Plan Review Details - Permit 99120531
Plan Review Stops For Permit 99120531
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-10-13 Cont ID  
Sent By dpalmer Date 2000-10-13 Time 12:08 Rev Time 0.00
Received By dpalmer Date 2000-10-13 Time 12:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-01-08 Cont ID  
Sent By dpalmer Date 2000-01-08 Time 11:14 Rev Time 0.00
Received By dpalmer Date 2000-01-08 Time 11:14 Sent To  
Notes
2001-01-08 00:00:00***************PROVISO******************
  
 1)NOTE:AS PER 250-81/215-5 NEED TO SHOW
 BLDG.STEEL AS PART OF THE GROUNDING
 ELECTRODE SYSTEM.
  
 2)NOTE:AS PER 210-52D/215-5 NEED TO HAVE
 DEDICATED BATH(S) CIRCUT(S) 20 AMP#12
 AWG DRAWN ON PANEL SCHEDULE.
  
 3)NOTE: NEED TO SUBMIT AIC RATING OF
 PANEL/BKRS. AIC RATING IS FIGURED FROM
 FAULT CURRENT CALCULATIONS.
  
 4)NOTE:MISSING WP GFI OUTLETS REQ`D
 FRONT AND BACK OF DWELLINGS AS PER ART:
 210-52E
  
 5)NOTE:MISSING OUTLETS REQ`D AS PER ART:
 210-52 MASTER BR/AND BR#3 2`OF WALL.
  
 6)NOTE:MISSING WP GFI REQ`D FOR A/C
 AS PER 210-63
  
 7)NOTE: AS REQ`D PER 1993/1996 NFPA-72
 2-2.1.1.1 SMOKE DETECTORS ARE REQ`D
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS
 IN NEW DWELLINGS.
  
 8)NOTE: OUTLET SPACING IN KITCHEN IS TO
 MEET REQ`MENTS PER 210-52-C-1. 12"OF
 COUNTER SPACE.
  
 9)NOTE:OUTLET REQ`D FOR PENINSULAR PER
 210-52-C-3
  
 10)NOTE: ALL OUTLETS IN KITCHEN SERVING
 COUNTERSPACE ARE REQ`D TO BE GFI/GFI
 PROTECTED. AS PER 210-8-A-6
  
 ALL THE ABOVE NEEDS TO BE SUBMITTED FOR
 REVIEW AND APPROVAL BEFORE FIRST ROUGH
 ELECTRICAL INSPECTION IS CALLED IN.
 IF THERE ARE ANY QUESTIONS;PLEASE CALL
 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-12-27 Cont ID  
Sent By jleech Date 1999-12-27 Time 14:20 Rev Time 0.35
Received By jleech Date 1999-12-27 Time 14:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-12-20 Cont ID  
Sent By tlarge Date 1999-12-20 Time 10:23 Rev Time 0.33
Received By tlarge Date 1999-12-20 Time 10:23 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2000-02-15 Cont ID  
Sent By fknapp Date 2000-02-15 Time 13:34 Rev Time 1.00
Received By fknapp Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-01-27 Cont ID  
Sent By fknapp Date 2000-01-27 Time 08:14 Rev Time 3.00
Received By fknapp Date 2000-01-27 Time 08:14 Sent To  
Notes
2001-01-08 00:00:00 
  
 ***************DENIED*******************
  
 SBC 104.2.2
  
 1)PROVIDE DESIGN CERTIFICATION FORM FOR
 BUILDING CODE COMPLIANCE.
  
 2)PROVIDE 2 CURRENT COPIES OF PRODUCT
 APPROVALS FOR ALL EXTERIOR DOORS.
  
 3)PROVIDE 2 COPIES OF SOIL REPORT.
  
 4)PROVIDE 2 CURRENT COPIES OF PRODUCT
 APPROVALS FOR STORM PANELS COMPLETE
 WITH INSTALLATION SCHEDULE AND KEY PLAN
 WITH SPECIFIC ANCHORS TO BE USED.
  
 5)BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH CO., THE PERMIT PLANS STAMPED BY
 THEM AND THE RECIEPT ATTACHED TO THE
 PERMIT APPLICATION.

Review Stop Z ZONING
Rev No 1 Status P Date 1999-12-14 Cont ID  
Sent By gjoyce Date 1999-12-14 Time 09:22 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***