Plan Review Details - Permit 99111227
Plan Review Stops For Permit 99111227
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 1999-12-16 Cont ID  
Sent By fknapp Date 1999-12-16 Time 13:43 Rev Time 3.00
Received By fknapp Date   Time   Sent To  
Notes
2001-01-08 00:00:00 
 ***************NOTE*********************
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED,IMPACT FEES MUST BE PAID TO PALM
 BEACH CO.,THE PERMIT PLANS STAMPED BY
 THEM AND THE RECIEPT ATTACHED TO THE
 PERMIT APPLICATION

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-03-14 Cont ID  
Sent By dpalmer Date 2000-03-14 Time 20:36 Rev Time 0.00
Received By dpalmer Date 2000-03-14 Time 20:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-12-16 Cont ID  
Sent By dpalmer Date 1999-12-16 Time 11:24 Rev Time 0.00
Received By dpalmer Date 1999-12-16 Time 11:24 Sent To  
Notes
2001-01-08 00:00:00**************PROVISO******************
  
 1)NOTE:PLEASE SUBMIT AIC RATING OF
 EQUIPMENT MAINS.AS PER 110-9/215-5
  
 2)NOTE: PLEASE SHOW ROOF TOP REC REQ`D
 AS PER 210-63.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW AND APPROVAL BEFORE FIRST ROUGH
 ELECTRICAL INSPECTION IS CALLED IN.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-12-03 Cont ID  
Sent By rturnque Date 1999-12-03 Time 14:28 Rev Time 0.15
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 1999-12-23 Cont ID  
Sent By tlarge Date 1999-12-23 Time 13:36 Rev Time 0.50
Received By tlarge Date 1999-12-23 Time 13:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 1999-12-23 Cont ID  
Sent By tlarge Date 1999-11-29 Time 09:11 Rev Time 1.50
Received By tlarge Date 1999-11-29 Time 09:11 Sent To  
Notes
2001-01-08 00:00:00CLEARLY SHOW REQD. WHEELCHAIR TURNING
 SPACE(MIN.60" DIAM.)OR T-SHAPED SPACE IN
 H.C.TOILET STALL PER FACBC SEC.4.2.3.
  
 DRINKING FOUNTAIN SHALL COMPLY W/FACBC
 SEC.4.1.3.(10)(A).CLEARLY SHOW
 COMPLIANCE ON PLANS.
  
 SUBMIT A WATER RISER DIAGRAM FOR REVIEW
 PER COUNTYWIDE AMENDMENTS TO STD.PLBG.
 CODE SEC.104.2.1.
  
 SIZE ALL VENTS ON SAN.RISER.COMPLY W/
 SPC TABLE 920.2.
  
 DRINKING FOUNTAIN SHALL BE STACKED AND
 VENTED.SPC SEC.901.2.
  
 FLOOR DRAINS ARE REQD.IN THE RESTROOMS
 PER SPC SEC.409.4.1.1.
  
 URINALS SHALL BE SHOWN ON THE PLBG.RISER
  
 FLOORS AND WALLS IN RESTROOMS SHALL BE
 NON-ABSORBMENT TO A HEIGHT OF 4'PER SBC
 SEC.1204.2
  
 SUBMIT DETAILS FOR HANDICAP FIXTURES.
 (MOUNTING HEIGHTS,FIXTURE CLEARANCES,ETC
  
 SUBMIT OCCUPANT LOAD BASED ON SQ.FOOTAGE
 OF SPACE .COMPLY W/SPC TABLE 407 FOR
 NUMBER AND TYPE OF FIXTURES REQD.
  
 WATER CLOSETS NOT PERMITTED ON WET VENTS
 PER COUNTYWIDE AMENDMENTS TO STD.PLBG.
 CODE SEC.911.1.1.

Review Stop Z ZONING
Rev No 1 Status P Date 1999-12-16 Cont ID  
Sent By gjoyce Date 1999-12-16 Time 13:25 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***