Plan Review Details - Permit 99120595
Plan Review Stops For Permit 99120595
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-01-04 Cont ID  
Sent By dpalmer Date 2000-01-04 Time 16:13 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
2001-01-08 00:00:00**************NOTE*********************
  
 1)NOTE: JUST NOTE THAT ONLY BATH OUTLETS
 MAY BE ON BATH CIRCUT(S).
  
 2)NOTE: BEING THAT MORE THAN 49% OF
 HOUSE IS BEING REMODELED.THE CLEARENCES
 FOR AND THE TYPE OF CLOSET LIGHTING
 STILL NEED TO MEET CODE OF ART 410-8
  
 3)NOTE: RISER DIAGRAM SHOWS ONLY 2-2/0`S
 FOR FEED TO PANEL. NEEDS TO BE THREE
 CONDUCTORS FOR PANEL FEED.
  
 THE ABOVE WERE NOTES TO THE PLANS AND
 DO NOT NEED TO BE REDONE.ONLY IF THERE
 ARE ANY OTHER CHANGES/AS-BUILTS.
 IF THERE ARE ANY QUESTIONS CALL 659-8096
 EXT 8372.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-05-04 Cont ID  
Sent By cthirben Date 2000-05-04 Time 16:34 Rev Time 1.00
Received By cthirben Date 2000-05-04 Time 16:33 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-12-27 Cont ID  
Sent By jleech Date 1999-12-27 Time 14:38 Rev Time 0.35
Received By jleech Date 1999-12-27 Time 14:38 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-04-17 Cont ID  
Sent By tlarge Date 2000-04-17 Time 12:58 Rev Time 0.30
Received By tlarge Date 2000-04-17 Time 12:58 Sent To  
Notes
2001-01-08 00:00:00REVISED SAN.RISER.

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-12-20 Cont ID  
Sent By tlarge Date 1999-12-20 Time 11:01 Rev Time 0.33
Received By tlarge Date 1999-12-20 Time 11:01 Sent To  
Notes
2001-01-08 00:00:00LOCATION OF PLBG. FIXTURES ON SANITARY
 RISER SHALL MATCH FLOOR PLAN PER COUNTY
 WIDE AMENDMENTS TO SPC SSEC.104.2.1.
  
 FIXTURES LOCATED DOWNSTREAM OF WATER
 CLOSETS SHALL BE VENTED PER SPC SEC.
 913.2.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2000-03-04 Cont ID  
Sent By fknapp Date 2000-03-04 Time 17:35 Rev Time 1.00
Received By fknapp Date 2000-03-04 Time 17:35 Sent To  
Notes
2001-01-08 00:00:00***********NOT ACCEPTED*****************
 SBC 104.2.2
  
 1)PROVIDE TRUSS ENGINEERING SHEETS WITH
 RAISED SEAL AND ORIGINAL SIGNATURE OF
 ENGINEER WITH TRUSS LAYOUT.
  
 2)PROVIDE 2 CURRENT COPIES OF SBCCI OR
 METRO-DADE FOR ALL PRODUCT APPROVALS.
  
 3)PROVIDE INSTALLATION SCHEDULE AND KEY
 PLAN WITH SPECIFIC ANCHORS TO BE USED,
 WITH PRODUCT APPROVALS, UNDER SEPERATE
 PERMIT.
  
 NOTE****************
 ALL REVISONS MUST BE NOTED ON PLANS AND
 IDENTIFIED BY CLOUDS OR TRIANGLES AND
 ADDRESS TO SPECIFIC DISCIPLINES.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2000-01-10 Cont ID  
Sent By jcaloger Date 2000-01-10 Time 09:25 Rev Time 1.00
Received By jcaloger Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2000-01-10 Cont ID  
Sent By gjoyce Date 2000-01-10 Time 09:36 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***