Plan Review Details - Permit 99120128
Plan Review Stops For Permit 99120128
Review Stop E ELECTRICAL
Rev No 4 Status P Date 2000-05-31 Cont ID  
Sent By dpalmer Date 2000-05-31 Time 07:43 Rev Time 0.00
Received By dpalmer Date 2000-05-31 Time 07:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-02-12 Cont ID  
Sent By dpalmer Date 2000-02-12 Time 08:14 Rev Time 0.00
Received By dpalmer Date 2000-02-12 Time 08:14 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2000-02-07 Cont ID  
Sent By dpalmer Date 2000-02-07 Time 14:59 Rev Time 0.00
Received By dpalmer Date 2000-02-07 Time 14:59 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE: STILL NEED TO SUBMIT THE AIC
 RATINGS FOR EQUIPMENT MAINS!!!
 MUST BE RATED FOR THE AVAILABLE FAULT
 CURRENT SET FORTH BY FPL. PER 110-9/110-
 -10 OF THE NEC.
  
 ALSO PLEASE LALEL ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS BEING GFI/GFI
 PROTECTED. PER 210-8-A-6
  
 NEED TO SUBMIT ALL THE ABOVE INFORMAITON
 FOR REVIEW AND APPROVAL. IF THERE ARE
 ANY QUESTION PLEASE CALL. 659-8096 X8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 1999-12-29 Cont ID  
Sent By dpalmer Date 1999-12-29 Time 16:35 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
2001-01-08 00:00:00**************UNSAT*******************
  
 1)NOTE:PLEASE SUBMIT AIC RATING OF ALL
 EQUIPMENT MAINS AND BRKRS. AIC RATING IS
 FIGURED FROM FAULT CURRENT CALCULATIONS.
 REQ`D PER 230-65/110-9/215-5
  
 2)NOTE: AS REQ`D BY 210-52E WP GFI REC.
 ARE TO BE INSTALLED FRONT AND BACK OF
 ALL DWELLING UNITS.
  
 3)NOTE:REQ`D AS PER 210-63 WP GFI REC.
 FOR ALL A/C EQUIPMENT.
  
 4)NOTE:PLEASE LIST ON PANEL SCHEDULES
 CIRCUT(S) REQ`D FOR BATH(S) AS PER
 210-52D /215-5
  
 5)NOTE:AS REQ`D BY 250-81 AND 215-5
 PLEASE SHOW GROUNDING ELECTRODE CONDUCT-
 -OR GOING TO BLDG. STEEL ALSO.
  
 6)NOTE: NEED TO SHOW HOW THE GENERATOR
 CONNECTS WITH THE RISER/PANELS ??????
 TRANSFER SWITCH? DISCS? ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW AND APPROVAL. IF THERE ARE
 ANY QUESTIONS CALL 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-12-21 Cont ID  
Sent By cthirben Date 1999-12-21 Time 14:15 Rev Time 1.00
Received By cthirben Date 1999-12-21 Time 14:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-02-07 Cont ID  
Sent By tlarge Date 2000-02-07 Time 14:35 Rev Time 0.33
Received By tlarge Date 2000-02-07 Time 14:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 1999-12-20 Cont ID  
Sent By tlarge Date 1999-12-20 Time 11:30 Rev Time 0.00
Received By tlarge Date 2000-02-07 Time 14:36 Sent To  
Notes
2001-01-08 00:00:00LOCATION OF PLBG.FIXTURES ON SANITARY
 RISER SHALL MATCH FLOOR PLAN PER COUNTY
 WIDE AMENDMENTS TO SPC SEC.104.2.1.
  
 WATER CLOSETS AND FIXTURE BRANCHES NOT
 PERMITTED ON WET VENTS PER COUNTYWIDE
 AMENDMENTS TO SPC SEC.911.1.1
  
 FIXTURES DOWNSTREAM OF WATER CLOSETS
 SHALL BE VENTED PER SPC SEC.913.2.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2000-04-25 Cont ID  
Sent By rmcdouga Date 2000-04-25 Time 13:29 Rev Time 1.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-01-08 00:00:00****************UNSAT*******************
 TRUSS SHOP DRAWINGS
 1)ENGINEERED TRUSS PLANS NEED TO BE
 SIGNED,SEALED AND DATED
  
 2)ENGINEERED TRUSS PLAN LAYOUT DOES NOT
 CORRESPOND WITH ARCHITECTURAL TRUSS
 DRAWINGS.SUBMIT REVISED DRAWINGS.
  
 3)SPECIFY CONNECTORS TO BE USED FOR T31,
 T30,T32,GTX,GT1,MGT1,HHGT1,FGT4,T17
 AND ALL OTHERS NOT SHOWN ON SHEET A-7
 OF ARCHITECTURAL PLANS.
  
 4)SHOP DRAWINGS INCORRECTLY REFER TO
 1997 SBCCI DESIGN; CORRECT DESIGN
 STANDARD IS 1997 SBC (STANDARD
 BUILDING CODE)

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2000-01-11 Cont ID  
Sent By fknapp Date 2000-01-11 Time 13:52 Rev Time 4.00
Received By fknapp Date 2000-01-11 Time 11:51 Sent To  
Notes
2001-01-08 00:00:00 
  
 *****************PROVISO****************
  
 SBC 104.2.2
  
 1)PROVIDE ENGINEERING FOR BUTT GLASS
 OPENINGS.
  
 2)PROVIDE MISSILE IMPACT PROTECTION
 INFORMATION FOR ALL NON-IMPACT OPENINGS
 UNDER SEPERATE PERMIT.
  
 PLEASE SUBMIT PRIOR TO INSTALLATION
  
 3)PROVIDE SOIL REPORT PRIOR TO FIRST
 INSPECTION.

Review Stop Z ZONING
Rev No 1 Status P Date 1999-12-13 Cont ID  
Sent By gjoyce Date 1999-12-13 Time 11:10 Rev Time 0.50
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***