Plan Review Details - Permit 99111246
Plan Review Stops For Permit 99111246
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2000-03-22 Cont ID  
Sent By lmartine Date 2000-03-22 Time 10:52 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2000-02-24 Cont ID  
Sent By lmartine Date 2000-02-24 Time 07:22 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 1900-02-01 Cont ID  
Sent By lmartine Date 1900-02-01 Time 07:21 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 1999-12-14 Cont ID  
Sent By jcaloger Date 1999-12-14 Time 16:26 Rev Time 2.00
Received By jcaloger Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLAN A21,SPECIFY THE TYPE OCCUPANCY
 AND CONSTRUCTION TYPE AS DEFINED BY THE
 1997 STANDARD BUILDING CODE.
  
 THE ENTRY TO THE HANDICAPP TOILETS NEEDS
 TO COMPLY WITH SECT 4.13.6 FLORIDA
 HANDICAPP CODE FOR FRONT APPROCHES.
 18" CLEARANCE REQUIRED ON EACH SIDE OF
 THE DOOR.
  
 THE KEY PLAN NEEDS TO LOCATE THE
 SPECIFIC LOCATION OF THE OFFICE SPACE.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-12-07 Cont ID  
Sent By dpalmer Date 1999-12-07 Time 14:57 Rev Time 0.00
Received By dpalmer Date 1999-12-07 Time 14:57 Sent To  
Notes
2001-01-08 00:00:00**********PROVISO*****************
  
 NEED TO SUBMIT AIC RATING OF EQUIPMENT
 MAINS/PANEL. SUBMIT FOR REVIEW AND APP.
 BEFORE ROUGH ELEC.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-11-23 Cont ID  
Sent By rturnque Date 1999-11-23 Time 11:57 Rev Time 0.20
Received By rturnque Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVIDE PERMIT AND SHOP DRAWINGS FOR
 FIRE ALARM AND FIRE SPRINKLER SYSTEM

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-12-09 Cont ID  
Sent By ndenmark Date 1999-12-09 Time 10:18 Rev Time 0.33
Received By ndenmark Date 1999-12-09 Time 10:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status P Date 2000-03-17 Cont ID  
Sent By tlarge Date 2000-03-17 Time 15:24 Rev Time 0.65
Received By tlarge Date 2000-03-17 Time 15:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2000-03-06 Cont ID  
Sent By tlarge Date 2000-03-06 Time 11:08 Rev Time 0.50
Received By tlarge Date 2000-03-06 Time 11:08 Sent To  
Notes
2001-01-08 00:00:00 
 ADDITIONAL PLBG.FIXTURES REQD.FOR FEMALE
 OCCUPANTS PER TABLE 407 OF SPC.

Review Stop P PLUMBING
Rev No 3 Status F Date 2000-02-20 Cont ID  
Sent By tlarge Date 2000-02-20 Time 11:21 Rev Time 0.50
Received By tlarge Date 2000-02-20 Time 11:20 Sent To  
Notes
2001-01-08 00:00:00BASED ON THE SQUARE FOOTAGE OF THE SPACE
 AND TABLE 407 OF THE STANDARD PLUMBING
 CODE THE OCCUPANT LOAD IS 21 PEOPLE.
 (BASED ON HABITABLE FLOOR SPACE.SEE SPC
 SEC.407.1.3 FOR ALLOWABLE DEDUCTION OF
 SPECIFIC AREAS AND COMPONENTS).THE MIN.
 REQD.NUMBER OF SANITARY FACILITIES SHALL
 BE:MALES-1 WATER CLOSET,1-LAVATORY.
 FEMALES-2 WATER CLOSETS,2-LAVATORIES.
 DRINKING FOUNTAIN-1.
 SUBMIT CALCULATIONS SHOWING SQUARE FOOT-
 AGE OF ALLOWED DEDUCTIBLE AREAS AND
 HABITABLE FLOOR SPACE.HABITABLE FLOOR
 SPACE SHALL NOT EXCEED 1300 SQ.FEET TO
 COMPLY W/NOTED OCCUPANT LOAD OF 13
 PERSONS.
  
 WATER HEATER SHALL BE READILY ACCESSIBLE
 PER SPC SEC.501.7.SUPPLY FIXED LADDER OR
 RELOCATE EWH TO FLOOR.CLEARLY SHOW HOW
 EWH COMPLIES W/THIS CODE SECTION-PLANS
 ARE VAGUE.

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-02-01 Cont ID  
Sent By tlarge Date 2000-02-01 Time 16:22 Rev Time 0.00
Received By tlarge Date 2000-02-01 Time 16:21 Sent To  
Notes
2001-01-08 00:00:00COMPLY W/ALL PREVIOUS COMMENTS DATED
 11/27/99.
  
 PER TABLE 407 OF SPC THE MIN.REQD.
 SANITARY FACILITIES ARE:
 MALES-1 WATER CLOSET,1 LAVATORY.
 FEMALES-2 WATER CLOSETS,2 LAVATORIES.
 1 DRINKING FOUNTAIN IS REQD.
  
 DRINKING FOUNTAIN SHALL COMPLY W/FACBC
 SEC.4.1.3(10)(A).
  
 FLOOR DRAINS ARE REQD.IN THE TOILET
 ROOMS PER SPC SEC.409.4.1.1.(EXCEPTION)
  
 STRUCTURE SHALL COMPLY W/FACBC SEC.6.1
 (2).-ALL PUBLIC AND COMMON USE AREAS ARE
 REQUIRED TO BE DESIGNED AND CONSTRUCTED
 TO BE ACCESSIBLE.

Review Stop P PLUMBING
Rev No 1 Status F Date 1999-11-27 Cont ID  
Sent By tlarge Date 1999-11-27 Time 12:37 Rev Time 0.75
Received By tlarge Date 1999-11-27 Time 12:37 Sent To  
Notes
2001-01-08 00:00:00DELETE REFERENCE TO S.F.B.C.PER COUNTY-
 WIDE AMENDMENTS TO STD.PLBG.CODE SEC.101
  
 THE NUMBER AND TYPE OF REQD.PLUMBING
 FIXTURES SHALL COMPLY W/TABLE 407 OF SPC
  
 WATER HEATER SHALL BE READILY ACCESSIBLE
 SUPPLY FIXED LADDER AND PLATFORM OR
 RELOCATE EWH TO FLOOR.SPC 501.7.
  
 DRAINAGE PIPING 2 1/2" & LESS SHALL BE
 INSTALLED AT 1/4/" PER FT.SLOPE PER SPC
 SEC.705.2
  
 CLEARLY SHOWSQ.FOOTAGE OF SPACE.REFER
 TO TABLE 407 FOR OCCUPANT LOAD REQS.
 SEE COMMENT #2.