Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-12-13 Cont ID  
Sent By dpalmer Date 1999-12-13 Time 06:32 Rev Time 0.00
Received By dpalmer Date 1999-12-13 Time 06:31 Sent To  
Notes
2001-01-08 00:00:00************** PROVISO ****************
  
 ***BEFORE FIRST INSPECTION SI CALLED IN*
  
 1)NOTE:PLEASE CHECK REQ`MENTS FOR
 KITCHEN OUTLETS FOR PENINSULAR AND
 ISLAND AS PER ART: 210-52-C-2-3
  
 2)NOTE:ALSO AS PER 210-8-A-6 ALL OUTLETS
 SERVING KITCHEN COUTNTERSPACE ARE TO BE
 GFI /GFI PROTECTED.
  
 3)NOTE:AS PER 210-52D 1996 NEC REQ`S
 BATH(S) TO BE ON 20AMP DEDICATED CIRCUT.
 NO LIGHTING IS TO BE PLACED ON BATH
 CIRCUTS.
  
 4)NOTE: AS PER 1993/1996 NFPA-72
 2-2.1.1.1 SMOKE DETECTORS ARE REQ`D
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS!!
 IF THEY ARE ROOMS WITH CLOSET SPACE THEN
 THEY ARE TO ALSO MEET THE REQ`MENT.
  
 5)NOTE: AS PER 250-81/215-5 NEED TO SHOW
 COMPLETE GROUNDING ELECTRODE SYSTEM.
 TO INCLUDE GROUND ROD,BLDG.STEEL AND
 COLD WATER PIPE AS PART OF THE SYSTEM.
  
 6)NOTE: NEEDTO SHOW CONDUCTOR SIZE OF
 THE GROUNDING ELECTRODE. SIZE PER 250-94
  
 7)NOTE: NEED TO SHOW ALL CONDUCTORS FOR
 SERVICE.!!! FROM METER TO PANELS. SHOW
 CONDUIT SIZES. SHOW METER CAN SIZE.
 IF THERE ARE TWO PANELS THEN SHOW TWO
 FEEDS TO PANELS. PANEL B CANNOT BEFED
 THROUGH PANEL A AS PER 373-8/215-5
 PLEASE INCLUDE GROUNDING CONDUTORS IN
 ALL CONDUITS.EG. A/C FEEDS.
  
 8)NOTE: NEED TO SUBMIT AIC RATING OF
 ALL EQUIPMENT. TO INCLUDE MAINS AND
 BRKRS. AIC IS FIGURED FROM FAULT CURRENT
 CALCULATIONS. AS PER 110-9/215-5
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW AND
 APPROVAL BEFORE FIRST ROUGH ELECTRICAL
 INSPECTION IS CALLED IN. PLEASE SUBMIT
 PLANS FOR NOTES :5,6,7,AND 8 WITHIN 20
 DAYS OF RECIEPT OF NOTES. IF THERE ARE
 ANY QUESTIONS PLAESE CALL AT 659-8096
 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-12-09 Cont ID  
Sent By cthirben Date 1999-12-09 Time 12:05 Rev Time 1.00
Received By cthirben Date 1999-12-09 Time 12:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-12-09 Cont ID  
Sent By tlarge Date 1999-12-09 Time 06:41 Rev Time 0.50
Received By tlarge Date 1999-12-09 Time 06:41 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2000-03-10 Cont ID  
Sent By fknapp Date 2000-03-10 Time 11:18 Rev Time 2.00
Received By fknapp Date 2000-03-10 Time 11:18 Sent To  
Notes
2001-01-08 00:00:00APPROVED PER JC NOTES

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2000-02-28 Cont ID  
Sent By fknapp Date 2000-02-28 Time 14:50 Rev Time 1.00
Received By fknapp Date 2000-02-28 Time 14:50 Sent To  
Notes
2001-01-08 00:00:00 
  
 ****************DENIED******************
  
 SEE NOTES FROM JC

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-01-07 Cont ID  
Sent By jcaloger Date 2000-01-07 Time 13:49 Rev Time 3.00
Received By jcaloger Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVIDE DESIGN CERTIFICATION FORM.
  
 PLAN S3,SPECIFYS THE INCORRECT CODE
 EDITION WAS USED.NOTE THE VALID CODE
 EDITION IS THE 1997 STANDARD BUILDING
 CODE.
  
 PROVIDE MANUAL J CALCULATIONS WITH THE
 ENERGY FORM.
  
 PROVIDE A DETAIL FOR ATTACHING THE
 WINDOW & DOOR SUB-BUCKS.
  
 PROVIDE PRODUCT APPROVAL FOR THE WINDOWS
 EXTERIOR DOORS, OVERHEAD GARAGE DOOR,
 ROOF TILES, FIREPLACE AND HURRICANE
 MISSLE IMPACT PROTECTION.SECT 1707.4 AME
  
 PLANS NEED PALM BEACH COUNTY IMPACT FEE
 REVIEW.
  
 SPECIFY ON S1 PLAN THAT ALL FOOTERS ARE
 REQUIRED TO BE A MININUM OF 12" BELOW
 GRADE. SECT 1804.1.3SBC 1997

Review Stop Z ZONING
Rev No 1 Status P Date 1999-12-07 Cont ID  
Sent By gjoyce Date 1999-12-07 Time 13:47 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***