| 2001-01-08 00:00:00 | **************UNSAT ******************* |
| | |
| | 1)NOTE:ALL OUTLET SPACING IN KITCHEN IS |
| | TO BE PER ART.210-52 1,2,3,4,5. |
| | |
| | 2)NOTE:AS PER 210-8-A-6 ALL OUTLETS |
| | SERVING KITCHEN COUNTERSPACE ARE TO BE |
| | GFI/GFI PROTECTED. |
| | |
| | 3)NOTE:PLEASE DRAW ON ELEC. PLANS A/C |
| | COND. UNIT SHOWING REQ`D DISC. AND REC. |
| | AS PER 440-11,210-63 AND 215-5. |
| | |
| | 4)NOTE:AS PER 210-52G GFI OUTLET IS REQ` |
| | IN GARAGE. |
| | |
| | 5)NOTE:SHOW DISC. FOR A/C AIR HANDLER |
| | UNIT. |
| | |
| | 6)NOTE: PLEASE SHOW GFI OUTLETS REQ`D |
| | PER 210-52E FROUNT AND BACK OF RES. |
| | |
| | 7)NOTE: AS PER 1993/1996 NFPA-72 |
| | 2-2.1.1.1 SMOKE DETECTORS ARE REQ`D |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS |
| | IN NEW RESIDENTIAL DWELLINGS. |
| | |
| | 8)NOTE:PLEASE INDICATE ON PANEL WHEATHER |
| | IT IS MAIN CIRCUT BRKR OR NOT. 215-5 |
| | |
| | 9)NOTE:NEED AIC RATING OF EQUIPMENT / |
| | MAINS AND BRKRS. AS PER 110-9/215-5 |
| | AIC RATING IS FIGURED FROM FAULT CURRENT |
| | CALCULATIONS. |
| | |
| | 10)NOTE: IF DRYER IS 4 KW THEN WHY IS |
| | BEING PROTECTED WITH 50 AMP BRKR.?? |
| | MOST DRYERS ARE 5KW AND AHVE #10 WIRE |
| | WITH 30 AMP OVERCURRENT PROTECTION. 50A |
| | BRKR. IS TOO HIGH FOR 4 KW. |
| | |
| | 11)PLEASE INCLUDE FRIG.IN LOAD CALC. |
| | |
| | 12)NOTE:SMALL APPLIANCE CIRCUT(S) SHOW |
| | #14 AWG. NEEDS TO BE #12 AWG. |
| | |
| | 13)NOTE:ALSO AS PER 310-16 # 14 ON |
| | LAUNDRY CIRCUT IS NOT LARGE ENOUGH.NEED |
| | TO CHANGE TO #12 AWG. |
| | |
| | 14)NOTE:GEN. LIGHTING SHOW # 14 BEING |
| | PROTECTED WITH 20AMP BRKR. PLEASE MAKE |
| | CORRECTION. |
| | |
| | 15)NOTE:PLEASE SHOW REQ`D DEDICATED |
| | CIRCUT FOR BATH(S) AS PER 210-52D.CIRCUT |
| | IS TO BE 20 AMP WITH # 12 WIRE. |
| | |
| | 16)NOTE: AS PER 250-81/215-5 NEED TO |
| | SHOW BLDG.STEEL AND COLD WATER PIPE AS |
| | PART FO THE GROUNDING ELECTRODE SYSTEM. |
| | YOU SHOW 4/0 AS GROUND CONDUCTOR?? IS |
| | THIS CORRECT?/ CHECK 250-94 FOR SIZING |
| | GROUNDING ELECTRODE CONDUCTORS. |
| | |
| | 17)NOTE: AS PER 215-5 NEED TO CORRELATE |
| | WIRE SIZES SHOWN!! RISER SHOWS 2-#4`S |
| | W/ 1-2/0 ?? YET BETWEEN METER AND PANEL |
| | YOU SHOW 3 1/0 `S?? PLEASE INDICATE WIRE |
| | BEING USED. |
| | |
| | PLEASE RESUBMIT THE ABOVE FOR REVIEW AND |
| | APPROVAL. IF THERE ARE ANY QUESTION |
| | PLEASE CALL:659-8096 EXT 8372 |