Plan Review Details - Permit 99120159
Plan Review Stops For Permit 99120159
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-05-18 Cont ID  
Sent By hpiskura Date 2000-05-18 Time 11:28 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-03-09 Cont ID  
Sent By sgraham Date 2000-03-09 Time 09:07 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-01-12 Cont ID  
Sent By dpalmer Date 2000-01-12 Time 16:38 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2000-04-21 Cont ID  
Sent By mgonzale Date 2000-04-21 Time 13:42 Rev Time 1.00
Received By mgonzale Date   Time   Sent To  
Notes
2001-01-08 00:00:00POLLUTION PREVENTION PLANS SUBMITTED AND
 SATISFACTORY. PASSED.ALL ITEMS IN
 PRIOR REVIEW NOTES (ENG1 AND ENG2) HAVE
 BEEN MET.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2000-04-12 Cont ID  
Sent By mgonzale Date 2000-04-12 Time 14:51 Rev Time 2.00
Received By mgonzale Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2000-02-28 Cont ID  
Sent By dlauderm Date 2000-02-28 Time 10:41 Rev Time 2.00
Received By dlauderm Date 2000-02-28 Time 10:41 Sent To  
Notes
2001-01-08 00:00:00FAILED.
 IF THE CONTRACTOR WANTS TO START WORK HE
 CAN GET A BUILDING PERMIT ONLY, THAT
 WOULD NOT COVER ANY OF THE SITE WORK.
 IF HE WANTS A BUILDING PERMIT THEN
 SUBMIT ALL SITE WORK SHEETS SEPARATELY
 AND APPLY FOR A SITE WORK PERMIT AND
 THEY WILL GIVE YOU A BUILDING ONLY
 PERMIT.
  
 WATER AND SANITARY COMMENTS:
 1. A DCDA WILL NEED TO BE INSTALLED AT
 THE PROPERTY LINE ON THE FIRE LINE, IT
 IS NOT A CITY WATER MAIN EXTENSION BUT
 WILL BE CONSIDERED A PRIVATE FIRE LINE.
  
 2. WATER AND SANITARY PLANS SHOULD BE
 SUBMITTED TO B&Z FOR THE BUILDING PERMIT
 THAT ARE ALREADY STAMPED APPROVED BY THE
 PUBLIC UTILITIES DEPARTMENT.
  
 3. A WATER AND SANITARY DEP PERMIT IS
 REQUIRED FOR THIS JOB, UNLESS WE RECEIVE
 A LETTER FROM THE HEALTH DEPARTMENT
 SAYING THAT A PERMIT IS NOT REQUIRED.
  
 STORM WATER REQUIREMENTS:
 TO OBTAIN A CONSTRUCTION PERMIT THE
 FOLLOWING MUST BE SUBMITTED SIGNED AND
 SEALED BY A FLORIDA PROFESSIONAL
 ENGINEER (PE).
  
 1.CONSTRUCTION PLANS.
  
 2.DETAILS AND SPECIFICATIONS.
  
 3.HYDRAULIC COMPUTATIONS AND SUPPORTING
 DOCUMENTATION.
  
 4.IMPERVIOUS AREA COMPUTATIONS.
  
 5.POLLUTION PREVENTION PLAN.THE
 POLLUTION PREVENTION PLAN SHALL BE KEPT
 ON SITE AT ALL TIMES DURING
 CONSTRUCTION. THE PLAN SHALL BE
 INSTALLED IN THE FIELD PRIOR TO ANY
 EARTHWORK. THE ENGINEER OF RECORD SHALL
 CERTIFY TO THE CITY, ON A MONTHLY BASIS,
 THAT THE PLAN IS WORKING PROPERLY AND AS
 DESIGNED. THE ENGINEER OF RECORD IS
 RESPONSIBLE TO CERTIFY IMPLEMENTATION OF
 THE PROVISIONS OF CITY ORDINANCE NO.
 3132-98 OF THE CITY CODE AT SUCH TIME
 THE PERMITTEE APPLIES FOR A CERTIFICATE.
  
 OF OCCUPANCY FROM THE CITY BUILDING
 OFFICIAL.
  
 6.EVERY SIX MONTHS AFTER CONSTRUCTION A
 PE SHALL CERTIFY THAT THE PERMANENT
 POLLUTION PREVENTION STRUCTURES, DRY-WET
 WATER DETENTION FACILITIES, AND
 EXFILTRATION SYSTEMS ARE WORKING AS
 DESIGNED AND ARE IN GOOD OPERATING
 CONDITION.
  
 ALL CERTIFICATIONS MUST BE SUBMITTED TO:
 STORM WATER UTILITY ENGINEER
 CITY OF WEST PALM BEACH PUBLIC UTILITIES
 DEPARTMENT
 P.O. BOX 3366, WEST PALM BEACH, FL
 33402.
  
 THE CERTIFICATION MUST INCLUDE THE
 BUILDING PERMIT NUMBER, THE ADDRESS OF
 THE PROPERTY AND THE NAME OF THE
 ESTABLISHMENT/PROJECT CONSTRUCTED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-07-11 Cont ID  
Sent By rturnque Date 2000-07-11 Time 13:36 Rev Time 0.20
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-12-16 Cont ID  
Sent By rturnque Date 1999-12-16 Time 10:54 Rev Time 0.35
Received By rturnque Date   Time   Sent To  
Notes
2001-01-08 00:00:001. THE MAXIMUM HEIGHT OF STAIR RISERS IS
 7 INCHES.
 2. PROVIDE PROTECTED SINGLE MEANS OF
 EGRESS FROM MEZZANINE IF USED FOR OTHER
 THAN DEAD STORAGE.
 3. FIRE ALARM SYSTEM SHALL BE CLASS"A"
 OR ADDRESSABLE.
 4. FIRE HYDRANT SHALL BE WITHIN 150 FEET
 OF FIRE DEPARTMENT CONNECTION.
 5. PROVIDE PERMIT AND SHOP DRAWINGS FOR
 FIRE SPRINKLER AND FIRE ALARM SYSTEMS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-12-27 Cont ID  
Sent By ndenmark Date 1999-12-27 Time 08:36 Rev Time 0.50
Received By ndenmark Date 1999-12-27 Time 08:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2000-04-04 Cont ID  
Sent By tlarge Date 2000-04-18 Time 09:41 Rev Time 2.50
Received By tlarge Date 2000-04-18 Time 09:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2000-03-02 Cont ID  
Sent By tlarge Date 2000-03-02 Time 10:00 Rev Time 3.50
Received By tlarge Date 2000-03-02 Time 10:00 Sent To  
Notes
2001-01-08 00:00:00JOB SPEC.02700-6-SEC.2.11-MATERIALS
 SHALL COMPLY W/STANDARDS REFERENCED IN
 SPC SEC.1402.(SEE ASTM C 478).
  
 JOB SPEC.15440-1-SEC.1.03-FIXTURES SHALL
 COMPLY W/ SEC.406 OF SPC(WATER SAVING).
 SCHEDULE ON P-1 DOESN'T SPECIFY.
  
 INDICATE WATER SOURCE FOR IRRIGATION
 SYSTEM.IF FROM AN ARTIFICIAL BODY OF
 WATER OR WELL,A WATER USE PERMIT FROM
 SFWMD SHALL BE REQUIRED PER F.S.373.219.
  
 A RAIN SENSOR IS REQUIRED ON THE
 IRRIGATION SYSTEM PER F.S.373.62.
  
 SINK IN KITCHEN AND COMMON AREA SHALL
 COMPLY W/FACBC SECS.4.24.1-4.24.7.
  
 SUBMIT INFORMATION ON THE TYPE OF
 MATERIALS BEING STORED IN THE WAREHOUSE.
 AN EMERGENCY SHOWER MAY BE REQD. PER
 TABLE 407.
  
 SUBMIT OCCUPANT LOAD ON THE PLANS.
 DOCUMENTATION SHALL BE SUBMITTED BY
 OWNER AS PER OCCUPANT CONTENT PER SHIFT
 PER TABLE 407 OF SPC.
  
 WATER SUPPLY CONTROL SHALL COMPLY W/SPC
 SEC.610.4.1,610.4.2.
  
 VENTS THRU ROOF SHALL NOT BE INCREASED
 IN SIZE PER SPC SEC.905.2.(APPROVED ONLY
 WHERE FROST IS A PROBLEM.)
  
 SUBMIT ELEVATION DETAIL OF DRINKING
 FOUNTAIN.COMPLY W/FACBC SEC.4.15 AND
 FIGURE 27.

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-01-08 Cont ID  
Sent By tlarge Date 2000-01-08 Time 13:55 Rev Time 0.00
Received By tlarge Date 2000-01-08 Time 13:55 Sent To  
Notes
2001-01-08 00:00:00SHOW LOCATION OF ROOF DRAINS ON ARCH.
 PLAN AND SUBMIT STORM DRAINAGE ISOMETRIC
 FOR REVIEW.SHOW SQ.FOOTAGE DRAINED BY
 EACH DRAIN.COMPLY W/SB SEC.1517.6.4.1.,
 1517.6.4.2.,1517.6.4.3.,TABLE 1108.1,
 1108.2.
  
 PROVIDE DETAILS FOR SECONDARY DRAINAGE.
 COMPLY W/SPC SEC.1109.2,1109.3,AND
 APPENDIX "A",SEC.A101.2 AND TABLE A101.2
  
 FLUSH CONTROLS FOR HANDICAP WATER CLOSET
 SHALL BE LOCATED ON WIDE SIDE PER FACBC
 SEC.4.16.5.
  
 FLOOR DRAIN NOT PERMITTED IN MECHANICAL
 ROOM W/AIR HANDLER WHEN ROOM IS USED AS
 PLENUM PER SPC SEC.409.4.4.1.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-01-08 Cont ID  
Sent By tlarge Date 2000-01-08 Time 12:41 Rev Time 4.50
Received By tlarge Date 2000-01-08 Time 12:41 Sent To  
Notes
2001-01-08 00:00:00JOB SPEC.02700-6-SEC.2.09(B)-MATERIALS
 SHALL COMPLY W/STANDARDS REFERENCED IN
 SPC SEC.1402.
  
 JOB SPEC.02700-7-SEC.2.10-DELETE "CITY
 OF BOCA RATON"FROM SPEC.COMPLY W/CITY OF
 WEST PALM BEACH REQS.
  
 JOB SPEC.02700-7-SEC.2.11-MANHOLES TO
 COMPLY W/SEC.1402 OF SPC.
  
 JOB SPEC.15408-1-SEC.1.03-INSERT 1994
 EDITION OF STANDARD PLUMBING CODE PER
 COUNTYWIDE AMENDMENTS TO SPC SEC.100.
  
 JOB SPEC.15408-2-SEC.1.03(A)-SLOPE OF
 SANITARY DRAINAGE PIPE SHALL COMPLY W/
 SPC SEC.705.
  
 JOB SPEC.15440-1-SEC.1.03-FIXTURES SHALL
 COMPLY W/SEC.406 OF SPC.(WATER SAVING).
  
 JOB SPEC.15992-3-SEC.1.06,1.07-TESTING
 OF SANITARY AND WATER SYSTEMS SHALL
 COMPLY W/SPC SECS.311.1.2.1,311.3
  
 INDICATE OCCUPANT LOAD FOR COMPLIANCE
 W/TABLE 407 OF SPC.
  
 INDICATE WATER SUPPLY SOURCE FOR IRRIG.
 SYSTEM.IF FROM AN ARTIFICIAL BODY OF
 WATER OR WELL A WATER USE PERMIT FROM
 SFWMD SHALL BE REQD.PER F.S.373.219.
  
 A RAIN SENSOR IS REQD.ON THE IRRIGATION
 SYSTEM PER F.S.373.62.
  
 KIT.SINK SHALL COMPLY W/FACBC SEC.4.24.1
 THRU 4.24.7.
  
 HANDICAP STALLS SHALL COMPLY W/FACBC
 SEC.4.17.3.(A LAVATORY IS REQD.WITHIN
 THE STALL-SEE EXCEPTION:NEW CONSTRUCTION
  
 DRINKING FOUNTAINS SHALL COMPLY W/FACBC
 SEC.4.1.3.(10)(A).PROVISIONS REQD.FOR
 PERSONS HAVING TROUBLE BENDING OR STOOP-
 ING.
  
 SIZE OF HANDICAP STALLS SHALL COMPLY W/
 FACBC SEC.4.17.3 AND FIGURE 28.
  
 URINAL SHALL BE SET AT HANDICAP HEIGHT.
 COMPLY W/FACBC SEC.4.18 FOR REQS.AND
 CLEAR FLOOR SPACE.
  
 SHT.7A-4-HEIGHT OF W.C.'S SHALL COMPLY
 W/FACBC SEC.4.16.3.AND FIGURE 28.(SPACE
 FROM FINISH WALL).
  
 EMERG.SHOWER REQD.IN WAREHOUSE PER SPC
 TABLE 407.(SEE FOOTNOTE #14 ALSO.)
  
 SHT.7-S7-PLAN SHOWS PVC DRAINS BY DIS-
 PENSERS.SHOW TERMINATION POINT.AN INTER-
 CEPTOR MAY BE REQD.SPC SEC.1004.1.
  
 SHT.7-P1-WATER HEATER SHALL BE READILY
 ACCESSIBLE PER SPC SEC.501.7.SUPPLY A
 FIXED LADDER OR RELOCATE WATER HEATER TO
 FLOOR.
  
 RELIEF DRAIN AND PAN DRAIN SHALL NOT USE
 COMMON RISER PER COUNTYWIDE AMENDMENT TO
 SPC SEC.507.8.3.,507.8.4.
  
 SHT.7P-2-NOTE #3-FLOOR SINK OR FLOOR
 DRAIN SHALL BE INSTALLED IN LIEU OF HUB
 DRAIN.
  
 SHT.7P-2-NOTE#6-BACKWATER VALVE SHALL BE
 ACCESSIBLE PER SPC SEC.1112.5.
  
 SHT.7P-2-DETAIL #6-VENTS THRU ROOF SHALL
 NOT INCREASE IN SIZE PER SPC 905.2,918.
 SEE 7P-3-DETAIL#4 ALSO.
  
 SHT.7P-2-DETAILS#3 & #5-WATER SUPPLY
 SHALL COMPLY W/SPC SECS.610.4.1.&
 610.4.2.
  
 SHT.7P-3-WATER CLOSETS AND FIXTURE
 BRANCHES NOT PERMITTED ON WET VENT PER
 COUNTYWIDE AMENDMENTS TO SPC SEC.911.1.1
  
 VENTING SYSTEM SHALL BE SIZED PER SPC
 TABLE 920.2.9 SEE AREA AT BACK TO BACK
 WATER CLOSETS.
  
 COMMENTS CONTINUED ON SECOND PLBG.STEP.

Review Stop Z ZONING
Rev No 1 Status P Date 1999-12-08 Cont ID  
Sent By gjoyce Date 1999-12-08 Time 16:17 Rev Time 0.75
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***