE FDC.PLEASE CHECK AND SEE IF | | | EXISTS AND WAS LEFT OFF THE PLAN BY | | | MISTAKE OR IF IT NEEDS TO BE ADDED. | | | | | | 5.THE REDUCED PRESSURE BACKFLOW | | | PREVENTER SHOWN IS A SINGLE DEVICE.WE | | | STRONGLY SUGGEST ON DOMESTIC, CRITICAL | | | USAGE LOCATIONS, SUCH AS THIS THAT TWO | | | DEVICES ARE INSTALLED IN PARALLEL.THIS | | | WAY IF ONE FAILS OR HAS TO BE SHUT OFF | | | TO BE WORKED ON THE HOSPITAL IS NOT | | | WITHOUT WATER. | | | | | | 6.THE TEMPORARY JUMPER CONNECTION SHOWN | | | ON PAGE C3.01 IS WRONG.TWO IN-LINE | | | VALVES ARE REQUIRED WITH AN OPEN VENT | | | BETWEEN.THIS ALLOWS WATER TO PASS THRU | | | THE PROTECTED BYPASS FOR TESTING AND | | | WITHOUT THE CHANCE OF BACKFLOW THRU THE | | | SINGLE VALVE.THIS IS A DEP REQUIREMENT | | | ALSO. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2000-01-07 |
|
|
Cont ID |
|
| Sent By |
rturnque |
Date |
2000-01-06 |
Time |
11:17 |
Rev Time |
0.55 |
| Received By |
rturnque |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1. FIRE ALARM SYSTEM SHALL BE CLASS "A" | | | OR ADDRESSABLE AND MONITORED BY AN | | | APPROVED CENTRAL STATION. | | | 2.RFER TO NFPA, 1985 LIFE SAFETY CODE. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2000-01-24 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-01-24 |
Time |
14:47 |
Rev Time |
5.00 |
| Received By |
ndenmark |
Date |
2000-01-24 |
Time |
14:46 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | SEE LETTER FROM JLSD ON ABSENCE OF F/D | | | INTO SHAFT FOR EXHAUST DUCT FOR ISOLA- | | | TION ROOMS |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
8 |
Status |
P |
Date |
2000-04-21 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-04-21 |
Time |
16:51 |
Rev Time |
5.75 |
| Received By |
tlarge |
Date |
2000-04-21 |
Time |
16:51 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ******************PROVISO*************** | | | SUBMIT CALCULATIONS FOR SECONDARY ROOF | | | DRAINAGE.COMPLY W/SPC SEC.1109.1-1109.3. | | | APPENDIX"A",AND SBC SECS.1517.6.4.1 THRU | | | 1517.6.4.3. I'VE REQUESTED THIS | | | INFORMATION SINCE MY FIRST REVIEW ON | | | 1/12/00 AND HAS NOT BEEN PROPERLY | | | ADDRESSED TO DATE. | | | THE PLANS NOTE SCUPPERS AND NOTHING IS | | | SHOWN.SUBMIT ALL REQD.INFO. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
7 |
Status |
F |
Date |
2000-03-20 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-03-20 |
Time |
12:41 |
Rev Time |
2.50 |
| Received By |
tlarge |
Date |
2000-03-20 |
Time |
12:40 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | SEE REVIEW STOPS #5 & 6 FOR COMMENTS. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
6 |
Status |
F |
Date |
2000-03-19 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-03-19 |
Time |
10:56 |
Rev Time |
15.75 |
| Received By |
tlarge |
Date |
2000-03-19 |
Time |
10:56 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | CONTINUATION OF PLBG.COMMENTS: | | | | | | SHT.P-13-FLOOR DRAINS NOT PROPERLY | | | VENTED.SPC SEC.901.2. | | | | | | SHT.P-16-JOINTS ON WATER DISTRIBUTION | | | SYSTEM NOT PERMITTED UNDER SLAB INSIDE | | | BUILDING PER COUNTYWIDE AMENDMENTS SEC. | | | 611.3.SEE DETAIL #4. | | | | | | FIXTURES HAVING SLIP JOINT CONNECTIONS | | | SHALL COMPLY W/SPC SEC.401.5.2.(SEE | | | SHT.P-16,DETAIL #1. | | | | | | MINIMUM SIZE OF DRAINAGE PIPE UNDER- | | | GROUND SHALL BE 2" PER SPC SEC.714.4. | | | | | | BACKWATER VALVES SHALL BE INSTALLED ON | | | DRAIN CONNECTIONS FROM FOUNTAINS TO | | | STORM SYSTEM PER SPC 301.11.1,409.9.2. | | | | | | SHTS.A1.32-ROOM#1627 & A1.34 &1.36-ROOM | | | #1647-SHOWERS SHALL COMPLY W/FACBC SECS. | | | 4.21.2-4.21.8.WASHER AND DRYER SHALL | | | COMPLY W/FACBC SEC.6.1(1). | | | | | | VOID ALL PREVIOUS PLBG.SHEETS REPLACED | | | BY NEW REVISIONS AND INSERT NEW SHEETS | | | INTO PLANS .COUNTYWIDE AMENDMENTS TO SPC | | | SEC.104.2.1. | | | | | | SHT.P24-VENT SIZING SHALL COMPLY W/SPC | | | TABLE 920.2,920.4. | | | | | | SHT.P24-THE SANITARY SCHEMATIC IS VAGUE | | | REGARDING THE LINE SIZES FOR THE DRAIN- | | | AGE SYSTEM.THERE ARE SECTIONS WITH NO | | | SIZES,LONG RUNS W/NO SIZES, | | | | | | SHT.P24-HORIZONTAL DRAIN PIPING LACKS | | | SIZES AND SCHEMATIC DOESN'T REFLECT | | | THE SYSTEM AS DRAWN ON SHTS.P3 & P4. | | | COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1 | | | | | | VENTS NOT PERMITTED TO INCREASE IN SIZE. | | | SPC 905.2.(PERMITTED ONLY WHERE FROST | | | CLOSURE IS A PROBLEM.) | | | | | | NOTE:I RECOMMEND A MEETING W/THE DESIGN | | | PROFESSIONALS AND MYSELF TO CLARIFY | | | ISSUES,EPECIALLY THE PLUMBING SCHEMATIC. | | | | | | PLEASE CALL 561-659-8096 EXT.8377 IF YOU | | | HAVE ANY QUESTIONS. | | | TIMOTHY K.LARGE,PLUMBING PLAN REVIEW. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
F |
Date |
2000-03-19 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-03-19 |
Time |
09:10 |
Rev Time |
0.00 |
| Received By |
tlarge |
Date |
2000-03-19 |
Time |
09:10 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | JOB SPEC.15400-1.3-DELETE REFERENCE TO | | | 1997 EDITION OF STANDARD PLUMBING CODE. | | | THE 1994 EDITION IS THE ADOPTED STANDARD | | | | | | SPEC.15141-3.1(A)(B)-HANGERS & SUPPORTS | | | FOR PIPING SHALL COMPLY W/SPC SEC.310.2, | | | 310.3. | | | | | | SPEC.15412-3.7(A)-SIZE AND SPACING OF | | | CLEANOUTS IN THE SANITARY SYSTEM SHALL | | | COMPLY W/SPC SEC.710.2.1-710.2.4,711.1, | | | 711.2.,712. | | | | | | SUBMIT APPROVALS FROM CITY OF WEST PALM | | | BEACH ENGINEERING DEPT.FOR STORM | | | DRAINAGE SYSTEM.COUNTYWIDE AMENDMENTS TO | | | SPC SEC.101.4.7. | | | | | | SUBMIT COPIES OF APPROVALS FROM PALM | | | BEACH COUNTY HEALTH DEPT.AND DEP FOR | | | WATER MAIN/WATER SERVICE EXTENSION. | | | COUNTYWIDE AMENDMENTS TO SPC SEC.101.4.7 | | | | | | INDICATE WATER SOURCE FOR IRRIGATION | | | SYSTEM.IF SUPPLY IS FROM AN ARTIFICIAL | | | MEANS(WELL,LAKE,ETC.)A WATER USE PERMIT | | | WILL BE REQD.FROM SO.FLA.WATER MNGMT. | | | PER F.S.373.219. | | | | | | SUBMIT COPY OF AHCA APPROVAL FOR THIS | | | PROJECT.COUNTYWIDE AMENDMENTS TO SPC | | | SEC.101.4.7. | | | | | | NOTE OCCUPANT LOAD FOR THE STRUCTURE | | | BASED UPON SQ.FOOTAGE.REFER TO SPC SEC. | | | 407.1.3 AND TABLE 407. | | | | | | SHT.C1.00-SHOW SQ.FOOT AREA DRAINED BY | | | EACH AREA DRAIN.COMPLY W/SPC TABLE | | | 1108.2. | | | | | | SHT.C2.00-LOCATION OF BFP DEVICE SHALL | | | BE APPROVED BY CITY OF WPB UTILITIES. | | | CALL 659-8000,EXT.2008. | | | | | | REFER TO "A"DRAWINGS-REVISE NOTES THAT | | | REFER TO 1997 EDITION OF STD.PLBG.CODE | | | TO READ 1994 EDITION.AMENDMENTS TO SPC | | | SECS.101.1,101.2. | | | | | | REFER TO "A" DRAWINGS -THERE ARE STILL | | | SHEETS THAT DO NOT SHOW LAVATORIES IN | | | THE HANDICAP ACCESSIBLE STALLS.SEE A7.7, | | | A7.13, | | | | | | SHT.A6.9-SHOW CLEAR FLOOR SPACE UNDER | | | H.C.LAV.COMPLY W/FACBC SEC.4.19.2(MIN. | | | 29" REQD.). | | | | | | MEDICAL CARE FACILITIES SHALL COMPLY W/ | | | FACBC SECS.6.1(1) FLA.10% RULE,6.4,4.22, | | | 4.23.THE STRUCTURE DOES NOT PRESENTLY | | | COMPLY. | | | | | | BATHTUBS LOCATED IN HANDICAP ACCESSIBLE | | | PATIENT ROOMS SHALL COMPLY W/FACBC SECS. | | | 4.20.1-4.20.7. | | | | | | SHT.A6.1-GRAB BARS FOR TUB W/SEAT AT | | | HEAD SHALL COMPLY W/FACBC FIG.34. | | | | | | SHT.A6.1-MOUNTING HEIGHTS OF MIRRORS, | | | TOWEL DISPENSERS,ETC.SHALL COMPLY W/ | | | FACBC SEC.4.2.5,4.2.6,4.19.6,4.23.9, | | | & FIGS.5 & 6. | | | | | | SUBMIT DETAILS/CALCULATIONS FOR | | | SECONDARY ROOF DRAINAGE.(REFER TO ROOFS | | | FOR FLOORS #1,2,3,& 5.COMPLY W/SPC SEC. | | | 1109.1-1109.3,APPENDIX "A",AND SBC SECS. | | | 1517.6.4.1.-1517.6.4.3. | | | | | | SHT.A1.30-ROOM 1631-SHOWER FLOOR SHALL | | | BE DRAINED TO COMPLY W/SPC SEC.409.8.3. | | | | | | EFFLUENT FROM ELEVATOR SUMP SHALL FIRST | | | PASS THRU AN OIL INTERCEPTOR AND THEN TO | | | THE SANITARY SYSTEM BY INDIRECT CONNECT- | | | ION PER SPC SEC 301.4,1004.1,1004.5 & | | | FLA.ADMIN.CODE CHAPT.61(C)-5.OO1 | | | | | | FILM PROCESSORS UTILIZING WATER AND | | | WASTE CONNECTIONS SHALL COMPLY W/SPC | | | SECS.606.1,801.4. | | | | | | SHT.P-14-CLEANOUT PLUG SHOWN IN SHOWER | | | DRAIN.PLUG SHALL BE ACCESSIBLE PER SPC | | | SEC.710.6.1. | | | | | | SEE PLBG.STEP #6 FOR CONTINUATION. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
F |
Date |
2000-01-29 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-01-29 |
Time |
11:07 |
Rev Time |
6.25 |
| Received By |
tlarge |
Date |
2000-01-29 |
Time |
11:14 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | SEE PLBG.STEP #2 FOR PLBG.COMMENTS. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2000-01-28 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-01-28 |
Time |
21:08 |
Rev Time |
3.00 |
| Received By |
tlarge |
Date |
2000-01-28 |
Time |
21:07 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | THESE COMMENTS ARE A CONTINUATION OF THE | | | PLUMBING PLAN REVIEW FOR THIS PROJECT. | | | | | | SUBMIT COPY OF AHCA APPROVAL FOR THIS | | | PROJECT.COUNTYWIDE AMENDMENTS TO SPC | | | SEC.101.4.7. | | | | | | SUBMIT APPROVAL FROM SO.FLA.WATER MNGMT. | | | FOR INSTALLATION OF DRAINAGE WORK.COUNTY | | | WIDE AMENDMENTS TO SPC SEC.101.4.7. | | | | | | SUBMIT COMPLETE ISOMETRIC DIAGRAMS FOR | | | THE INSTALLATION OF THE SANITARY,STORM, | | | AND WATER SYSTEMS.THE DRAWINGS SHALL | | | CLEARLY REFLECT THE ENTIRE SCOPE OF | | | PLUMBING WORK BEING DONE.(INCLUDE ALL | | | UNDERGROUND WORK ON THE ISOMETRICS.) | | | COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.2 | | | | | | INDICATE SLOPE OF PIPE ON THE PLANS FOR | | | THE STORM DRAINAGE SYSTEM.COMPLY W/TABLE | | | 1108.2 OF SPC. | | | | | | DISCHARGE LINE FROM ELEVATOR SUMP SHALL | | | CONNECT INDIRECTLY TO THE STORM DRAIN | | | SYSTEM.FLA.ADMIN.CODE CHAPT.61(C)-5.001. | | | | | | THE SHUT-OFF AND CHECK VALVES FOR THE | | | ELEVATOR SUMP SHALL BE LOCATED ABOVE THE | | | SUMP COVER AND BE ACCESSIBLE PER SPC | | | SEC.717.2. | | | | | | SUBMIT REVISED BLUEPRINTS SHOWING | | | LAVATORIES WITHIN THE REQD.ACCESSIBLE | | | STALLS.THE DIMENSIONS OF THE STALL SHALL | | | COMPLY W/FACBC SEC.4.17.3.(MIN.81"WIDE.) | | | | | | SHT.P-13-SUBMIT DETAILS FOR THE WATER | | | FILL LINE TO THE FOUNTAIN.SHOW REQD. | | | BACKFLOW PROTECTION OF THE WATER SYSTEM. | | | SPC 606.1,606.2 | | | | | | SHT.P-16-FIXTURES HAVING CONCEALED SLIP | | | JOINT CONNECTIONS SHALL COMPLY W/SPC | | | 401.2.2.(SEE DETAIL #2) | | | | | | SHT.18-DETAIL#3-VENT SIZING SHALL COMPLY | | | W/SPC SEC.920.2.(FIXTURE UNIT LOAD | | | EXCEEDS 2" CAPACITY.)CHECK ALL RISERS | | | FOR PROPER VENT SIZING PER SPC 920.2. | | | | | | SUBMIT CONDENSATE RISER FOR REVIEW. | | | COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1 | | | | | | SUBMIT MANUF.SHEETS FOR FILM PROCESSOR. | | | WATER CONNECTION SHALL BE PROTECTED | | | AGAINST BACKFLOW AND EFFLUENT SHALL | | | BE NEUTRALIZED PRIOR TO DISCHARGE TO | | | SANITARY SYSTEM.SPC SEC.606.1,801.4. | | | | | | SUBMIT PLANS FOR IRRIGATION SYSTEM.SHOW | | | WATER SOURCE AND PROTECTION AGAINST | | | BACKFLOW PER SPC 606.1 | | | | | | A PERMIT MAY BE REQD.FOR THE WATER | | | SERVICE FROM DEPT.OF ENVIRON.PROTECTION | | | & HEALTH DEPT.SUBMIT DOCUMENTATION THESE | | | AGENCIES HAVE REVIEWED AND APPROVED | | | THE PLANS. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2000-01-12 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-01-12 |
Time |
10:42 |
Rev Time |
7.50 |
| Received By |
tlarge |
Date |
2000-01-12 |
Time |
10:42 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | SUBMIT PLANS/INFORMATION ON PNEUMATIC | | | TUBE TRANSFER YSTEM. | | | | | | **********************NOTE************** | | | THE ABOVE COMMENTS ARE DERIVED FROM THE | | | ARCHITECTURAL PLANS ONLY.THE PLUMBING | | | DRAWINGS WERE NOT SUBMITTED AND HENCE | | | NOT REVIEWED.ADDITIONAL PLUMBING REVIEW | | | COMMENTS MAY BE GENERATED WHEN COMPLETE | | | REVIEW IS COMPLETED. | | | CALL TIMOTHY LARGE AT (561)659-8096 | | | EXT.8377 IF YOU HAVE ANY QUESTIONS. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-01-12 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-01-12 |
Time |
07:12 |
Rev Time |
0.00 |
| Received By |
tlarge |
Date |
2000-01-12 |
Time |
07:12 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | SUBMIT COPY OF JOB SPECIFICATIONS AND | | | COMPLETE PLUMBING DRAWINGS INCUDING | | | ISOMETRICS FOR STORM,SANITARY,WATER AND | | | ALL OTHER RELATED PLUMBING SYSTEMS PER | | | COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1 | | | | | | SUBMIT OCCUPANT LOAD PER SPC SEC.407.1.3 | | | TO ENSURE COMPLIANCE FOR MINIMUM REQD. | | | SANITARY FACILITIES. | | | | | | SHT.C1.00-SHOW SQ.FT.AREA DRAINED BY | | | EACH AREA DRAIN.COMPLY W/SPC TABLE | | | 1108.2. | | | | | | SHT.C2.00-LOCATION OF BFP DEVICE SHALL | | | BE APPROVED BY CITY OF WPB UTILITIES. | | | CALL 659-8000,EXT.2008. | | | | | | SHT.AO-11-SUBMIT DETAILS FOR RIVER ROCK | | | FOUNTAIN.(FILL LINE,DRAINS,PUMP,ETC)PER | | | COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1 | | | | | | SHT.A1-1-REVISE PLBG.STANDARD AT CODE | | | BRIEF TO READ 1994 ED.PER COUNTYWIDE | | | AMENDMENTS TO SPC SEC.101.1,101.2. | | | | | | FLOORS AND WALLS IN TOILET ROOMS/REST- | | | ROMMS SHALL BE NONABSORBENT TO A HEIGHT | | | OF 4' PER SBC SEC.1204.2. | | | | | | FLOOR DRAINS ARE REQD.IN ALL TOILET/ | | | RESTROOMS PER SPC SEC.409.4.1.1(SEE | | | EXCEPTION). | | | | | | SUBMIT DETAILS FOR OVERFLOW DRAINAGE FOR | | | ROOF STRUCTURE.COMPLY W/SBC 1517.6.4.1, | | | THRU 1517.6.4.3.,1109.1- 1109.3.,AND | | | APPENDIX "A"OF SPC. | | | | | | CLEARLY SHOW ALL RESTROOM/TOILET ROOM & | | | TOILET STALL DIMENSIONS ON ARCH.FLOOR | | | PLANS.COUNTYWIDE AMENDMENTS TO SPC SEC. | | | 104.2.1,104.2.2. | | | | | | ALL HANDICAP TOILET STALLS SHALL CONTAIN | | | AN ACCESSIBLE LAVATORY WITHIN THE STALL | | | PER FACBC SEC.4.17.3(EXCEPTION:NEW | | | CONSTRUCTION). | | | | | | ALL LOUNGE/BREAKROOM SINKS AND SINKS | | | LOCATED IN OTHER NON-WORK AREAS SHALL | | | BE FULLY ACCESSIBLE AND COMPLY W/FACBC | | | SEC.4.24.1-4.24.7. | | | | | | CLEARLY SHOW DIMENSIONS (LXW)OF ALL | | | SHOWER STALLS.SIZE OF ACCESSIBLE SHOWERS | | | SHALL COMPLY W/FACBC SECS.4.21-4.21.8. | | | OTHER SHOWERS SHALL BE ADAPTABLE PER | | | FACBC SEC.4.1.3.(11).SEAT IN SHOWER | | | SHALL COMPLY W/FACBC SEC.4.21.3. | | | | | | URINALS SHALL COMPLY W/FACBC SEC.4.18.1- | | | 4.18.4. | | | | | | FLUSH CONTROLS FOR WATER CLOSETS SHALL | | | COMPLY W/FACBC SEC.4.16.5. | | | | | | DRINKING FOUNTAINS ARE REQD.PER SPC | | | TABLE 407 AND ACCESSIBLE FOUNTAINS SHALL | | | COMPLY W/FACBC SEC.4.1.3.(10)(A)(B). | | | | | | ACCESSIBLE WATER CLOSETS IN STALLS SHALL | | | BE LOCATED IN THE CORNER,DIAGONAL TO THE | | | DOOR PER FACBC SEC.4.17.3(EXCEPTION:NEW | | | CONSTRUCTION). | | | | | | MEDICAL CARE FACILITIES SHALL COMPLY W/ | | | FACBC SECS.6.1(1).(10% RULE) AND 6.1(4) | | | (A)(B),6.4. | | | | | | BATHTUBS IN ACCESSIBLE PATIENT ROOMS | | | SHALL COMPLY W/FACBC SEC.4.20.1-4.20.7. | | | | | | CLEARLY SHOW WHEELCHAIR TURNING SPACE IN | | | ACCESSIBLE TOILET ROOMS AND STALLS PER | | | FACBC SEC.4.2.3. | | | | | | SHT.A6-2-SUBMIT U.L.ASSEMBLY NUMBERS FOR | | | FIRE SAFING DETAILS PER SBC 701.5.2. | | | (1996 ED.)AND SBC SEC.3502. | | | | | | SUBMIT COMPLETE INFO FOR SECONDARY ROOF | | | DRAINAGE | | | | | | PLUMBING INSTALLATION SHALL COMPLY W/SPC | | | APPENDIX "G"FOR HOSPITALS. | | | | | | MUTIPLE/GANG SHOWERS SHALL COMPLY W/SPC | | | SEC.409.8.3. | | | *****(SEE PLBG.STEP#2FOR CONTINUATION)** |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2000-04-25 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2000-04-25 |
Time |
12:10 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | OK'D BY SEAN EBERSOLD 4/25/00 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
1999-12-21 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2000-02-29 |
Time |
07:43 |
Rev Time |
0.25 |
| Received By |
gjoyce |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | NEEDS FORMALSITE PLAN REVIEW |
|
|