| 2001-01-08 00:00:00 | ***************PROVISO****************** |
| | |
| | 1)NOTE:AS PER 250-81/215-5 NEED TO SHOW |
| | BLDG.STEEL AS PART OF THE GROUNDING |
| | ELECTRODE SYSTEM. |
| | |
| | 2)NOTE:AS PER 210-52D/215-5 NEED TO HAVE |
| | DEDICATED BATH(S) CIRCUT(S) 20 AMP#12 |
| | AWG DRAWN ON PANEL SCHEDULE. |
| | |
| | 3)NOTE: NEED TO SUBMIT AIC RATING OF |
| | PANEL/BKRS. AIC RATING IS FIGURED FROM |
| | FAULT CURRENT CALCULATIONS. |
| | |
| | 4)NOTE:MISSING WP GFI OUTLETS REQ`D |
| | FRONT AND BACK OF DWELLINGS AS PER ART: |
| | 210-52E |
| | |
| | 5)NOTE:MISSING OUTLETS REQ`D AS PER ART: |
| | 210-52 MASTER BR/AND BR#3 2`OF WALL. |
| | |
| | 6)NOTE:MISSING WP GFI REQ`D FOR A/C |
| | AS PER 210-63 |
| | |
| | 7)NOTE: AS REQ`D PER 1993/1996 NFPA-72 |
| | 2-2.1.1.1 SMOKE DETECTORS ARE REQ`D |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS |
| | IN NEW DWELLINGS. |
| | |
| | 8)NOTE: OUTLET SPACING IN KITCHEN IS TO |
| | MEET REQ`MENTS PER 210-52-C-1. 12"OF |
| | COUNTER SPACE. |
| | |
| | 9)NOTE:OUTLET REQ`D FOR PENINSULAR PER |
| | 210-52-C-3 |
| | |
| | 10)NOTE: ALL OUTLETS IN KITCHEN SERVING |
| | COUNTERSPACE ARE REQ`D TO BE GFI/GFI |
| | PROTECTED. AS PER 210-8-A-6 |
| | |
| | ALL THE ABOVE NEEDS TO BE SUBMITTED FOR |
| | REVIEW AND APPROVAL BEFORE FIRST ROUGH |
| | ELECTRICAL INSPECTION IS CALLED IN. |
| | IF THERE ARE ANY QUESTIONS;PLEASE CALL |
| | 659-8096 EXT 8372 |