Plan Review Details - Permit 99111317
Plan Review Stops For Permit 99111317
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-02-12 Cont ID  
Sent By dpalmer Date 2000-02-12 Time 08:22 Rev Time 0.00
Received By dpalmer Date 2000-02-12 Time 08:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-12-09 Cont ID  
Sent By dpalmer Date 1999-12-09 Time 06:55 Rev Time 0.00
Received By dpalmer Date 1999-12-09 Time 06:55 Sent To  
Notes
2001-01-08 00:00:00*************PROVISO*******************
  
 1)NOTE: NEED TO SUBMIT AIC RATING ON
 ALL PLANS FOR EQUIPMENT MAINS/BRKRS AS
 REQ`D BY 110-9/215-5. AIC RATING IS
 FIGURED FROM FAULT CURRENT CALCULATIONS.
  
 2)NOTE:NEED TO INCLUDE BLDG.STEEL AS
 PART OF THE GROUNDING ELECTRODE SYSTEM.
 AS PER 250-81
  
 3)NOTE:AS REQ`D BY NEC EQUIPMENT GROUND-
 -ING BETWEEN MAIN DISC. AND PANEL. SIZE
 PER 250-95
  
 4)NOTE: AS PER 210-52D/215-5 NEED TO
 SHOW DEDICATED BATH(S) 20AMP CIRCUT ON
 PANEL SCHEDULE.
  
 PLEASE SUBMIT THE ABOVE INFORNMATION
 FOR REVIEW AND APPROVAL BEFORE FIRST
 ROUGH ELECTRICAL INSPECTION IS CALLED IN
 IF THERE ARE ANY QUESTIONS PLEASE CALL;
 659-8096 EXT.8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-12-06 Cont ID  
Sent By cthirben Date 1999-12-06 Time 14:44 Rev Time 1.00
Received By cthirben Date 1999-12-06 Time 14:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-02-26 Cont ID  
Sent By tlarge Date 2000-02-26 Time 06:45 Rev Time 0.30
Received By tlarge Date 2000-02-26 Time 06:45 Sent To  
Notes
2001-01-08 00:00:00PLBG.NOT AFFECTED THIS REVISION.

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-12-02 Cont ID  
Sent By tlarge Date 1999-12-02 Time 18:41 Rev Time 0.33
Received By tlarge Date 1999-12-02 Time 18:41 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 1999-12-21 Cont ID  
Sent By jgomez Date 1999-12-21 Time 13:05 Rev Time 2.00
Received By jgomez Date 1999-12-21 Time 13:05 Sent To  
Notes
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-ENTRY EGRESS DOOR TO HAVE 32" MIN.
 CLEAR OPENING. TABLE 1004 SBC 1997.
 2-PROVIDE PRODUCT APPROVAL FOR: ENTRY
 DOORS WITH TRANSOM ABOVE ASSEMBLY,
 SLIDING GLASS DOORS WITH TRANSOM ABOVE
 ASSEMBLY. (NOTE: SLIDING GLASS DOORS
 TO BE THE REINFORCED TYPE, IN ORDER TO
 MEET THE DESIGN PRESSURES CALCULATED
 BY THE ARCHITECT.
 3-UPDATE THE DESIGN CERTIFICATION FOR
 BUILDING CODE COMPLIANCE FORM.
 4-TRUSS DRAWINGS:
 -PROVIDE UPDATED ENGINEERED TRUSS
 DRAWINGS USING SBC 1997 ONLY (NOT SBC
 1991 OR 1994) OR ASCE-7-95.
 -DESIGNER OF RECORD TO REVIEW ALL TRUSS
 DRAWINGS PRIOR TO SUBMITTAL.
 5-STORM PANELS:
 -PROVIDE A COMPLETE INSTALLATION
 SCHEDULE AS PER CITY SAMPLE.
 -STORM PANEL DRAWINGS DON'T MATCH
 PRODUCT APPROVAL NUMBER.
 6-CHECK/CLARIFY IF CANTILEVERED BEAM AT
 BREAKFAST AREA IS SUPPOSE TO CARRY THE
 LOAD OF TRUSS GIRDER AT ENTRY PORCH
 AND THE ROOF TRUSSES ABOVE OR IF ROOF
 TRUSSES ARE RESTING ON THE EXTERIOR
 CMU WALL. SEE ROOF FRAMING PLAN.
 PROVIDE ENGINEERED CALCULATIONS FOR
 STRUCTURAL STABILITY OF CANTILEVERED
 BEAM. SEC 104.2.2 CITY AMENDMENTS TO
 SBC 1997.

Review Stop Z ZONING
Rev No 1 Status P Date 1999-12-01 Cont ID  
Sent By gjoyce Date 1999-12-01 Time 09:56 Rev Time 0.50
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***