Plan Review Details - Permit 99120507
Plan Review Stops For Permit 99120507
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-01-25 Cont ID  
Sent By hpiskura Date 2000-01-25 Time 11:20 Rev Time 0.00
Received By hpiskura Date   Time   Sent To ENG
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-12-29 Cont ID  
Sent By dpalmer Date 1999-12-29 Time 08:14 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
2001-01-08 00:00:00**************PROVISO*******************
  
 1)NOTE: PLEASE SUBMIT AIC RATING OF
 EQUIPMENT MAINS AND BRKRS. AIC RATING IS
 FIGURED FROM FAULT CURRENT CALCULATIONS.
 REQ`D PER 230-65/110-9/215-5.
  
 2)NOTE: PLEASE SHOW BLDG. STEEL AS PART
 OF THE GROUNDING SYSTEM PER 250-81/215-5
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION
 BEFORE ROUGH ELECTRICAL INSPECTION IS
 CALLED IN. IF THERE ARE ANY QUESTIONS
 CALL 659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2000-02-09 Cont ID  
Sent By hpiskura Date 2000-01-25 Time 11:21 Rev Time 2.00
Received By dlauderm Date 2000-02-09 Time 10:59 Sent To  
Notes
2001-01-08 00:00:00PASSED WITH PROVISOS:
  
 SHEET P-1:
 A CLEAN-OUT IS REQUIRED AT THE TIE-IN TO
 THE CITY SYSTEM AT THE PROPERTY LINE.
 THIS IS NOT SHOWN ON THE DRAWINGS.
  
 THE SANITARY SEWER LATERAL RUNS OUT THE
 EAST SIDE OF THE BUILDING.THERE IS NO
 SANITARY MAIN IN OLIVE.THE SANITARY
 MAIN IS IN THE ALLEY ON THE NORTH SIDE
 OF THE PROPERTY.HAVE THE PLUMBER CALL
 659-8079 AND HAVE THE MAINTENANCE CREW
 CHECK TO SEE IF THERE IS AN EXISTING
 LATERAL TO THE PROPERTY, IF THERE IS
 THEN RUN THE SANITARY LINE OUT TO THE
 EXISTING LATERAL (WHICH MAY BE WEST OF
 THE PROPOSED BUILDING).IF THERE IS NO
 EXISTING LATERAL THE CONTRACTOR WILL
 NEED TO TIE INTO THE EXISTING MAIN WITH
 A WYE, TWO FERNCOS USING SDR 26 PVC PIPE
 AND FITTINGS.THE EXISTING MAIN IN THE
 ALLEY IS 12" CLAY AND THE LATERAL WILL
 NEED TO BE 6".
  
  
 THE WATER LINE RUNS OUT THE WEST SIDE OF
 THE BUILDING.THERE IS A 3" TRANSITE
 WATER MAIN IN THE ALLEY THAT CAN BE USED
 FOR THE SERVICE.
  
 THE PLAN DOES NOT SHOW THE SIZE OF THE
 WATER METER REQUIRED AND IT DOES NOT
 SHOW A REDUCED PRESSURE PRINCIPLE
 BACKFLOW ASSEMBLY AT THE METER, ONE WILL
 BE REQUIRED.
  
 IT IS SUGGESTED THAT A SEPARATE
 IRRIGATION METER BE INSTALLED, THE
 SAVINGS WILL BE IN WATER USED.ALL
 WATER USED FOR THE BUILDING METER WILL
 BE CHARGED AGAINST THE SEWER CHARGES
 ALSO, DOUBLING THE WATER BILL FOR THE
 WATER USED TO IRRIGATE.
  
 NO DUMPSTER IS SHOWN.HOW WILL GARBAGE
 BE PICKED UP?WE HAVE INCLUDED A
 DUMPSTER DETAIL IF ONE NEEDS TO BE
 BUILT.THE RECYCLE SECTION IS ONLY A
 SUGGESTION.THE ENCLOSURE WILL NEED TO
 BE PLACED WHERE A TRUCK CAN PULL RIGHT
 UP TO THE OPEN GATES TO PICK UP THE
 DUMPSTER.
  
 A RIGHT OF WAY PERMIT APPLICATION IS
 INCLUDED FOR THE WORK INVOLVED WITH
 REMOVING THE SIDEWALKS AND DRIVEWAY ON
 EIGHTH STREET AND FOR THE NEW DRIVEWAY.
 A DRIVEWAY DETAIL DRAWING IS ALSO
 INCLUDED.THE DRIVEWAY APPROACH DETAIL
 MUST BE FOLLOWED.
  
 A FDOT PERMIT MAY BE REQUIRED TO TIE
 INTO THE CATCH BASIN ON OLIVE.CHECK
 WITH FDOT PRIOR TO DOING ANY WORK ON
 THIS BOX.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-12-15 Cont ID  
Sent By rturnque Date 1999-12-15 Time 10:47 Rev Time 0.20
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-12-16 Cont ID  
Sent By cthirben Date 1999-12-16 Time 14:34 Rev Time 0.00
Received By cthirben Date 1999-12-16 Time 14:41 Sent To  
Notes
2001-01-08 00:00:00FAN SHUT DOWN BY DUCT SMOKE DECTECTOR
 REQUIRED WITH NOTIFICATION BY BUILDING
 FIRE ALARM SYSTEM OR TIED TO HORN AND
 STROBE PER NFTA 4-4.4.2 OR 4-4.4.3

Review Stop P PLUMBING
Rev No 1 Status F Date 1999-12-23 Cont ID  
Sent By tlarge Date 1999-12-23 Time 15:22 Rev Time 1.50
Received By tlarge Date 1999-12-23 Time 15:22 Sent To  
Notes
2001-01-08 00:00:00A DRINKING FOUNTAIN IS REQD.PER TABLE
 407 OF SPC.
  
 PRIVATE BATHS SHALL BE HANDICAP
 ADAPTABLE PER FACBC SEC.4.1.3.(11).
  
 STAFF ROOM SINK SHALL COMPLY W/FACBC
 SEC.4.24.1.- 4.24.7.
  
 DRINKING FOUNTAIN SHALL COMPLY W/FACBC
 SEC.4.1.3.(10)(A).
  
 URINAL SHALL COMPLY W/FACBC SEC.4.18.2,
 THRU 4.18.4.
  
 MEN'S R.R.-STALL DOOR CANNOT SWING INTO
 CLEAR FLOOR SPACE FOR URINAL PER FACBC
 SEC.4.22.2.
  
 WALLS AND FLOORS IN TOILET ROOMS SHALL
 COMPLY W/SBC SEC.1204.2.
  
 WATER CLOSETS AND FIXTURE BRANCHES NOT
 PERMITTED ON WET VENTS PER COUNTYWIDE
 AMENDMENTS TO SPC SEC.911.1.1.(SEE
 PRIVATE TOILET ROOMS ON SANITARY RISER.
  
 MAX.OF 2 FIXTURES PERMITTED TO BE
 CONNECTED TO 1/2" C.W.AND 4 FIXTURES TO
 1/2" H.W.PER COUNTYWIDE AMENDMENTS TO
 SPC SEC.607.7.
  
 WATER SUPPLY CONTROL SHALL COMPLY W/SPC
 SEC.610.4.1.,610.4.2.

Review Stop Z ZONING
Rev No 1 Status F Date 1999-12-13 Cont ID  
Sent By gjoyce Date 1999-12-13 Time 11:02 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
2001-01-08 00:00:00NEEDS LANDSCAPE PLAN