Plan Review Details - Permit 99120440
| Plan Review Stops For Permit 99120440 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2000-01-07 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2000-01-07 |
Time |
08:48 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2000-02-03 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-02-03 |
Time |
15:14 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-02-03 |
Time |
15:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
1999-12-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
1999-12-27 |
Time |
13:42 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
1999-12-14 |
|
|
Cont ID |
|
| Sent By |
rturnque |
Date |
1999-12-14 |
Time |
15:12 |
Rev Time |
0.15 |
| Received By |
rturnque |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | EXIT DOOR THROUGH LOUNGE/CONFERENCE RM. | | | SHALL NOT LOCK AGAINST THE MEANS OF | | | EGRESS. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
1999-12-27 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
1999-12-27 |
Time |
15:20 |
Rev Time |
0.33 |
| Received By |
ndenmark |
Date |
1999-12-27 |
Time |
15:20 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | **********PROVISO*********************** | | | | | | 1)PROVIDE EXHAUST FROM JANITORS CLOSET | | | PER 1997 SMC 503.2 | | | 2) EXHAUST DUCT (8") PENETRATING DEMIS- | | | ING WALL TO BE PROTECTED BY FIRE DAMPERS | | | OR COMPLY W/ EXCEPTIONS AND NOTES 1997 | | | SMC 610.1.3(3)1,2,3, AND 4 | | | 3)DUCT SMOKE DETECTORS TO BE TIED TO | | | BLDG FIRE ALARM FOR NOTIFICATION PER | | | NFPA 90A 4-4.4.2 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2000-01-06 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-01-06 |
Time |
06:52 |
Rev Time |
1.00 |
| Received By |
tlarge |
Date |
2000-01-06 |
Time |
06:52 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ******************PROVISO*************** | | | | | | FLOOR DRAIN NOT PERMITTED IN ROOM W/AIR | | | HANDLER IF ROOM IS USED AS PLENUM.SPC | | | SEC.409.4.4.1 | | | | | | HEAT TRAPS REQD.ON EWH PER FEC SEC. | | | 412.1ABCD.2.1.3. | | | | | | WATER HEATER SHALL BE READILY ACCESSIBLE | | | PER SPC SEC.501.7.SUPPLY PERMANENT | | | LADDER AND PLATFORM OR RELOCATE TO FLOOR |
|
|
|