Plan Review Details - Permit 99111444
Plan Review Stops For Permit 99111444
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-04-05 Cont ID  
Sent By dpalmer Date 2000-04-05 Time 22:05 Rev Time 0.00
Received By dpalmer Date 2000-04-05 Time 22:05 Sent To  
Notes
2001-01-08 00:00:00NO PERMIT APPLICATION??/

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2000-03-07 Cont ID  
Sent By dpalmer Date 2000-03-07 Time 06:11 Rev Time 0.00
Received By dpalmer Date 2000-03-07 Time 06:11 Sent To  
Notes
2001-01-08 00:00:00************** UNSAT *******************
  
 NOTES ALREADY GIVEN ON THE SAME THINGS.
  
 1)NOTE:NEED TO SUBMIT THE AIC RATING OF
 THE EQUIPMENT MAINS!! MAINS ARE TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 AS REQ`D BY 110-9/110-10 OF THE NEC.
 AIC RATINGS CAN BE FIGURED FROM FAULT
 CURRENT CALCULATIONS.
  
 2)NOTE:OUTLETS IN KITCHEN ARE STILL NOT
 SHOWN AS REQ`D BY 210-52.
 EVERY 2` OF WALL SPACE 6` FROM DOOR ETC.
  
 3)NOTE: PLEASE CHECK PANEL SCHEDULE FOR
 WIRE SIZES TO MATCH OVERCURRENT
 PROTECTION.!!!
  
 PLEASE HAVE ALL THE ABOVE INFORMATION
 SUBMITTED FOR REVIEW AND APPROVAL.
 IF THERE ARE ANY QUESTIONS PLEASE CALL
 659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 1999-12-13 Cont ID  
Sent By dpalmer Date 1999-12-13 Time 05:34 Rev Time 0.00
Received By dpalmer Date 1999-12-13 Time 05:34 Sent To  
Notes
2001-01-08 00:00:00**************UNSAT *******************
  
 1)NOTE:ALL OUTLET SPACING IN KITCHEN IS
 TO BE PER ART.210-52 1,2,3,4,5.
  
 2)NOTE:AS PER 210-8-A-6 ALL OUTLETS
 SERVING KITCHEN COUNTERSPACE ARE TO BE
 GFI/GFI PROTECTED.
  
 3)NOTE:PLEASE DRAW ON ELEC. PLANS A/C
 COND. UNIT SHOWING REQ`D DISC. AND REC.
 AS PER 440-11,210-63 AND 215-5.
  
 4)NOTE:AS PER 210-52G GFI OUTLET IS REQ`
 IN GARAGE.
  
 5)NOTE:SHOW DISC. FOR A/C AIR HANDLER
 UNIT.
  
 6)NOTE: PLEASE SHOW GFI OUTLETS REQ`D
 PER 210-52E FROUNT AND BACK OF RES.
  
 7)NOTE: AS PER 1993/1996 NFPA-72
 2-2.1.1.1 SMOKE DETECTORS ARE REQ`D
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS
 IN NEW RESIDENTIAL DWELLINGS.
  
 8)NOTE:PLEASE INDICATE ON PANEL WHEATHER
 IT IS MAIN CIRCUT BRKR OR NOT. 215-5
  
 9)NOTE:NEED AIC RATING OF EQUIPMENT /
 MAINS AND BRKRS. AS PER 110-9/215-5
 AIC RATING IS FIGURED FROM FAULT CURRENT
 CALCULATIONS.
  
 10)NOTE: IF DRYER IS 4 KW THEN WHY IS
 BEING PROTECTED WITH 50 AMP BRKR.??
 MOST DRYERS ARE 5KW AND AHVE #10 WIRE
 WITH 30 AMP OVERCURRENT PROTECTION. 50A
 BRKR. IS TOO HIGH FOR 4 KW.
  
 11)PLEASE INCLUDE FRIG.IN LOAD CALC.
  
 12)NOTE:SMALL APPLIANCE CIRCUT(S) SHOW
 #14 AWG. NEEDS TO BE #12 AWG.
  
 13)NOTE:ALSO AS PER 310-16 # 14 ON
 LAUNDRY CIRCUT IS NOT LARGE ENOUGH.NEED
 TO CHANGE TO #12 AWG.
  
 14)NOTE:GEN. LIGHTING SHOW # 14 BEING
 PROTECTED WITH 20AMP BRKR. PLEASE MAKE
 CORRECTION.
  
 15)NOTE:PLEASE SHOW REQ`D DEDICATED
 CIRCUT FOR BATH(S) AS PER 210-52D.CIRCUT
 IS TO BE 20 AMP WITH # 12 WIRE.
  
 16)NOTE: AS PER 250-81/215-5 NEED TO
 SHOW BLDG.STEEL AND COLD WATER PIPE AS
 PART FO THE GROUNDING ELECTRODE SYSTEM.
 YOU SHOW 4/0 AS GROUND CONDUCTOR?? IS
 THIS CORRECT?/ CHECK 250-94 FOR SIZING
 GROUNDING ELECTRODE CONDUCTORS.
  
 17)NOTE: AS PER 215-5 NEED TO CORRELATE
 WIRE SIZES SHOWN!! RISER SHOWS 2-#4`S
 W/ 1-2/0 ?? YET BETWEEN METER AND PANEL
 YOU SHOW 3 1/0 `S?? PLEASE INDICATE WIRE
 BEING USED.
  
 PLEASE RESUBMIT THE ABOVE FOR REVIEW AND
 APPROVAL. IF THERE ARE ANY QUESTION
 PLEASE CALL:659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-05-08 Cont ID  
Sent By cthirben Date 2000-05-08 Time 14:55 Rev Time 1.00
Received By cthirben Date 2000-05-08 Time 14:55 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2000-04-10 Cont ID  
Sent By cthirben Date 2000-04-10 Time 09:05 Rev Time 1.00
Received By cthirben Date 2000-04-10 Time 08:59 Sent To  
Notes
2001-01-08 00:00:00 
  
 ****************DENIED******************
  
 1. ENERGY CACULATION SHEETS REQUIRED
 AS PER A/C INFO.
 2. SUBMIT SIZE AND WHERE EXHAUST FANS
 ARE VENTED TO.
  
 3. DRYER VENT TO BE SHOWN ON PLANS AND
 WHERE VENTED TO.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-03-13 Cont ID  
Sent By cthirben Date 1999-12-06 Time 11:22 Rev Time 0.00
Received By cthirben Date 2000-03-13 Time 11:00 Sent To  
Notes
2001-01-08 00:00:00PROVISO: INDICATE LOCATION OF RAG
 REQUIRES INFOMATION ON A/C
 INDICATE EXHAUST FAN IN BATHROOM
 RETURN AIR TO BE SHOWN ON PLANS
 SUPPLY AIR DUCT CFM QUANTITIES TO BE
 INDICATED ON PLANS

Review Stop P PLUMBING
Rev No 5 Status P Date 2001-03-19 Cont ID  
Sent By jleech Date 2001-03-19 Time 07:42 Rev Time 0.50
Received By jleech Date 2001-03-19 Time 07:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2000-06-01 Cont ID  
Sent By tlarge Date 2000-06-01 Time 19:38 Rev Time 0.33
Received By tlarge Date 2000-06-01 Time 19:38 Sent To  
Notes
2001-01-08 00:00:00PROVISO:SUBMIT SANITARY RISER THAT
 CORRELATES W/FLOOR PLAN PRIOR TO PLBG.
 INSPECTION.COUNTYWIDE AMENDMENTS TO SPC
 SEC.104.2.1.

Review Stop P PLUMBING
Rev No 3 Status F Date 2000-04-18 Cont ID  
Sent By tlarge Date 2000-04-18 Time 18:34 Rev Time 0.33
Received By tlarge Date 2000-04-18 Time 18:34 Sent To  
Notes
2001-01-08 00:00:00NOTHING HAS BEEN CORRECTED FOR PLUMBING.
 COMPLY W/ALL PREVIOUS COMMENTS PRIOR TO
 RESUBMITTING PLANS FOR REVIEW.

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-03-07 Cont ID  
Sent By tlarge Date 2000-03-07 Time 08:55 Rev Time 0.33
Received By tlarge Date 2000-03-07 Time 08:55 Sent To  
Notes
2001-01-08 00:00:00SUBMIT A SANITARY RISER FOR REVIEW THAT
 COMPLIES W/STD.PLBG.CODE AND MATCHES THE
 FLOOR PLAN.COUNTYWIDE AMENDMENTS TO SPC
 SEC.104.2.1.

Review Stop P PLUMBING
Rev No 1 Status F Date 1999-12-02 Cont ID  
Sent By tlarge Date 1999-12-02 Time 17:23 Rev Time 0.33
Received By tlarge Date 1999-12-02 Time 17:23 Sent To  
Notes
2001-01-08 00:00:00LOCATION OF FIXTURES ON SANITARY RISER
 SHALL MATCH ARCH.FLOOR PLAN.COUNTYWIDE
 AMENDMENTS TO SPC SEC.104.2.1.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2000-05-30 Cont ID  
Sent By jcaloger Date 1999-12-16 Time 07:50 Rev Time 1.00
Received By jcaloger Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVIDE A SITE PLAN.
  
 PROVIDE A UPDATED DESIGN COMPLIANCE FORM
 ATTACHED IS A COPY.
  
 SPECIFY THE WIND PRESSURES FOR THE OVER
 HEAD GARAGE DOOR OPENING AND THEN
 SPECIFY THE PROPOSED GARAGE DOOR TO BE
 INSTALLED FROM THE SBCCI PRODUCT REPORT.
  
 PROVIDE PRODUCT APPROVAL FOR THE WINDOWS
 ROOFING AND EXTERIOR SWING DOORS.
  
 SPECIFY THE ROOF SHEATHING NAILING
 REQUIREMENTS.
  
 SPECIFY THE METHOD OF ATTACHING THE
 GIRDER TRUSS TO THE BOND BEAM.
  
 SEE PLAN REVIEW COMMENTS FROM PLUMBING
 AND ELECTRIC.
  
 OWES ADDITIONAL PERMIT FEES.

Review Stop Z ZONING
Rev No 1 Status P Date 1999-12-02 Cont ID  
Sent By gjoyce Date 1999-12-02 Time 14:59 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***