Plan Review Details - Permit 99120416
Plan Review Stops For Permit 99120416
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-01-14 Cont ID  
Sent By hpiskura Date 2000-01-14 Time 14:11 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-12-28 Cont ID  
Sent By dpalmer Date 1999-12-28 Time 11:15 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
2001-01-08 00:00:00***********PROVISO**********************
  
 1)NOTE: PLEASE CORRECT RISER DIAGARM TO
 CORRELATE WITH PANEL SCHEDULES.
 PANEL SCHED. SHOWS 125 AND RISER 225 AND
 PANEL'L' SHOWS 225 AND 125 ON RISER.
  
 PLEASE MAKE CHANGES WITH THE ABOVE IN-
 -FORMATION AND SUBMIT FOR REVIEW AND
 APPROVAL BEFORE FIRST ROUGH ELECTRICAL
 INSPECTION IS CALLLED IN. IF THERE ARE
 ANY QUESTIONS;CALL 659-8096 EXT 8373

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-12-14 Cont ID  
Sent By rturnque Date 1999-12-14 Time 14:28 Rev Time 0.15
Received By rturnque Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVIDE PERMIT AND SHOP DRAWINGS FOR
 FIRE SPRINKLER AND FIRE ALARM REMODEL

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-12-29 Cont ID  
Sent By ndenmark Date 1999-12-29 Time 07:24 Rev Time 0.33
Received By ndenmark Date 1999-12-29 Time 07:24 Sent To  
Notes
2001-01-08 00:00:00***********PROVISO*********************
  
 NOTE: MEDICAL GAS (DENTAL) REQUIRES
 SEPARATE MECHANICAL PERMIT. SUBMIT PLANS
 WITH MECHANICAL PERMIT APPLICATION.

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-01-06 Cont ID  
Sent By tlarge Date 2000-01-06 Time 08:38 Rev Time 0.75
Received By tlarge Date 2000-01-06 Time 08:37 Sent To  
Notes
2001-01-08 00:00:00****************PROVISO*****************
 FLOOR DRAIN W/TRAP PRIMER REQD.IN TOILET
 ROOM PER SPC SEC.409.4.1.1.(EXCEPTION)
  
 A HEATER PAN W/DRAIN SHALL BE INSTALLED
 UNDER WATER HEATER PER COUNTYWIDE AMEND-
 MENTS TO SPC SEC.507.8.1,507.8.3.
  
 FLOOR AND WALLS IN TOILET ROOM SHALL BE
 NONABSORBENT MATERIAL TO A HEIGHT OF 4'
 PER SBC 1204.2.