| Plan Review Stops For Permit 99120033 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
1999-12-01 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
1999-12-01 |
Time |
15:16 |
Rev Time |
0.30 |
| Received By |
jleahy |
Date |
1999-12-01 |
Time |
15:12 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1- SUBMIT LOAD CALCS. FOR UNITS | | | 2- NEED BRANCH CIRCUIT NUMBERS FOR THE | | | ELECTRICAL WORK SHOWN ON PLAN | | | 3- NEED SERVICE OUTLET AT EACH LOCATION | | | FOR ACS | | | 4- SERVICE OUTLET IS TO BE GFI PROTECTED | | | 5- PROVIDE THIS INFORMATION PRIOR TO | | | ANY ELECTRICAL INSPECTIONS |
|
|
|