| 2001-01-08 00:00:00 | ************UNSAT*********************** |
| | |
| | 1)NOTE:AS PER 250-81/215-5 NEED TO SHOW |
| | BLDG.STEEL AS PART OF THE GROUNDING |
| | ELECTRODE SYSTEM.ALSO GOING TO METERCAN. |
| | |
| | 2)NOTE: AS PER 210-8-A-6 ALL OUTLETS |
| | SERVING KITCHEN COUNTERSPACE ARE TO BE |
| | GFI/GFI PROTECTED. PLEASE SHOW. |
| | |
| | 3)NOTE: AS PER 1993/1996 NFPA-72 CHAPTER |
| | 2-2.1.1.1 SMOKE DETECTORS ARE REQ`D |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS |
| | OF NEW DWELLINGS. |
| | |
| | 4)NOTE: PLEASE SHOW ON PANEL SCHEDULE |
| | DEDICATED CIRCUT(S) FOR BATH(S) REQ`D BY |
| | 210-52D ALSO LABEL ALL BATH RECEPTS.GFI |
| | |
| | 5)NOTE:MISSING WP GFI RECEPTS REQ`DFOR |
| | A/C COND. UNITS AS PER 210-63 |
| | |
| | 6)NOTE:MISSING GFI RECEPT REQ`D FOR |
| | GARAGE AS PER 210-52G |
| | |
| | 7)NOTE:MISSING RECEPTS FOR FRONT AND |
| | BACK OF DWELLING.AS PER 210-52E |
| | |
| | 8)NOTE:PLEASE SUBMIT AIC RATING OF ALL |
| | EQUIPMENT,MAINS AND BRKRS. AIC RATING IS |
| | FIGURED FROM FAULT CURRENT CALCULATIONS. |
| | REQ` PER 110-9/215-5. |
| | |
| | 9)NOTE: PLEASE CORRECT PANEL SHOWING |
| | AMPS INSTEAD OF VOLTS. 215-5 |
| | |
| | 10)NOTE:LOAD ON PANEL 'B' IS TO INCLUDE |
| | LOAD OF PANEL 'C'.ALSO 40% OF LOAD ON |
| | PANEL 'C' IS NOT 361WATTS. PLEASE MAKE |
| | CHANGE. PLEASE REFIGURE LOAD CALCULATION |
| | -S ON PANEL'A', 'B',AND 'C', |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW AND APPROVAL. IF YOU HAVE ANY |
| | QUESTIONS PLEASE CALL AT 659-8096 |
| | EXT 8372 |