| 2001-01-08 00:00:00 | ************** PROVISO **************** |
| | |
| | ***BEFORE FIRST INSPECTION SI CALLED IN* |
| | |
| | 1)NOTE:PLEASE CHECK REQ`MENTS FOR |
| | KITCHEN OUTLETS FOR PENINSULAR AND |
| | ISLAND AS PER ART: 210-52-C-2-3 |
| | |
| | 2)NOTE:ALSO AS PER 210-8-A-6 ALL OUTLETS |
| | SERVING KITCHEN COUTNTERSPACE ARE TO BE |
| | GFI /GFI PROTECTED. |
| | |
| | 3)NOTE:AS PER 210-52D 1996 NEC REQ`S |
| | BATH(S) TO BE ON 20AMP DEDICATED CIRCUT. |
| | NO LIGHTING IS TO BE PLACED ON BATH |
| | CIRCUTS. |
| | |
| | 4)NOTE: AS PER 1993/1996 NFPA-72 |
| | 2-2.1.1.1 SMOKE DETECTORS ARE REQ`D |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS!! |
| | IF THEY ARE ROOMS WITH CLOSET SPACE THEN |
| | THEY ARE TO ALSO MEET THE REQ`MENT. |
| | |
| | 5)NOTE: AS PER 250-81/215-5 NEED TO SHOW |
| | COMPLETE GROUNDING ELECTRODE SYSTEM. |
| | TO INCLUDE GROUND ROD,BLDG.STEEL AND |
| | COLD WATER PIPE AS PART OF THE SYSTEM. |
| | |
| | 6)NOTE: NEEDTO SHOW CONDUCTOR SIZE OF |
| | THE GROUNDING ELECTRODE. SIZE PER 250-94 |
| | |
| | 7)NOTE: NEED TO SHOW ALL CONDUCTORS FOR |
| | SERVICE.!!! FROM METER TO PANELS. SHOW |
| | CONDUIT SIZES. SHOW METER CAN SIZE. |
| | IF THERE ARE TWO PANELS THEN SHOW TWO |
| | FEEDS TO PANELS. PANEL B CANNOT BEFED |
| | THROUGH PANEL A AS PER 373-8/215-5 |
| | PLEASE INCLUDE GROUNDING CONDUTORS IN |
| | ALL CONDUITS.EG. A/C FEEDS. |
| | |
| | 8)NOTE: NEED TO SUBMIT AIC RATING OF |
| | ALL EQUIPMENT. TO INCLUDE MAINS AND |
| | BRKRS. AIC IS FIGURED FROM FAULT CURRENT |
| | CALCULATIONS. AS PER 110-9/215-5 |
| | |
| | PLEASE SUBMIT THE ABOVE FOR REVIEW AND |
| | APPROVAL BEFORE FIRST ROUGH ELECTRICAL |
| | INSPECTION IS CALLED IN. PLEASE SUBMIT |
| | PLANS FOR NOTES :5,6,7,AND 8 WITHIN 20 |
| | DAYS OF RECIEPT OF NOTES. IF THERE ARE |
| | ANY QUESTIONS PLAESE CALL AT 659-8096 |
| | EXT 8372 |