Plan Review Details - Permit 99111357
Plan Review Stops For Permit 99111357
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-01-27 Cont ID  
Sent By hpiskura Date 2000-01-27 Time 09:37 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-01-28 Cont ID  
Sent By jcaloger Date 1999-12-15 Time 16:49 Rev Time 3.50
Received By tlarge Date   Time   Sent To  
Notes
2001-01-08 00:00:00THE FOLLOWING DOORS NEED TO COMPLY WITH
 SECTION 4.13.6 OF THE FLORIDA ACCESS CDE
 HANDICAPP TOLIET B AND A, LOUNGE RM DR 2
 AND EXAM RM#1.
  
 HANDICAPP TOILET B IS REQUIRED TO HAVE
 A 60" CLEARANCE ON THE PULL SIDE.
 SECT 4.13.6 FL ACCESS CODE.
  
 SPECIFY THE REQUIRED CLEARANCES FOR THE
 FIXTURES LOCATED IN THE HANDICAPP TOILET
 SECT 4.19, 4.22, 4.16 FL ACCESS CODE
  
 THE DOOR HARDWARE FOR DOORS NUMBERS 1,3
 DOES NOT COMPLY WITH THE REQUIREMENTS OF
 SECTION 4.13 FLORIDA ACCESS CODE.
  
  
 PROVIDE CONSTRUCTION DETAILS ILLUSTRATIN
 INSTALLING THE EXTERIOR GLASS BLOCK
 AS SPECIFIED IN SECT 2112 STANDARD BUILD
 CODE.
  
 PROVIDE PRODUCT APPROVAL FOR THE NEW
 STOREFRONT. NOTE THIS OPENING WILL
 REQUIRE HURRICANE MISSLE IMPACT PROTECT.
 THE DESIGNER OF RECORD NEEDS TO SPECIFY
 THE WIND PRESURES FOR THIS OPENING.
  
 ENTRY RAMP, THE LANDING ON THE PULL SIDE
 OF THE DOORS NEEDS TO BE 60" DEEP AS
 PER FIGURE 25 FL ACC CODE.
  
 PROVIDE CONSTRUCTION DETAILS FOR THE
 ENTRY RAMP AND RAILING. SECT. 4.7 FL
 ACCESS CODE
  
 NOTE:PLANS APPROVED BY H.PISKURA.STATUS
 IN COMPUTER CHANGED BY T.LARGE IN ORDER
 TO PRINT PERMIT.1/28/00.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-12-07 Cont ID  
Sent By dpalmer Date 1999-12-07 Time 07:12 Rev Time 0.00
Received By dpalmer Date 1999-12-07 Time 07:12 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-12-01 Cont ID  
Sent By rturnque Date 1999-12-01 Time 16:07 Rev Time 0.20
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-12-15 Cont ID  
Sent By ndenmark Date 1999-12-15 Time 07:13 Rev Time 0.25
Received By ndenmark Date 1999-12-15 Time 07:13 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 ALL A/C UNITS TO BE SHUT DOWN BY DUCT
 SMOKE DETECTOR

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-01-27 Cont ID  
Sent By tlarge Date 2000-01-27 Time 17:20 Rev Time 0.75
Received By tlarge Date 2000-01-27 Time 17:20 Sent To  
Notes
2001-01-08 00:00:00*************PROVISO********************
 NEW TOILET ROOMS SHALL HAVE FLOOR DRAINS
 SPC 409.4.1.1.

Review Stop P PLUMBING
Rev No 2 Status N Date 2000-01-27 Cont ID  
Sent By tlarge Date 2000-01-12 Time 12:56 Rev Time 0.65
Received By tlarge Date 2000-01-12 Time 12:56 Sent To  
Notes
2001-01-08 00:00:00A DRINKING FOUNTAIN IS REQD.ON THE 2ND.
 FLR.AND IS REQD.TO BE ACCESSIBLE PER SPC
 TABLE 407 AND FACBC SEC.4.1.3.(10)(A).
  
 SQ.FOOTAGE AND OCCUPANT LOAD SHALL BE
 SHOWN ON THE PLAN PER SPC 407.1.3 AND
 COUNTYWIDE AMENDMENTS TO SPC.104.2.1.
  
 DELETE "STAFF TOILET" LABEL FROM TOILET
 ROOM FOR COMPLIANCE TO TABLE 407 OF SPC.
  
 MOUNTING HEIGHT OF TP DISPENSER REQD.PER
 FACBC SEC.4.16.6,FIGURE 29(B).
  
 WATER SUPPLY CONTROL SHALL COMPLY W/SPC
 610.4.2.
  
 SINK FOR 2ND FLR NOT SHOWN ON WATER
 RISER.CLARIFY.

Review Stop P PLUMBING
Rev No 1 Status N Date 2000-01-27 Cont ID  
Sent By tlarge Date 1999-12-03 Time 06:14 Rev Time 0.75
Received By tlarge Date 1999-12-03 Time 06:14 Sent To  
Notes
2001-01-08 00:00:00LOUNGE SINK SHALL COMPLY W/FACBC SEC.
 4.24.1-4.24.7.
  
 TYPE AND NUMBER OF PLBG.FIXTURES SHALL
 COMPLY W/SPC SEC.407.
  
 DRINKING FOUNTAIN SHALL COMPLY W/FACBC
 SEC.4.1.3(10)(A).
  
 SUBMIT MOUNTING HEIGHT DETAILS FOR H.C.
 FIXTURES AND APPURTENANCES.COMPLY W/
 FACBC OCT.1,1997 EDITION.
  
 CLEARLY SHOW MIN.REQD.WHEELCHAIR TURNING
 SPACE INSIDE TOILET ROOMS.COMPLY W/FACBC
 SEC.4.2.3.
  
 SUBMIT WATER RISER FOR REVIEW PER COUNTY
 WIDE AMENDMENTS TO SPC SEC.104.2.1.
  
 PLANS SHOW DARK ROOM.CLEARLY INDICATE
 IF A X-RAY PROCESSOR WILL BE INSTALLED
 AND IF SO SUBMIT MANUF.SHEETS FOR UNIT
 AND DETAILS FOR THE PROPER DISPOSAL OF
 ANY CHEMICALS BEING USED.