Plan Review Details - Permit 99111482
Plan Review Stops For Permit 99111482
Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-12-14 Cont ID  
Sent By dpalmer Date 1999-12-14 Time 06:33 Rev Time 0.00
Received By dpalmer Date 1999-12-14 Time 06:33 Sent To  
Notes
2001-01-08 00:00:00**************PROVISO*****************
  
 1)NOTE: NEED TO SUBMIT AIC RATING OF
 EQUIPMENT, MAINS AND BRKRS. AIC RATING
 IOS FIGURED FROM FAULT CURRENT
 CALCULATIONS. AS PER 110-9/215-5
  
 2)NOTE: SUBMIT REVISED RISER DIAGRAM
 TO INCLUDE SIZE OF WIRE ,CONDUITS.ALSO
 PLEASE INDICATE ON PANEL MCB.
  
 3)NOTE: SUBMIT RISER DIAGRAM SHOWING
 COMPLETE GROUNDING SYSTEM AS PER THE
 NEC 250-81/215-5 SHOW GROUND RODS,
 COLD WATER PIPE AND IF ANY BLDG.STEEL
 BEING BONDED.
  
 4)NOTE: AS PER 210-8-A-6 ALL OUTLETS
 SERVING KITCHEN COUNTERSPPACE ARE TO BE
 GFI/GFI PPROTECTED. PLEASE SHOW ALL OUT-
 -LETS AS GFI.
  
 5)NOTE: AS PER 210-52D PLEASE SHOW REQ`D
 DEDICATED CIRCUT FOR BATH(S) AND SHOW
 ON PANEL SCHEDULE. TO BE 20AMP AND #12
 AWG.
  
 PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW AND APPROVAL BEFORE FIRTST
 ROUGH ELECTRICAL INSPECTION IS CALLED IN
 IF THERE ARE ANY QUESTIONS PLEASE CALL
 659-8096 EXT 8372.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-08-10 Cont ID  
Sent By cthirben Date 2000-08-10 Time 11:00 Rev Time 1.00
Received By cthirben Date 2000-08-10 Time 11:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-12-10 Cont ID  
Sent By cthirben Date 1999-12-10 Time 11:48 Rev Time 0.50
Received By cthirben Date 1999-12-10 Time 11:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-05-30 Cont ID  
Sent By tlarge Date 2000-05-30 Time 08:09 Rev Time 0.30
Received By tlarge Date 2000-05-30 Time 08:09 Sent To  
Notes
2001-01-08 00:00:00INSTALLATION OF SANITARY SYSTEM FOR
 UPPER FLOORS SHALL COMPLY W/SPC SEC.
 912.2,910.2.,
  
 WATER CLOSETS NOT PERMITTED ON COMBIN-
 ATION WASTE AND VENT SYSTEM.SPC SEC.
 911.4.

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-12-09 Cont ID  
Sent By tlarge Date 1999-12-09 Time 08:08 Rev Time 0.33
Received By tlarge Date 1999-12-09 Time 08:08 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2000-06-09 Cont ID  
Sent By fknapp Date 2000-05-19 Time 15:48 Rev Time 1.00
Received By fknapp Date 2000-05-19 Time 15:48 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2000-01-31 Cont ID  
Sent By fknapp Date 2000-01-31 Time 09:16 Rev Time 3.00
Received By fknapp Date 2000-01-31 Time 09:16 Sent To  
Notes
2001-01-08 00:00:00 
  
 ****************PROVISO*****************
  
 SBC 104.2.2
  
 1)PROVIDE 2 CURRENT COPIES OF PRODUCT
 APPROVALS FOR FRONT DOOR ASSEMBLY.
  
 2)PROVIDE 2 CURRENT COPIES OF PRODUCT
 APPROVALS FOR GARAGE DOOR.
  
 3)PROVIDE TRUSS LAYOUT REVIEWED AND
 APPROVED BY DESIGNER OF RECORD.
  
 4)PROVIDE ORIGINAL SIGNATURE OF ENGINEER
 ON TRUSS ENGINEERING SHEETS OR PROVIDE
 TRUSS DESIGN CERTIFICATION.
  
 PLEASE SUBMIT PRIOR TO INSTALLATION.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 1999-12-20 Cont ID  
Sent By jcaloger Date 1999-12-20 Time 11:00 Rev Time 2.50
Received By jcaloger Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVIDE MANUAL CALCULATIONS WITH THE
 ENERGY CALCULATIONS.
  
 CLARIFY THE DIMENSIONS OF THE EXISTING
 FOOTERS WHICH ARE TO BE REUSED. THEY
 WILL BE REQUIRED TO COMPLY WITH SECT.
 211.6 SBC 1997 CITY WPB AMEND AND BE 4"
 ABOVE GRADE.
  
 THE CODE EDITION REFERENCED ON PLAN A4
 USED FOR THE WIND ANALYSIS IS IN VALID.
 NOTE WE ARE CURRENTLY USING THE 1997
 SBC WITH THE CWPB AMENDMENTS. RECALCULAT
 THE WIND LOADS AND RESUBMIT FOR REVIEW.
 SECT. 16 SBC 1997
  
 SPECIFY THE WIND LOADS FOR THE OVERHEAD
 GARAGE DOOR.PROVIDE PRODUCT APPROVAL
 WHICH SPECIFYS THE DOORS DESIGNED LOADS.
 SECT 16 SBC 1997.
  
 THE PRODUCT APPROVAL SUBMITTED FOR THE
 WINDOWS DOES NOT MEET THE REQUIREMENTS
 OF SECT 1707.4.1 CWPB AMEND.PRODUCTS
 ARE REQUIRED TO BE CERTIFIED BY A
 RECONIZED CERTIFICATION PROGRAM. AT THIS
 TIME THESE PROGRAMS ARE METRO-DADE OR
 SBCCI.
  
 PLANS NEED PALM BEACH COUNTY IMPACT FEE
 REVIEW.

Review Stop Z ZONING
Rev No 2 Status P Date 2000-01-31 Cont ID  
Sent By gjoyce Date 2000-01-31 Time 09:39 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 1999-12-08 Cont ID  
Sent By gjoyce Date 1999-12-08 Time 09:51 Rev Time 0.75
Received By gjoyce Date   Time   Sent To  
Notes
2001-01-08 00:00:00SPOKE W/ RICHARD, HE IS MAKING CHANGES