Plan Review Details - Permit 99120126
Plan Review Stops For Permit 99120126
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-03-14 Cont ID  
Sent By dpalmer Date 2000-03-14 Time 19:28 Rev Time 0.00
Received By dpalmer Date 2000-03-14 Time 19:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 1999-12-13 Cont ID  
Sent By dpalmer Date 1999-12-13 Time 07:44 Rev Time 0.00
Received By dpalmer Date 1999-12-13 Time 10:00 Sent To  
Notes
2001-01-08 00:00:00************UNSAT***********************
  
 1)NOTE:AS PER 250-81/215-5 NEED TO SHOW
 BLDG.STEEL AS PART OF THE GROUNDING
 ELECTRODE SYSTEM.ALSO GOING TO METERCAN.
  
 2)NOTE: AS PER 210-8-A-6 ALL OUTLETS
 SERVING KITCHEN COUNTERSPACE ARE TO BE
 GFI/GFI PROTECTED. PLEASE SHOW.
  
 3)NOTE: AS PER 1993/1996 NFPA-72 CHAPTER
 2-2.1.1.1 SMOKE DETECTORS ARE REQ`D
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS
 OF NEW DWELLINGS.
  
 4)NOTE: PLEASE SHOW ON PANEL SCHEDULE
 DEDICATED CIRCUT(S) FOR BATH(S) REQ`D BY
 210-52D ALSO LABEL ALL BATH RECEPTS.GFI
  
 5)NOTE:MISSING WP GFI RECEPTS REQ`DFOR
 A/C COND. UNITS AS PER 210-63
  
 6)NOTE:MISSING GFI RECEPT REQ`D FOR
 GARAGE AS PER 210-52G
  
 7)NOTE:MISSING RECEPTS FOR FRONT AND
 BACK OF DWELLING.AS PER 210-52E
  
 8)NOTE:PLEASE SUBMIT AIC RATING OF ALL
 EQUIPMENT,MAINS AND BRKRS. AIC RATING IS
 FIGURED FROM FAULT CURRENT CALCULATIONS.
 REQ` PER 110-9/215-5.
  
 9)NOTE: PLEASE CORRECT PANEL SHOWING
 AMPS INSTEAD OF VOLTS. 215-5
  
 10)NOTE:LOAD ON PANEL 'B' IS TO INCLUDE
 LOAD OF PANEL 'C'.ALSO 40% OF LOAD ON
 PANEL 'C' IS NOT 361WATTS. PLEASE MAKE
 CHANGE. PLEASE REFIGURE LOAD CALCULATION
 -S ON PANEL'A', 'B',AND 'C',
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW AND APPROVAL. IF YOU HAVE ANY
 QUESTIONS PLEASE CALL AT 659-8096
 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-12-09 Cont ID  
Sent By cthirben Date 1999-12-09 Time 12:25 Rev Time 1.00
Received By cthirben Date 2000-03-15 Time 11:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-03-15 Cont ID  
Sent By tlarge Date 2000-03-15 Time 09:46 Rev Time 0.33
Received By tlarge Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 1999-12-09 Cont ID  
Sent By tlarge Date 1999-12-09 Time 06:52 Rev Time 0.65
Received By tlarge Date 1999-12-09 Time 06:52 Sent To  
Notes
2001-01-08 00:00:00LOCATION OF FIXTURES ON SANITARY RISER
 SHALL MATCH FLOOR PLAN PER CITY OF WPB
 AMENDMENTS TO SPC SEC.104.2.1.
  
 TUB ,SHOWER AND BIDET NOT PROPERLY
 VENTED.SPC SEC.901.2.
  
 MAIN VENT THRU ROOF REQD.PER SPC SEC.
 904.3.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2000-03-20 Cont ID  
Sent By fknapp Date 2000-03-20 Time 11:01 Rev Time 2.00
Received By fknapp Date 2000-03-20 Time 11:01 Sent To  
Notes
2001-01-08 00:00:00 
  
 ****************PROVISO*****************
  
 SBC 104.2.2
  
 1)PROVIDE DETAILS OF TOWER ABOVED GARAGE
  
 2)PROVIDE 32" CLEAR OPENING AT FRONT
 ENTRY DOOR. SBC 1012.1.1
  
 3)PROVIDE IMPACT RESISTANT GLASS FOR ALL
 GLAZING.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2000-01-11 Cont ID  
Sent By fknapp Date 2000-01-11 Time 10:48 Rev Time 4.00
Received By fknapp Date 2000-01-10 Time 14:02 Sent To  
Notes
2001-01-08 00:00:00 
  
 ****************PROVISO*****************
  
 SBC 104.2.2
  
 1)PROVIDE 2 CURRENT COPIES OF PRODUCT
 APPROVALS FOR UL LISTED FIREPLACE
  
 2)PROVIDE SAFETY GLASS IN LOCATIONS AS
 REQUIRED SBC 2405.2.1(3)
  
 3)PROVIDE 32" CLEAR OPENING AT FRONT
 ENTRY SBC 1012.1.1
  
 4)PROVIDE MISSILE IMPACT PROTECTION
 INFORMATION UNDER SEPERATE PERMIT
  
 PLEASE SUBMIT PRIOR TO INSTALLATION

Review Stop Z ZONING
Rev No 1 Status P Date 1999-12-08 Cont ID  
Sent By gjoyce Date 1999-12-08 Time 10:30 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***